Rev 2.0 DVM S Advance Service & Troubleshooting Due to Samsung’s policy of ongoing product development, specifications
Views 92 Downloads 3 File size 6MB
Rev 2.0
DVM S Advance Service & Troubleshooting Due to Samsung’s policy of ongoing product development, specifications are subject to change without prior notice. Every effort has been made to insure that the information included in this presentation is as accurate as possible at the time of it’s publication. This presentation is provided as a guide to help HVAC field technicians understand the most common service and diagnostic procedures for the Samsung DVMS VRF systems. This training module is not intended to replace Samsung service manuals, technical data books, installation/operation manuals or other factory documents. Only properly trained, HVAC professionals should attempt to install and service any Samsung heating and airconditioning system. High Voltage Caution: Extra care must be taken when working on or around DVM S equipment due to numerous high voltage components. Whether installing or servicing DVM S equipment in the field or while attending Samsung HVAC training classes which include powered simulators and equipment, be aware of the potential dangers of high voltage – use caution This presentation may only be used with authorization by Samsung HVAC. Unauthorized use, duplication or alteration of this presentation is prohibited. For technical support issues, always contact your Samsung equipment provider. www.samsunghvac.com
www.schoox.com/login.php
www.dvmdownload.com
2
Advance Service & Troubleshooting TOPICS Basic System Operation Heat Pump Introduction Heat Recovery Introduction Indoor Unit (IDU) Control Outdoor Unit (ODU) Control Heat Pump Refrigerant Circuit Heat Recovery Refrigerant Circuit 3
DVM S Basic System Operation
Basic System Operation Indoor Unit Control – On/Off ODU Status IDU Status
RC Status
Turn on
Refrigerant flowing F3/F4 comm.
Thermo on ON
ON
ON
Turn on
Refrigerant stop F3/F4 comm.
OFF
ON
Thermo off ON
Refrigerant stop
Turn off
F3/F4 comm.
OFF
OFF
OFF
5
Basic System Operation Outdoor Unit Control – On/Off
OFF
OFF
OFF
OFF
OFF
OFF
OFF
ON
Any indoor unit in a “thermo on” condition will start the outdoor unit
OFF
OFF
OFF
Example: IDU is ON but the EEV is closed (Thermo Off) – ODU is OFF
OFF
ON *Thermo on
OFF
OFF
ON
*Thermo on
ON *Thermo off
ON *Thermo off
OFF
ON
6
Basic System Operation Outdoor Unit Capacity Control 18,000 Btu/h
18,000 Btu/h
18,000 Btu/h
OFF
OFF
OFF
18,000 Btu/h
ON
Outdoor unit target capacity
ON
18,000 Btu/h
ON
54,000 Btu/h
ON
18,000 Btu/h
*Thermo on 18,000 Btu/h
ON
18,000 Btu/h
18,000 Btu/h
ON
OFF
*Thermo on
*Thermo on
18,000 Btu/h
18,000 Btu/h
ON *Thermo off
ON
*Thermo on
18,000 Btu/h
ON
*Thermo on 18,000 Btu/h
18,000 Btu/h
OFF
ON *Thermo off
7
Basic System Operation Operating Temperature Range For Outdoor Unit Start
When ambient temperature is out of range, the system will not start and generates error E440 – Prevention of heat operation E441 – Prevention of cool operation
System checks ambient temperature condition only on outdoor unit (compressor) start up The DVM S outdoor units will operate when ambient temperatures are exceeded however capacity and efficiency will decrease accordingly -13°F 23°F Cooling start prohibited Outdoor temperature
Cooling operation area -5~48℃(23~120℉) Heating operation area
Heating start prohibited
-20~24℃(-4~75 ℉) 75°F
86°F
8
DVM S VRF Heat Pump Introduction
Heat Pump Introduction Heat Pump Outdoor Unit OD Fan
Control Box Control Box
OD Fans
OD Heat Exchanger
OD Heat Exchanger
4-WAY V/V
4-WAY V/V
Accumulator
Accumulator
Subcooler
Subcooler
Compressor Gas V/V
Liquid V/V
Oil Separator
Oil Separator Gas V/V
Liquid V/V
Compressor
10
Heat Pump Introduction
Name
Heat Pump Refrigerant Circuit – Single Fan 1 compressor unit
SV_G
OFM
T_A T_CO
OHX
T_S
CV_E
HPS
E
V_4W
V_EB s T_EO
CV_D
E_M
T_EI E
IC
E_EV
OS HPSW
T_D s
T_CT
INV
V_HG
LPS
CH
AC
IPMC T_L
V_ES
s V_AR
SV_L
INV OFM OHX AC OS IC IPMC CH HPS LPS HPSW E_M E_EV V_ES V_EB V_HG V_4W V_AR CV_E CV_D T_D T_S T_CO T_EI T_EO T_L T_CT T_A SV_G SV_L
Inverter Compressor Outdoor Fan Motor Outdoor Heat Exchanger Accumulator Oil Separator Intercooler IPM Cooler Crank Case Heater High Pressure Sensor Low Pressure Sensor High Pressure Switch Main EEV EVI EEV EVI Sol. Valve EVI Bypass Valve Hot Gas Bypass Valve 4Way Valve Accumulator Oil Return Valve EEV Bypass Check Valve Discharge Check Valve Discharge Temp. Sensor Suction Temp. Sensor Cond Out Temp. Sensor EVI In Temp. Sensor EVI Out Temp. Sensor Liquid Tube Temp. Sensor Comp. Top Temp. Sensor Ambient Temp. Sensor Gas Pipe Service Valve Liquid Pipe Service Valve
12
Heat Pump Introduction Heat Pump Refrigerant Circuit – Dual Fan 1 compressor unit
OFM
SV_G
OFM
T_A T_C O
OHX
T_S
CV_E
HPS
V_EB s
CV_D
E
V_4W
T_EO
E_M
T_EI E
IC
E_EV
OS HPSW
T_D
V_HG s
T_CT
INV
LPS
CH
AC
IPMC
T_L V_ES
sV_AR
SV_L
INV OFM OHX AC OS IC IPMC CH HPS LPS HPSW E_M E_EV V_ES V_EB V_HG V_4W V_AR CV_E CV_D T_D T_S T_CO T_EI T_EO T_L T_CT T_A SV_G SV_L
Name Inverter Compressor Outdoor Fan Motor Outdoor Heat Exchanger Accumulator Oil Separator Intercooler IPM Cooler Crank Case Heater High Pressure Sensor Low Pressure Sensor High Pressure Switch Main EEV EVI EEV EVI Sol. Valve EVI Bypass Valve Hot Gas Bypass Valve 4Way Valve Accumulator Oil Return Valve EEV Bypass Check Valve Discharge Check Valve Discharge Temp. Sensor Suction Temp. Sensor Cond Out Temp. Sensor EVI In Temp. Sensor EVI Out Temp. Sensor Liquid Tube Temp. Sensor Comp. Top Temp. Sensor Ambient Temp. Sensor Gas Pipe Service Valve Liquid Pipe Service Valve
13
Heat Pump Introduction Heat Pump Refrigerant Circuit – Dual Fan 2 compressor unit SV_G OFM
T_A T_CO
OHX
OS
IC
OS
T_EI
V_EB s T_EO
HPSW
E_EV
T_D V_HG
INV
s
T_D T_CT INV
CH
CV_D
E
T_CT
IPMC
IPMC
CV_D
E_M
T_S
HPS
HPSW
E
CV_E V_4W
LPS
CH
T_L s
V_ES
AC
V_ES
V_AR
SV_L
INV OFM OHX AC OS IC IPMC CH HPS LPS HPSW E_M E_EV V_ES V_EB V_HG V_4W V_AR CV_E CV_D T_D T_S T_CO T_EI T_EO T_L T_CT T_A SV_G SV_L
Name Inverter Compressor Outdoor Fan Motor Outdoor Heat Exchanger Accumulator Oil Separator Intercooler IPM Cooler Crank Case Heater High Pressure Sensor Low Pressure Sensor High Pressure Switch Main EEV EVI EEV EVI Sol. Valve EVI Bypass Valve Hot Gas Bypass Valve 4Way Valve Accumulator Oil Return Valve EEV Bypass Check Valve Discharge Check Valve Discharge Temp. Sensor Suction Temp. Sensor Cond Out Temp. Sensor EVI In Temp. Sensor EVI Out Temp. Sensor Liquid Tube Temp. Sensor Comp. Top Temp. Sensor Ambient Temp. Sensor Gas Pipe Service Valve Liquid Pipe Service Valve
14
Heat Pump Introduction Part Introduction – Major Components
E IPM2 IPM1
3 4 2 2
2
2
1
1
1
4
s
1
3 E
s
s
Name
Description
Compressors
1
Oil separator
2
Intercooler
3
Accumulator
4
■ 2 types of inverter compressors ■ Vapor injection compressor & Flash injection compressor When compressor operates, oil is discharged from the compressors. To maintain proper compressor oil level. 1. To secure sub-cooling, 2. Vapor injection To protect the compressor from liquid flood back operation, the accumulator collects liquid refrigerant and allows only the gas to enter the compressor.
15
Heat Pump Introduction Part Introduction – Valve & EEV 5
3
2
1
3
IPM2
IPM1
4
7
E
2
6
7
Name
Type
4
s
1
E
5 s
s 6
Function
Hot gas bypass valve
1
Solenoid
To compensate severe low pressure drop.
4way valve
2
Solenoid
To change operation mode of cooling and heating operation.
Main EEV
3
Stepper Motor
To control refrigerant flow rate in heating operation.
EVI EEV
4
Stepper Motor
To control refrigerant flow rate for sub-cooling.
5 EVI bypass valve Accumulator Oil Return Valve 6 7 EVI Sol valve
Solenoid Solenoid
To supply vapor refrigerant to compressor suction. To recover oil from accumulator.
Solenoid
To inject vapor into the compressor scroll.
16
Heat Pump Introduction Part Introduction – Sensor & Switch 4
5 6
10
11 2
4
3
1
2
6 3 2
1
s
2
8
9
1 s
5
3
E
1
IPM2 IPM1
7
E
10 9 83
7 s
Name
Type
Name
Type
Discharge temp. sensor
1
200K ohm
Tube temp. sensor
7
10K ohm
Top temp. sensor
2
200K ohm
EVI in sensor
8
10K ohm
High pressure switch
3
-
EVI out sensor
9
10K ohm
High pressure sensor
4
-
Suction temp. sensor
10
10K ohm
Ambient air temp. sensor
5
10K ohm
Low pressure sensor
11
-
Cond. out temp. sensor
6
10K ohm
17
Heat Pump Introduction Part Introduction – Sensor & Switch Name
Type
Discharge temp. sensor
200K ohm
To sense compressor discharge gas temperature
Ambient temp. sensor
10K ohm
To sense outside ambient temperature
Cond_out temp. sensor
10K ohm
To sense condensing outlet temperature.
EVI in/out temp. sensor
10K ohm
To sense the temperature of vapor injection refrigerant
Liquid tube temp. sensor
10K ohm
To sense the sub-cooled refrigerant temperature.
Suction temp. sensor
10K ohm
To Sense compressor suction gas temperature
Name
Description
Description
Output
High pressure sensor
To sense high pressure. To control fan RPM in cooling operation. To control compressor capacity in heating operation.
DC voltage 0 ~4.5V
Low pressure sensor
To sense low pressure temperature To control compressor capacity in cooling operation To control fan RPM in heating operation
DC voltage 0 ~4.5V
18
DVM S VRF Heat Recovery Introduction
Heat Recovery Introduction Heat Recovery Refrigerant Circuit – 1 Fan 1 compressor unit CV_MC s
CV_H
SV_HG
OFM
T_A
V_MC
T_CO
OHX
s
s
V_OE
V_HG2
E
CV_E
T_S1
V_4W
E_M
HPS V_EB s
CV_D
SV_LG
T_EO
OS HPSW
E_EV
T_S2 IPMC
T_D
T_CT
T_EI E
IC
V_HG1 s
INV
LPS
AC T_L
CH V_ES
s V_AR
SV_L
INV OFM OHX AC / OS IC / IPMC CH HPS LPS HPSW E_M / E_EV V_MC V_ES V_EB V_HG1 V_HG2 V_4W V_AR V_OE CV_E CV_D CV_H CV_MC T_D T_S1 T_S2 T_CO T_EI T_EO T_L T_CT T_A SV_HG SV_LG SV_L
Name Inverter Compressor Outdoor Fan Motor Outdoor Heat Exchanger Accumulator / Oil Separator Intercooler / IPM Cooler Crank Case Heater High Pressure Sensor Low Pressure Sensor High Pressure Switch Main EEV / EVI EEV Main Cooling Valve EVI Sol. Valve EVI Bypass Valve Hot Gas Bypass Valve 1 Hot Gas Bypass Valve 2 4Way Valve Accumulator Oil Return Valve Outdoor EEV Valve EEV Bypass Check Valve Discharge Check Valve HR Check valve Main Cooling Check Valve Discharge Temp. Sensor Suction Temp. Sensor 1 Suction Temp. Sensor 2 Cond Out Temp. Sensor EVI In Temp. Sensor EVI Out Temp. Sensor Liquid Tube Temp. Sensor Comp. Top Temp. Sensor Ambient Temp. Sensor High Gas Pipe Service Valve Low Gas Pipe Service Valve Liquid Pipe Service Valve
20
Heat Recovery Introduction Heat Recovery Refrigerant Circuit – 2 Fan 1 compressor unit
CV_MC s
CV_H
SV_HG
OFM
OFM
T_A
V_MC
T_CO
OHX
s
s
V_OE
V_HG2
E
CV_E
T_S
V_4W
E_M
HPS V_EB s
CV_D
SV_LG
T_EO
OS HPSW
E_EV
T_S2
T_D
T_CT
IPMC
V_HG1 s
INV
T_EI E
IC
LPS
AC T_L
CH
V_ES
s V_AR
SV_L
INV OFM OHX AC / OS IC / IPMC CH HPS LPS HPSW E_M / E_EV V_MC V_ES V_EB V_HG1 V_HG2 V_4W V_AR V_OE CV_E CV_D CV_H CV_MC T_D T_S1 T_S2 T_CO T_EI T_EO T_L T_CT T_A SV_HG SV_LG SV_L
Name Inverter Compressor Outdoor Fan Motor Outdoor Heat Exchanger Accumulator / Oil Separator Intercooler / IPM Cooler Crank Case Heater High Pressure Sensor Low Pressure Sensor High Pressure Switch Main EEV / EVI EEV Main Cooling Valve EVI Sol. Valve EVI Bypass Valve Hot Gas Bypass Valve 1 Hot Gas Bypass Valve 2 4Way Valve Accumulator Oil Return Valve Outdoor EEV Valve EEV Bypass Check Valve Discharge Check Valve HR Check valve Main Cooling Check Valve Discharge Temp. Sensor Suction Temp. Sensor 1 Suction Temp. Sensor 2 Cond Out Temp. Sensor EVI In Temp. Sensor EVI Out Temp. Sensor Liquid Tube Temp. Sensor Comp. Top Temp. Sensor Ambient Temp. Sensor High Gas Pipe Service Valve Low Gas Pipe Service Valve Liquid Pipe Service Valve
21
Heat Recovery Introduction Heat Recovery Refrigerant Circuit – Dual Fan 2 compressor unit SV_HG CV_MC
OFM
s
V_MC
CV_H
T_A T_CO
OHX
s E_M
CV_E V_4W
s
E
V_OE
V_HG2
T_S
INV OFM OHX AC / OS IC / IPMC CH HPS LPS HPSW E_M / E_EV V_MC V_ES V_EB V_HG1 V_HG2 V_4W V_AR
HPS CV_D OS
T_CT
OS
T_S2
HPSW T_D T_D T_CT
s
LPS
CH
T_EO
T_EI
IC
SV_LG
AC T_L
s V_ES
V_EB s
E_EV
V_HG
INV
INV CH
CV_D
E
HPSW
IPMC
IPMC
V_ES
V_AR
SV_L
V_OE CV_E CV_D CV_H CV_MC T_D T_S1 T_S2 T_CO T_EI T_EO T_L T_CT T_A SV_HG SV_LG SV_L
Name Inverter Compressor Outdoor Fan Motor Outdoor Heat Exchanger Accumulator / Oil Separator Intercooler / IPM Cooler Crank Case Heater High Pressure Sensor Low Pressure Sensor High Pressure Switch Main EEV / EVI EEV Main Cooling Valve EVI Sol. Valve EVI Bypass Valve Hot Gas Bypass Valve 1 Hot Gas Bypass Valve 2 4Way Valve Accumulator Oil Return Valve Outdoor EEV Valve EEV Bypass Check Valve Discharge Check Valve HR Check valve Main Cooling Check Valve Discharge Temp. Sensor Suction Temp. Sensor 1 Suction Temp. Sensor 2 Cond Out Temp. Sensor EVI In Temp. Sensor EVI Out Temp. Sensor Liquid Tube Temp. Sensor Comp. Top Temp. Sensor Ambient Temp. Sensor High Gas Pipe Service Valve Low Gas Pipe Service Valve Liquid Pipe Service Valve
22
Heat Recovery Introduction Part Introduction – Major Components s s s
E
4 3 2 2
2
3 E
s s
1
2
1
1
4
1 s
Name
Description
Compressors
1
Oil separator
2
Intercooler
3
Accumulator
4
■ 2 types of inverter compressors ■ Vapor injection compressor & Flash injection compressor When compressor operates, oil is discharged from the compressors. To maintain proper compressor oil level. 1. To secure sub-cooling, 2. Vapor injection To protect the compressor from liquid flood back operation, the accumulator collects liquid refrigerant and allows only the gas to enter the compressor.
23
Heat Recovery Introduction Part Introduction – Valve & EEV s
5
s
4
5
8
E
6
s
3
4
2
3
1
2 7
E
6 s 1 s
8
Name Hot gas bypass valve 1 Hot gas bypass valve 2 4way valve Main cooling valve Outdoor EEV valve EVI bypass valve Accumulator Oil Return Valve EVI Sol valve
1 2 3 4 5 6 7 8
Type Solenoid Solenoid Solenoid Solenoid Stepper Motor Solenoid Solenoid Solenoid
s 7
Function To compensate severe low pressure drop. To equalize high & low pressure on unit stop To change Heat/Cool operation mode – Energizes for heat operation. To supply refrigerant to heating indoor unit in main cooling operation. To control refrigerant flow rate in main cooling operation. To supply vapor refrigerant to compressor suction. To recover oil from accumulator. To inject vapor to scroll.
24
Heat Recovery Introduction Part Introduction – Valve & EEV
s s
s
E
1
2 1 E
s
2
s s
Name Outdoor main EEV EVI EEV
Type
Function
1 Stepper Motor To control refrigerant flow rate in heating operation. 2 Stepper Motor To control refrigerant flow rate for sub-cooling.
25
Heat Recovery Introduction Part Introduction – Sensor & Switch 5 s
6
4
s
10
s
E
11 9 8 3 7 2
10 4
12
3 2
11
6 1
3
5
1
8
9
s
2
s
E
1
12
7
s
Name
Type
Name
Type
Discharge temp. sensor
1
200K ohm
Tube temp. sensor
7
10K ohm
Top temp. sensor
2
200K ohm
EVI in sensor
8
10K ohm
High pressure switch
3
-
EVI out sensor
9
10K ohm
High pressure sensor
4
-
Suction temp. sensor 1
10
10K ohm
Ambient air temp. sensor
5
10K ohm
Suction temp. sensor 2
11
10K ohm
Cond. out temp. sensor
6
10K ohm
Low pressure sensor
12
-
26
Heat Recovery Introduction Part Introduction – Sensor & Switch Name
Type
Discharge temp. sensor
200K ohm
To sense compressor discharged gas temperature
Ambient temp. sensor
10K ohm
To sense outdoor ambient temperature
Cond_out temp. sensor
10K ohm
To sense condenser outlet temperature.
EVI in/out temp. sensor
10K ohm
To sense vapor injection refrigerant temperature
Liquid tube temp. sensor
10K ohm
To sense sub-cooled refrigerant temperature
Suction temp. sensor
10K ohm
To sense compressor suction gas temperature
Name
Description
Description
Output
High pressure sensor
To sense high pressure. To control fan RPM in cooling operation. To control compressor capacity in heating operation.
DC voltage 0 ~4.5V
Low pressure sensor
To sense low pressure To control compressor capacity in cooling operation To control fan RPM in heating operation
DC voltage 0 ~4.5V
27
Heat Recovery Introduction Mode Change Units – S*NEK Heat Recovery – MCU Mode Change Unit 1,2,4&6 port models (max. 8 indoor units per port) Brazed pipe connections Main 3-pipe connection on both sides of MCU for series installation Excl. S1NEK single port MCU – right side connection only No condensate drain Auto addressing
S1NEK1N
S2NEK2N
S4NEK3N
S6NEK2N
27
Heat Recovery Introduction Mode Change Units – S*NEK
Low pressure gas Refrigerant pass through design 2,4&6 port models
High pressure gas Liquid
Liquid & dual pressure gas ports to indoor units
28
Heat Recovery Introduction Cooling Operation
Hot gas bypass valve 2 open condition 20 mins. In cooling Cooling oil recovery System stop in 2 mins. 30 sec. (pressure equalization)
30 sec. open then close
E
s E
s s
E
E
E
s
E
s s
Low temperature & pressure gas High temperature & pressure gas High temperature & pressure liquid
E
E
28
Heat Recovery Introduction Video
30
Heat Recovery Introduction Main Cooling Operation Cooling
E
s s
E
s
E
E
Heating E
s
E
s s
Low temperature & pressure gas High temperature & pressure gas High temperature & pressure liquid
E
E
29
Heat Recovery Introduction Video
32
Heat Recovery Introduction Heating Operation Heating E
s s
E
s
E
E
E
s
E
s s
Low temperature & pressure gas High temperature & pressure gas High temperature & pressure liquid
E
E
30
Heat Recovery Introduction Video
34
Heat Recovery Introduction Main Heating Operation Heating E
s s
E
s
E
E
Cooling E
s
E
s s
Low temperature & pressure gas High temperature & pressure gas High temperature & pressure liquid
E
E
31
Heat Recovery Introduction Video
36
DVM S Indoor Unit Control
Indoor Unit Control Indoor Unit Component Diagram IDU Controlled Devices Fan – On/Off & Speed Electronic Expansion Valve Condensate Lift Pump (specific units) Control Components Temperature thermistor sensors Main PCB Remote Controller (wired or wireless)
Example: 4-Way Cassette PCB
Coil outlet sensor (Gas) I N
FAN
D O O R
Discharge sensor
Return air sensor
C O
NOTE: Discharge sensor is optional on ducted IDU’s
I
EEV
Example: MWR-WE11N
L
Coil inlet sensor (Liquid)
38
Indoor Unit Control Fan Speed Control Fan speed control step User control - Ultra Low: minimum step( * non feedback type : 5 step + Low step x 0.25)
System
- Low Low: Low – 1 step ( * 1step : about 20rpm)
control
- High High: High + 1 step - Ultra High: High + 2 step
Quiet Mode reduces the sound level from the fan motor during cooling or heating operation Fan feedback indoor unit (ex. RAC, 1way, 2way, 4way) - Current Fan speed -1 step (1step = about 20 rpm)
Fan non feedback indoor unit (ex. duct) - H M , M L , L L
39
Indoor Unit Control Fan On/Off Control – Thermo-off Condition
Mode
Cooling
Thermo
EEV
Fan
“02” SEG4 setting
“02” SEG 4
External room s/s
Minimizing fan operation
ON
Open
On
0,1,2,3
0
Disuse
Disuse
OFF
Closed (0 or 35)
On
0,1,2,3
1
Use
Disuse
Off
4,5,6,7
2
Disuse
Use-Heating
Open
On
0
3
Use
Use-Heating
Off & On(20°F↑)
0,4
4
Disuse
Use-Cooling
Off & On (20°F↑, 20sec on every 5mins)
2,6
5
Use
Use-Cooling
6
Disuse
Use-Both
Off
1,3,5,7
7
Use
Use-Both
ON
Heating
OFF
Open 120 step
40
Indoor Unit Control Fan Speed Control – Cold Air Prevention (Heat Mode) On a heat thermo-On, the fan operation is delayed until the indoor coil reaches 82.4°F This is a default function and cannot be deactivated Airflow in heating mode
Indoor coil temperature. 100.4°F
High or lower
96.8°F 93.2°F
Mid or lower Low
89.6°F
Mid or lower
86°F 82.4°F 79°F 68°F
High or lower
Low Low Fan off
Low Low Low Fan off
41
Indoor Unit Control Cool & Heat Thermo On & Off Operation Cooling Operation Thermo on : Room temp. ≥ Set temp. Thermo off : Room temp. ≤ Set temp. -1
on
Thermo on
Tset Tset-1 Thermo off
Thermo off
Heating Operation Thermo on : Room temp. ≤ Set temp. - 1 + T°F Thermo off : Room temp. ≥ Set temp. + T°F
Thermo off
Thermo off
Tset + T°F Tset-1 + T°F on
Thermo on
42
Indoor Unit Control Heating Compensation Temperature
T°C = Heating compensation temperature
Factory default (product code SEG6)
4-Way type: Others:
T℃ = 9°F T℃ = 3.6°F
Installation Setting (option code SEG21)
When using remote controller built-in room sensor – Installation option: SEG4=1
T℃ = 0°F
When wired R/C built-in sensor is set as “use” then T℃ = 0°F regardless of SEG4 setting Priority: Wired R/C built-in sensor use = Ext. Room Sensor setting > Installation Option > Product Option
If higher priority setting is applied, lower will be ignored
43
Indoor Unit Control Indoor Unit Operation Mode Mode
Fan speed
EEV
Fixed – Auto
Auto mode
Difference between Set temp. & Room temp.)
Control
Low: 1°F ≤ Mid ≤ 3°F : High
Cooling mode Dry mode Heating mode Turbo mode (while Cooling/Heating) Fan mode Defrost Oil recovery
User input (Low, Mid, High, Auto) Fixed - Auto (Low / Low Low)
User input (Low, Mid, High, Auto)
Control Control Control
Fixed – High or Turbo
Control
User input
Fixed
(Low, Mid, High)
(Close)
Stop Turn on: User selected Turn off: Stop
Fixed (Open)
Control
Setting temp. range 18~30℃ (65~86℉) 18~30℃ (65~86℉) 18~30℃ (65~86℉)
16~30℃ (61~86℉) Unable
Remark User selection
User selection User selection User selection Operating for 30mins then return to previous
-
User selection
-
System
-
System
44
Indoor Unit Control Indoor Coil Freeze Protection Control
Purpose: To prevent indoor coil freeze up due to abnormally low coil temperature Process: Hz Hold Hz Down HP Down (no error code for freeze protection) Start Evap temp<35.6°F for 40 sec.
Hz Hold
Evap temp< 32°F for 40 sec.
Evap temp> 39.2°F → Return to normal control Hz down
After 2 min.
Evap temp ≥ 32°F → Holding current Hz Evap temp< 32°F → 5Hz down * Minimum Hz : HGV on
Evap temp< 28.4°F for 40 sec.
HP down
Evap temp > 39.2°F → Return to normal control
END
45
Indoor Unit Control Auto Mode - Default Initial operation mode determination If Room Temp. ≥ Set Temp. – 1°F
If Room Temp. < Set Temp. – 1°F
Auto cooling mode
Auto heating mode
Thermo-On/Off
Thermo-On/Off is same in cooling & heating mode
When mode change is carried out Model
Heat pump
Heat recovery
Condition
1&2&3
1 or 2 or 3
1. Thermo off for 30 mins 2. Only 1 IDU is turned on. 3. IDU product option change Detail
“Seg 5 current + 2” ex) 014046-194XXX 014066-194XXX
1. Thermo off for 30 mins 2. IDU Set temp. change 3. Follow the installation option setting * refer to the next page for “3”
* If more than 2 IDUs are turned on, IDU mode will follow the ODU operation mode.
46
Indoor Unit Control Auto Mode – Auto Changeover Setting For Heat Recovery
A
D
B
C
T
47
Indoor Unit Control Auto Mode – Auto Changeover Setting For Heat Recovery
77°F
Setting
Value
0
1
2
3
4
5
6
7
A
Heating offset
SEG4
0
0.5
1
1.5
2
2.5
3
3.5
B
Cooling offset
SEG5
0
0.5
1
1.5
2
2.5
3
3.5
C
Heat cool
SEG6
1
1.5
2
2.5
3
3.5
4
4.5
D
Cool heat
SEG8
1
1.5
2
2.5
3
3.5
4
4.5
T
Time
SEG9
5
7
9
11
13
15
20
30
Start
Cooling Thermo off (Tr15
30 20 10
Max=10 min 2min
0 0 Pump Down
4 Soft Start
Mild Start
8
12
16
20
Safety start
58
Outdoor Unit Control 104
78.8
95
75.2
86
Room temp. (°F)
Room temp. (°F)
Quick Start (≥ 30% Indoor Unit Capacity Required)
Cooling Quick Start
77 68
Ambient temp. (°F)
59 59
68
77
86
95
104
113
Heating Quick Start
71.6 68 64.4 60.8 57.2 -13
Ambient temp. (°F) -4
5
14
23
32
41
50
59
59
Outdoor Unit Control Compression Ratio Control
Purpose: Protect the compressor from abnormal operation Process: Hz Hold Hz Down HP Down Compressor stop (E428)
Max. compression ratio: to limit capacity Min. compression ratio: to maintain lubrication PSI.
Compression Ratio = (High pressure + 14.7psi) / (Low pressure +14.7psi) (Absolute pressure = Gauge pressure + 14.7psi)
(Example) Compressor spec Compression ratio
640
HP down
568.93
8.5
497.82
Hz down
426.7
7.4
355.6
7.0
Hz hold
284.47 213.35
1.7
142.23
Minimum Hz limitation
71.12
1.5
0
PSI. 0
SH (7°F) control
28.45 56.89 85.34 113.79 142.23 170.68 99.13 227.57
Comp stop [E428]
60
Outdoor Unit Control Control Logic – Dual Compressors Starting
Comp 2: Hz=Comp 1 + offset Offset: Max. 10 Hz Major condition for next compressor starting (1or2)
Comp 2
Comp. Hz > 76Hz Comp. Hz > 60 Hz for 3 mins. Without unit stop Comp. Hz > 70 Hz for 3 mins. When unit stop
Comp 1
Control Logic – Additional Compressor Starting Comp1 on + Comp 2 start Comp 2
Comp 1
Comp 2 on + Comp 1 start Comp 2
Comp 1
61
Outdoor Unit Control Operating Priority Main
Sub 1
Sub 2
INV1
INV2
Modular System 2 or 3 ODU’s connected together on the same refrigerant network
Compressor priority in a unit
Master unit priority At initial starting from power supply
Which one is off longer
ODU address setting (Main - Sub1 - Sub2)
INV1 at initial starting from power supply
Master unit rotation 1- After defrost / oil recovery / all unit off (Master unit operates more than 60mins) 2 - Any unit is stopped over 40 min. Main Master Sub2 Sub1
Sub1 Sub1 Master Sub2
Sub2 Sub2 Sub1 Master
Additional compressor starting condition Over 60Hz & over 3mins operation Over 76Hz operation Efficiency of 30~80Hz is better than higher frequency Each unit will decide individually
62
Outdoor Unit Control Compressor Capacity Control
Equal frequency in a unit: max. 10Hz difference Equal capacity in a module: Capacity division by unit capacity, control all compressor frequency difference within 20Hz 38 HP System Equivalent capacity in module
Main unit (22HP)
Sub 1 unit (16HP)
High efficiency Oil balance
1
3
2
4
Equal Hz in a unit
Example) Required capacity = 273,000 Btu/h Main unit Compressor Module Capacity [Btu/h]
Comp 1 (64cc)
Sub 1 unit
Comp 2 (64cc)
Comp 1 (52cc)
Comp 2 (52cc)
273,000: *22/38 = 158,000
273,000: *16/38 = 115,000
Comp Capacity [Btu/h]
79,000
79,000
57,500
57,500
Frequency
70 Hz
70 Hz + α
62 Hz
62 Hz + α
63
Outdoor Unit Control System Pump Down – Cooling (Heat Pump) To minimize liquid flood back in the system on next start, pump down or pump out is initiated after ODU stop
64
Outdoor Unit Control System Pump Out – Heating (Heat Pump) To minimize liquid flood back in the system on next start, pump down or pump out is initiated after ODU stop
65
Outdoor Unit Control Heat Recovery – Operating Mode Determination Main Cooling Mode
Heating Capacity Ratio Hysteresis range : Max. range : -15% ~ 20%
0%
Cooling Mode
A%
Hysteresis A
100 %
B%
Criterion of HCR
Hysteresis B
Heating Mode
Main Heating Mode Ave. heating Indoor room temp. : 68°F Ave. cooling Indoor room temp. : 75.2°F Indoor operating ratio : 50%
※ Heating capacity ratio = Σ(Heating) / {Σ(Heating) + Σ(Cooling)} 100 90 80
Criterion of HCR Factor : Ambient temp. IDU’s operating ratio, room temp. Mode changeover in hysteresis Remaining 30 min in hysteresis area, mode changeover carry out
70
HCR[%]
Value to decide mode of Heat Recovery
60 50 40 30 20 10 0
Outdoor Temp[°F]
5 14 23 32 41 50 59 68 77 86 95104 113 122
66
Outdoor Unit Control Capacity Control - Cooling Compressor frequency is controlled by the target low pressure which is changed by the averaging of evaporator inlet temperature Low pressure < Target low pressure < Low pressure Excessive capacity
Insufficient capacity
Target low pressure (psi) 85.34
Comp Hz down
Comp Hz up
Capacity decreasing
Capacity increasing
106.68
113.78
120.89
128
- avg. evap. Inlet temp. = setting target low press maintain Target low pressure
Hz Up
- avg. evap. Inlet temp. < setting target low press increase - avg. evap. Inlet temp. > setting target low press decrease
Why is evaporator inlet temp used to find target low pressure? To compensate piping length between the ODU and IDU’s
ODU Option Settings (Capacity correction) Seg1
L.P : 113.78 psi
99.56
* Default value of target low pressure: 113.78 psi
Hz Down Hz Up
92.45
L.P :118 psi
L.P : 122 psi
L.P : 127 psi
Evap in : 46°F
Evap in : 48°F
Evap in : 50 °F
Main ODU
0
Seg2
Seg3
Seg4
Temperature
1
0 0 0 0 0 0 0
0 1 2 3 4 5 6
45°- 48°F 41°- 45°F (Default) 48°- 52°F 50°- 54°F 52°- 55°F 54°- 57°F 55°- 59°F
67
Outdoor Unit Control Capacity Control - Heating High pressure < Target high pressure < High pressure Seg1
Insufficient capacity
Seg3
Seg4
Pressure (psi)
2
0 0 0 0 0 0 0 0 0
0 1 2 3 4 5 6 7 8
426.7(default) 355.6 369.8 384 398.25 412.48 440.9 455.15 469.4
Excessive capacity
Comp Hz up
Comp Hz down
Capacity increasing
Capacity decreasing
Target high pressure control ODU option setting
Main
0
Hz down Hz up
Target high pressure High pressure
Air In
111F
Air Out
Ex) option : 02 (377 psi : saturated temp ≒ 111°F)
122°F
H/X
H/X
Air In
Ex) option : 00 (435 psi : saturated temp ≒ 122°F)
Air Out
Hz up
Seg2
68
Outdoor Unit Control Outdoor Unit Fan Control Cooling Fan rpm increase
Fan rpm decrease
Target high pressure
ODU setting
Target high pressure for cooling
Default
355.6 psi
ODU lowest setting Menu08 / value03
398.25 psi
Ambient temp. (°F)
Target low pressure for heating
Below 32
106.7 psi
32 ∼ 50
116.63 psi
50 ∼ 68
119.47 psi
68 ∼
123.74 psi
Heating Fan rpm decrease Fan rpm increase
Target low pressure
69
Outdoor Unit Control EVI – EEV Control Purpose: To increase sub-cool of system : Sub-cool ↑ Efficiency ↑
EVI On(Vapor Injection) mode Remark
*Condition
Open
Open
Open
Normal
Open
Open
Close
Close
Open
Open
All comp in unit 60hz ↑ T out < 96.8(c)/50(h)°F * Control by unit Safety start Defrost
Cooling
Heating
3 s
E
EVI Bypass mode
EVI Bypass
IPM2 IPM1
EVI mode
EVI Sol
1
s
EVI Bypass mode EVI On mode (Vapor Injection) EVI Off mode
EVI EEV
E
Valve
2
s
Cooling Vapor injection not working when ODU option 8 : ODU higher ODU option 9 : Long pipe
▷ SH control ▷ Sub-cooling control : 68°F ( High pressure Saturated temp. – Liquid tube temp.)
1. EVI out temp. – EVI In temp. > 50°F (priority) 2. T dis = 194°F ▷SH ( EVI out temp. – EVI in temp.) control : 3.6°F
If compressor discharge temp. is abnormally high, open EVI EEV to decrease the discharge temperature
70
Outdoor Unit Control Main EEV Control - Heating ▶ Main EEV control
EEV control period : every 20s In heating mode
① Stop ODU : Main EEV close ② Cooling ODU : Main EEV Full open
DSH normal
No
Yes Module installation
DSH protection control
No
▶ Main EEV control for module install 1. Refrigerant distribution between ODUs 2. Then Super Heat control (SH) 3. If discharge temp is high EEV step increases
Yes Low pressure equal between ODUs
Yes Low pressure equalization control
No Target SH control Single install : 35.6°F
Target SH control * SH = super heat (Suction temp. – Low pressure saturated temp.) * DSH = Discharge super heat (discharge temp. – high pressure saturated temp.)
Module install : 41°F EEV control repeat
71
Outdoor Unit Control Accumulator Oil Return Valve - ARV From EVI EEV 4Way valve Compressor
Refrigerant
ARV control
Stop
Close - Prevent refrigerant flowing to compressor
Starting
Close - Prevent refrigerant flowing to compressor
Running
Open - Oil return to compressor
Oil
ARV oil
NOTE: Compressor damage can occur if the ARV fails due to a lack of compressor oil return
72
Outdoor Unit Control Compressor Oil Recovery Operation
Oil recovery operation starts after a cumulative compressor run time of 7 hours The oil recovery interval will shorten if the outdoor unit or compressor stops
If defrost mode is in operation for more than 3 minutes, it counts as oil recovery operation as well In a modular system (manifolded ODU’s) on completion of oil recovery operation the master ODU will change
Before Cooling
Heating
Oil Recovery Cooling
Heating
After Cooling
Heating
Capacity of compressor
Current capacity + additional capacity
ODU fan
Normal control
ODU EEV
Normal control
EEV of operating indoor units
Higher step of [400(C)/300(H) or Current step]
Stopped indoor unit’s EEV
400(C)/300(H)
Time
3min(Cool) / 6min(Heat)
73
Outdoor Unit Control Hot Gas Bypass Valve Hot gas bypass valve compensates for abnormal low pressure Open status E
Safety start Low pressure protection control
On (psi)
≤ 45.51
≤ 19.91
Off (psi)
≥ 59.74
≥ 34.14
s
E
Heating
IPM2
IPM1
Cooling
s
Valve control
s
Hot Gas bypass valve
74
Outdoor Unit Control High Pressure Protection
Purpose: To protect the compressor and system from excessive high pressure Process: Hz hold Hz down HP down Compressor stop (E407)
Compressor Stop = E407 High Pressure 568.93 psi
HP Down area High Pressure
HP Down release
540.49 psi
Hz Down area High Pressure
Hz Down release
526.26 psi
Hz Hold area High Pressure
Hz Hold release
512 psi
Normal Operation High Pressure 426.7 psi
Compressor Stop Release
75
Outdoor Unit Control Low Pressure Protection
Purpose: To protect the compressor and system from abnormal low pressure Process: Hz hold Hz down HP down Compressor stop (E410) Compressor stop release: 3 mins. & low pressure 64 (cool) / 42.67 (heat) psi Auto restart (6 X max.) Heating
Operation
Cooling
Operation
Outdoor temp.
Pressure (psi)
Over 59°F
≤ 56.9
Less than 59°F
≤ 42.67
Over 59°F
≤ 49.78
Less than 59°F
≤ 35.56
Over 59°F
≤ 36.98
Less than 59°F
≤ 22.76
Hz Hold
Hz Hold
Hz Down
Hz Down
HP Down
Comp Down [E410]
≤ 11.38 for 3mins & dis temp 194°F↑
HP Down
Outdoor temp.
Pressure (psi)
Over 32°F
≤ 42.67
32°F~14°F
≤ 28.45
Less than 14°F
≤ 25.6
Over 32°F
≤ 31.29
32°F~14°F
≤ 22.76
Less than 14°F
≤ 17.07
Over 32°F
≤ 25.60
32°F~14°F
≤ 17.07
Less than 14°F
≤ 11.38
Comp Down [E410]
≤ 7.11 for 3mins & dis temp 194°F ↑
76
Outdoor Unit Control Discharge Temperature Protection
Purpose: To protect the compressor and system from abnormal discharge temperature Process: ESC EEV Open Hz Hold Hz Down HP Down Comp Stop (E416)
Compressor Stop = E416 Discharge Temp. 248°F HP / Hz Down area Discharge Temp. 221°F
HP Down release Hz Hold area
Discharge Temp. 212°F
Hz Down release EVI EEV Open
Discharge Temp. 203°F
Hz Hold release Normal Operation
Discharge Temp. 176°F
Compressor Stop Release
77
Outdoor Unit Control Intelligent Power Module (IPM)
Purpose: Protect the IGBT (Insulated Gate Bipolar Transistor) module from damage IGBT is a 3 terminal power semiconductor device functioning as an electronic switch
The switching function controls the compressor frequency rate which in turn creates heat
IMP temperature
. Hz Hold: Hold current Hz (Hz reduction possible) . Hz Down: Decrease 5 Hz / control period . HP Down: Decrease 1 Hz / sec
Compressor stop(E400 / E500)
212°F 100 ℃ HP Down area 98℃ 208°F
Compressor stop(E400 / E500), if condition remains for 10 min.
HP Down release Hz Down area Hz Down release
199°F 93℃ Hz Hold area 194°F 90℃
Hz Hold release
Compressor stop release
Normal operation
78
Outdoor Unit Control Inverter PCB Input Current Control Purpose: Inverter input current is controlled to protect circuit components from failure
INV PBA Input (A)
Compressor stop (E462) Comp stop
. Hz Hold: Hold current Hz (Hz reduction possible) . Hz Down: Decrease 5 Hz / control period . HP Down: Decrease 1 Hz / sec
HP Down area HP Down release
HP down
Hz Hold area Hz hold
Hz Hold release
(HP down – 1A)
Normal operation
79
Outdoor Unit Control Current Control Purpose: To protect the IPM module from overheating Reason: Outdoor temp increases IPM temp increases
Max. Hz limitation
In case of fan type IPM
OD 113°F OD 104°F OD 95°F
194°F
Cooling Current [A]
Comp down 2A Hz Down
Hz Hold Max HZ limitation by IPM temp Default
Max Hz
86
122
OD temp. (°F)
80
Outdoor Unit Control Maximum Current Control
Outdoor Unit option setting: 50% - 100% Hz Hold: Compressor current + Fan current > 95% of setting current Hz Down: Compressor current + Fan current > setting current
100%=Maximum current (MCA) of the system Setting: Outdoor unit option setting or DMS2 setting range (50% to 100%) Max current
Setting of Max. current
. Hz Hold: Hold current Hz (Hz reduction possible) . Hz Down: Decrease 5 Hz / control period . HP Down: Decrease 1 Hz / sec HP Hold area
80% Capacity range
Range
Capacity range
50%
Required capacity
100%
HP Hold area 95 %
81
Outdoor Unit Control Inverter PCB Current Control Inverter PCB input current is controlled to protect circuit components from failure INV PCB Input (A)
Compressor stop (E462) Comp stop
HP Down area HP down
HP Down release Hz Hold area
Hz hold
Hz Hold release
(HP down – 1A)
Normal operation
82
Outdoor Unit Control Refrigerant Overcharge - Cooling
System will run in normal operation until it is above regulated capacity High pressure protection control High pressure will be increased due to INV frequency increase
INV frequency goes to lowest setting
Increase sub cooling (Liquid piping temp decreases)
High pressure
Keep constant low pressure
Low pressure Low pressure is increased When INV frequency decreases
Inverter frequency Increases INV frequency to try to maintain low pressure Overcharge condition progression
83
Outdoor Unit Control Intelligent Defrost Optimal judgement for initiating defrost operation
MBtu/h
Btu/h 102,000 30000
14°F heating
30000 102,000
68,000 20000
20000 68,000
Defrost
34,000 10000
0
Conventional Intelligent
14°F heating
Conventional
Defrost
0 0
60
120
minutes
180
[Outdoor Temp. : 14°F DB, (Humidity 40%)] [Indoor Temp. : 68°F DB]
Time & Temp initiated defrost Unnecessary defrost
240
300
10000 34,000
00 0
[min]
60
120
180
240
300
[Outdoor Temp. : 14°F DB, (Humidity 40%)] [Indoor Temp. : 68°F DB]
Time & Temp & Sensing heat exchanger air resistance value Continuous Heating operation
84
Outdoor Unit Control Intelligent Defrost Test condition
Test result
- Installation 24HP Outdoor for each zone.
* Only 2 defrost cycles for 10 days Intelligent Defrost
24HP
Normal Defrost
24HP
Intelligent
Conventional
Defrost
Defrost
Total Operating time(min)
12,130
11,568
Defrost operation(times)
2
19
6,065
608
Result
Average Heating Operation without defrost(min)
85
Outdoor Unit Control Rotation Defrost Operation - Heat Recovery Module systems (2 or 3 connected units) – Defrost operation is actuated in sequential order to improve heating efficiency Operation requires option setting at commissioning
Actuator
Outdoor units in defrost mode
Units not being in defrost mode
Compressor
Depends on the outdoor unit capacity (86-110Hz)
General control
Outdoor EEV Outdoor Fan HR EEV
Full close 0 step Off
General control General control General control
Main cooling valve
ON
General control
Active unit Inactive unit Indoor EEV Active unit Heating Indoor unit Inactive unit Active unit Cooling indoor unit Inactive unit Indoor Fan Active unit Heating Indoor unit Inactive unit Time Cooling indoor unit
General control Required step for control of the superheat degree General control General control on inactive units General control Set fan speed Mid fan speed Off Maximum of 12 min -
86
Outdoor Unit Control Rotation Defrost Operation - Heat Recovery
87