MINI-SPLIT ERROR CODES Error Code

Explanation

E1

R Y G

Notes

1

It is a sensor put aside the exhaust pipe.Once the pressure of exhaust pipe surpass 3.15Mpa, the airconditioning system will stop working.

2

Sensor on the indoor unit dects the evaporator temperature continuously, once the temperature is lower than some point for certain time, it will turn off the system to avoid freezing the indoorunit.

3

For system with low pressure sensor(locating aside the inspiration pipe), once the pipe's pressure is lower than 0.15Mpa, the system will stop working.

High Pressure protect

E2 Inside Anti-Freeze Protect

E3 Low Pressure Protect

E4

Compressor Discharge protect

Explanation

4

6 sec Pause before Flash Sequence

Once the exhaust temperature of the compressor is higher than regulated, the system will be turned off automatically.

E5

low pressure over current protect

5

Once the system current is higher than regulated,the system stops.

E6

indoor-outdoor communication Error

6

Bad communication between indoor and outdoor units.

7

For multi split airconditioners,when one of the indoors is working for cooling(dehumidifying),other indoor unit can no work for heating.

8

While heating, indoor tube temperature sensor will detec

9

While heating, the indoor fan will work several minutes later than the compressor so that the airflow comes out the airconditioner will not be too cold.

10

For invertor system, the frequecy will lower down when the voltage drop sharply, so that the current can keep stable.

E7 Mode conflict

E8

high Temp protect

E9 cold wind protect

E0

AC Voltage Low

H6

No Indoor motor feedback

F1

room temp sensor open/short

11

1

Temperature sensor defect inspection.

F2

Indoor evaporator sensor open/short

2

F3

Outdoor temp sensor open/short

3

F4

F5

Outdoor evaporator sensor open/short Outdoor sensor open/short

F6

4

6 sec Pause before Flash Sequence

5

6

For invertor, while cooling, the outdoor tube temperature sensor detect the tempearture continuously, and will low the working frequency if the tube temperature is higher than some point for certain time.

7

For invertors only.After a period of cooling, the system will work in higher frequecy for a period.

8

For invertors only. Lower the freqecy, reduce the load if the current is higher than standard.

9

For invertors only. Lower frequecny, if exhaust temperature is higher than standard.

Cooling Overload

F7

F8

F9

F0 H1

Unused

Current Overlaod

Unused Unused Defrost

10 1

In heating condition, defrosting auotmatically and keep the heat exchange efficeincy.

H2

Static duct clean protect

2

H3

compressor overload protect

3

Compressor stop working when the compressor temperature is higher than regulated.

4

While cooling, system stops if the outdoor tube temperature is higher than a certain point for certain time. While heating, system stops if the indoor tube temperature is higher than a certain point for certain time.

Mode Protect

5

For invertors only.

Unused

6 6 sec Pause before Flash Sequence

Synchronize fail

7

H4 System Abnormal

H5 H6

H7 H8

8 Water full protect

For system with water pump,such as cassette airconditiners, the system stop working when the water level surpassed regulated level.

H9

heating Error

9

HO

Heat high temp protect

10

FA

FH

Pipe Hot

For invertors only.While cooling, lower the frequency if the outdoor tube temperatuer is higher than standard.

Freeze Protect

For invertors only. While cooling, lower frequency if the indoor tube tempearture is lower than standard.

12201 N.W. 107 th Ave. Miami, Fl 33178 toll free: fax:

For invertors only. While heating, lower the frequency if the indoor tube temperature is higher than standard.