VARICON PUMPS & SYSTEMS PVT. LTD. Plot: 10, PKM Road, Athipet, Chennai – 600 058. India Phone: + 91 44 2635 0628, Fax: +
Views 293 Downloads 14 File size 52KB
VARICON PUMPS & SYSTEMS PVT. LTD. Plot: 10, PKM Road, Athipet, Chennai – 600 058. India Phone: + 91 44 2635 0628, Fax: +91 44 2635 0629 Email: [email protected] W ebsite: www.variconsystems.com
TECHNICAL SPECIFICATION The NJEX 6300 System is a "Total System" approach to odorization of natural gas. This design approach provides for proportional-to-flow odorant injection, odorization measurement, system monitoring, and alarm notification. 1 - Injection Pump, Featuring: (Main Pump) Patented segregated pneumatic plunger pump design 316 stainless steel construction Complete purge capability for odour sensitive maintenance Cartridge style check valve for quick replacement during maintenance 1 – Pneumatic Metering Pump Featuring (Stand by pump) A Pneumatic Metering Pump operated by a Pneumatic Timer and works at constant flow-rate for stand bye. 1 - N-300 Controller Featuring: LPS Line Power Supply charger unit 120/240 VAC 50/60 Hz Local and remote programming access Locally displayed system performance data and programming information via a 4 line 20 character alphanumeric display Systems is Compatible for both RTU and ASCII format for remote communication Certified intrinsically safe application suitable for use in Class I Division 1 Group C/D Hazardous Areas 1 - VM-1000 Verometer Featuring: Simple known volume measurement design with one moving part Temperature compensation of injected volume 316 stainless steel construction Measurement accuracy exceeding 1% 1 – SS 304 500 Litter Odorant Storage Tank Featuring: (Fabricated by Varicon, India) Design as per ASME Sec VIII div .1 horizontal storage tank Odorant Magnetic level gauge 1
VARICON PUMPS & SYSTEMS PVT. LTD. Plot: 10, PKM Road, Athipet, Chennai – 600 058. India Phone: + 91 44 2635 0628, Fax: +91 44 2635 0629 Email: [email protected] W ebsite: www.variconsystems.com
Fitting and valve package designed for odorant service, including Relief valve, pressure gauge, 1 - Structural Steel Base Frame Featuring: (Fabricated by Varicon, India) Mounting locations for the NJEX odorant injection system and one 500 litter odorant storage tank Finished with an abrasion resistant, high-gloss industrial grade enamel 1 - Enclosure Featuring: SS 316 panel 1 - Odorant Filter Featuring: Anodized aluminium construction Replaceable filter elements 1 - Sentry4 Monitoring Software System Featuring: Quik View screen for real time online sub-system system performance monitoring Graphic sub-system performance analysis capability Hourly and daily odorant usage reporting Paperless audit trail system Detailed event logging Compatible with Windows 95/98/2000/NT 1 – Portable Odorant Detector (Odor Handy Plus) Featuring: Electro Chemical Sensor Measure Cap Connection hose Charging dock for automatic charging Power Supply 230V/115V Rotameter (Pressure up to 8 bar) OPERATION SPECIFICATIONS: Maximum Operating Pressure
: 1,440 psig (99.28 Barg)
Operating Temperature Range Power Supply
: 0 to140 degrees F (-17oC to 60oC) : LPS-120/240 volt 50/60Hz AC Charger, SPS-12 Solar Panel (optional)
Battery Reserve
: Approximately 30 days 2
VARICON PUMPS & SYSTEMS PVT. LTD. Plot: 10, PKM Road, Athipet, Chennai – 600 058. India Phone: + 91 44 2635 0628, Fax: +91 44 2635 0629 Email: [email protected] W ebsite: www.variconsystems.com
Actual reserve time is dependent on age and condition of battery and the usage rate of the NJEX System. Actuation Pressure
: 75 psig (5.17 Barg)
Gas Flow Rate Input Signal
: 1-5 VDC, 4-20 mA, or pulse
3