SITIO : EL VINCULO I.- MEDICION DE RESISTIVIDAD DE SUELO FECHA : 22/02/2006 INSTRUMENTO : MEGABRAS MTD SERIE 20 KW
Views 232 Downloads 7 File size 102KB
SITIO :
EL VINCULO
I.- MEDICION DE RESISTIVIDAD DE SUELO
FECHA
: 22/02/2006
INSTRUMENTO
: MEGABRAS MTD SERIE 20 KW
METODO
: SISTEMA DE 4 ELECTRODOS, CONFIGURACION SCHLUMBERGER
DATOS MEDIDOS: MEDICION
a
n
na
L
Re [ohm]
Pa [ohm]
1
1
1
1.0
0.6
18.86
6.52
2
1
2
2.0
0.8
5.44
6.67
3
1
4
4.0
4.5
3.42
214.88
4
1
6
6.0
6.5
0.46
60.70
5
1
8
8.0
8.5
0.15
33.93
6
1
10
10.0
10.5
0.09
31.10
7
1
12
12.0
12.5
0.05
24.50
8
1
15
15.0
15.5
0.03
22.62
9
1
18
18.0
18.5
0.02
21.49
10
1
23
23.0
23.5
0.015
26.01
11
1
28
28.0
28.5
0.01
25.51
RESULTADOS DE MEDIDA CURVA PATRON CAPA
A -9 (0,5) ESPESOR [m]
43.08 RESISTIVIDAD [ohm-m]
1
E1 =
0.8
P1 =
50
2
E2 =
0.5
P2 =
50.00
3
E3 =
10E+06
P3 =
10E+06
MEMORIA CALCULO MALLA BT
1.- CALCULO RESISTIVIDAD EQUIVALENTE DEL TERRENO, DE ACUERDO AL MODELO DE YAKOBS, DONDE:
(
eq (1(k)
=
DONDE:
CON:
r =
S
= RADIO EQUIVALENTE
DATOS INICIALES SUPERFICIE DISPONIBLE [m 2] PROF. ENTERRAMIENTO [m] RADIO CIRCULO EQUIV. [m] ro2 20.846 q2
50.388
4q2ro2
4201.561
S b r
67.5 0.8 4.635
u1 =
71.874 72.924
LUEGO h1 = h2 = h3 =
0.8 1.3 1.00E+07
h 12 = h 22 = h 32 =
0.64 1.69 1.00E+14
u2 = u3 =
1.00E+14
ENTONCES vo2 =
20.846
F1 =
0.145
v1 = v22 =
20.410
F2 = F3 =
0.229
0.02
1.000
0.0000001
2
v32 =
19.756 0.000
0.02
CON ESTO LA RESISTIVIDAD EQUIVALENTE ES:
eq
=
58.45
ohm-mt
2.- CALCULO DE LA RESISTENCIA DE LA MALLA BT SEGÚN METODO DE SCHWARZ CARACTERISTICAS MALLA PROPUESTA LADO MAYOR [m] LADO MENOR [m] PROFUNDIDAD DE ENTERRAMIENTO DIAMETRO CONDUCTOR [m] LARGO CONDUCTOR MALLA [m] Nº ELECTRODOS
A B b dc L N
SEGÚN SCHWARZ
DONDE Y
LUEGO K1 =
1.089
Y
K2 =
ENTONCES LA RESISTENCIA DE LA MALLA ES: Rpt =
3.19
[ohm]
Rpt (tratamiento ericogel) =
1.91417997
4.861
12 4.5 0.8 0.0094 61.5 2
1/0
3.- CALCULO DE CORTOCIRCUITO MONOFASICO CORTOCIRCUITO MONOFASICO:
(1)
DONDE, PARA SECUENCIA CERO:
Y
DONDE: R = Icc1 = Icc3 = V =
3.19 220 380 13200
ohm [A] [A] [V]
RESISTENCIA MALLA TIERRA CORRIENTE CCTO MONOFASICO (POR EMPRESA ELECTRICA) CORRIENTE CCTO TRIFASICO (POR EMPRESA ELECTRICA) VOLTAJE DE LINEA (POR EMPRESA ELECTRICA)
ENTONCES: x1 = x2 = x0 =
20.055 20.055 63.812
REEMPLAZANDO EN (1) Icc1 =
219
[A]
LA CORRIENTE DE CORTOCIRCUITO REAL SERA Ig = Icc1 * FD * Fc DONDE
FD = Fc =
1 1
LUEGO: Ig = CON ESTO:
219
[A]
FACTOR DE DECREMENTO PATA t = FACTOR DE CRECIMIENTO PARA t =
0,5 Seg 0,5 Seg
4.- DETERMINACION SECCION MINIMA CONDUCTOR MALLA DE ACUERDO A ECUACION DE ONDERDONKS:
DONDE I t Tm Ta A
= = = = =
219 0.5 1083 40
[A] [seg] ºC ºC CM
CORRIENTE CCTO REAL RMS TIEMPO DESPEJE Tº ADMISIBLE MAXIMA POR CONDUCTOR Tº AMBIENTE SECCION DEL CONDUCTOR EN CM
REEMPLAZANDO TENEMOS QUE A =
1075
CM
A =
1.08
MCM
A =
0.54
[mm2]
PERO
1 MCM
=
0.5067
[mm2]
5.- CALCULO VALORES MAXIMOS DE POTENCIALES TOLERADOS
Y
DONDE Vmp = Vpp = Cs =
VOLTAJE CONTACTO VOLTAJE PASO FACTOR DE CORRECCION
DONDE bo = s =
0.1 50
[mt] [ohm-mt]
ESPESOR RECUBRIMIENTO (GRAVILLA)
t = a =
3000 0.5 0.106
[ohm-mt] [seg] [mt]
RESISTIVIDAD RECUBRIMIENTO TIEMPO DESPEJE FUSIBLE EQUIVALENCIA PIE A ESFERA DE RADIO a
g =
REEMPLAZANDO TENEMOS QUE Cs =
0.659
RASISTIVIDAD 1º CAPA
LUEGO: Vmp =
651
[V]
Vpp =
2122
[V]
6.- CALCULO POTENCIALES MALLA PROPUESTA
Y
DONDE
DONDE L = n = D = ho =
61.5 5.5 6 1
[mt]
LARGO CONDUCTOR MALLA Nº CONDUCTORES LADO MENOR SEPARACION CONDUCTORES LADO MENOR
[mt] [mt]
REEMPLAZANDO Kii = Kn = Km = Ki = Ks =
0.418 1.341 0.888 1.602 0.294
LUEGO Vmp =
296
[V]
Vpp =
98
[V]
296 98
<