API 2000 - SEVENTH EDITION, MARCH 2014 ANNEXURE - F , "Guidance for Inert gas inert gas blanketing of tanks for flash ba
Views 64 Downloads 0 File size 53KB
API 2000 - SEVENTH EDITION, MARCH 2014 ANNEXURE - F , "Guidance for Inert gas inert gas blanketing of tanks for flash back protection" LEVEL - 3 (No additional protection against flame propagation from outside to the inside of tank is required) Required flow rate Volume of reserve inert gas Tank Dimensions: Dia Height Slope of cone roof Site Latitude
= = = =
In Flow rate
=
398 m3/hr
Out Flow Rate Operating Pressure Operating Temperature
= = = lin
440 m3/hr 3 kPag 65 °C
wall thickness of insulation inside heat transfer co-efficient thermal conductivity of insulation Reduction factor for insulation C Factor for Lattitude
22 13 12 23-24 °
1
5.00E-02 m
h λin
4 W/(m2.K) 0.043 W/(m.K)
Rin
0.177 6.5
Tank Volume
= Vtk
Out flow rate
Vpe
365.95 Nm3/hr
Required Nitrogen flow rate
=
591.12 Nm3/hr
Volume of reserve inert gas
=
606.9452 m3
@ 3 kPag, 65°C
Volume of reserve inert gas
=
79.60567 m
@ 600 kPag, 25°C
Required Outbrething flowrate Required Outbrething flowrate for PVRV Required vaccum capacity for PVRV Required Outbrething flowrate for SAPCV
= = = =
520.0629 Am3/h Air 420.0508 Nm3/hr Air 570.7385 Nm3/hr of Air 435.0526 Nm3/hr of N2
5057.88 m3
3
Emergency Relieving Reference API 2000 : Section 3.3.3.3 : Fire Relief Requirements
Wetted surface area Q F L T M
631.7115 m2 4,129,700 W 0.15 1519000 j/kg 338.15 K 30.33
Considering hexane 631.7115 m2 208.2 1 334900 j/kg 288.75 K 86.17
q
1234.486
41200.84 6427.331
Table 1 — Y-factor for various latitudes Latitude Y-factor Below 42° 0.32 Between 42° and 58° 0.25 Above 58° 0.2
Table 2 — C-factors Latitude
°C Below 42° Between 42° and 58° Above 58°
C-factor for various conditions Vapour pressure Hexane or similar Higher than hexane, or unknown Average storage temperature °C