RMS9C MicroVersa Trip Plus™ or MicroVersa Trip PM™ Digital RMS Trip Units (ANSI) Long/Short Time
700 600 500
200
1
400
.9 .8
200
100 90 80
4
70
70
60
60 50
50
TIME IN SECONDS
500
300
Maximum Trip Unit Response Time
3
40
40
30
30
2
20
.7 .8 .9 1
2
3
20
4
5
6
7
8 9 10
20
30 2
RMS9C MicroVersa Trip Plus™ or MicroVersa Trip PM™ Digital RMS Trip Units (ANSI) Fixed Hi-Range Instantaneous 50/60 Hz Operation Only
600
300
100 90 80
.6
700
Long-Time Delay Bands
400
2
.5
1 .9 .8
.7
.7
.6
.6
.5
.5
.4
.4
.3
.3
.2
.2
.1 .09 .08
.1 .09 .08
.07
.07
.06
.06
.05
.05
.04
.04
.03
.03
TIME IN SECONDS
.6
100
1000 900 800
.5
1.5
1
2.0
7
6
5
5
3.0
4
.01
.5
.6
.7 .8 .9 1
4
I2t In
3
4.0
2
2
3
4
5
6
7
8 9 10
20
.01 30
20
30
MULTIPLES OF BREAKER SHORT-TIME RATING (H)
3
2
MULTIPLES OF INSTANTANEOUS PICKUP SETTING 2
.5
.6
.7 .8 .9 1
2
3
4
5
6
7
8 9 10
2
RMS9C MicroVersa Trip Plus™ or MicroVersa Trip PM™ Digital RMS Trip Units (ANSI) Instantaneous
5.0
I2t Out 1 .9 .8
7.0
.7 .6
9.0
.5
Max
.4 .3
1 .9 .8 .7
.9 .8
.6
.6
.5
.5
.4
.4
1 .9 .8
1
Instantaneous Pickup Settings in Multiples of Rating Plug Amps (X)
.7
.7
Pickup Settings on Trip Units without Short-Time Function: For (S) = 150 thru 3200 amps: 1.5 to 10.0, in increments of 0.5 For (S) = 4000 amps: 1.5 to 9.0, in increments of 0.5 Pickup Settings on Trip Units with Short-Time Function: For (S) = 150 thru 2000 amps: 1.5 to 15.0, in increments of 0.5 For (S) = 3200 amps: 1.5 to 13.0, in increments of 0.5 For (S) = 4000 amps: 1.5 to 9.0, in increments of 0.5
.6 .5 .4
.3
.3
.2
.2
.2
.1 .09 .08
.1 .09 .08
.1 .09 .08
.1 .09 .08
.07
.07
.07
.07
.06
.06
.06
.06
.05
.05
.05
.05
.04
.04
.04
.04
.03
.03
.03
.03
.02
.02
.02
.01
.01
Application Determines End of Curve
Int .2
.3
Min
.01
.5 .6
.7 .8 .9 1
2
3
4
5
6
7 8 9 10
20
30
40
50
60 70 80 90
100
GES-9913
.02
7
2.5
6
Application Determines End of Curve
.02
Application Determines End of Curve
.5
.6
.7 .8 .9 1
MULTIPLES OF CURRENT SETTING (C)
2
3
4
5
6
7
8 9 10
MULTIPLES OF INSTANTANEOUS PICKUP SETTING
(Note: Does not include breaker clearing time.)
GE Consumer & Industrial Electrical Distribution Available Ratings (Amperes) Breaker Model GE, I-T-E®, Federal Pacific, Allis Chalmers, or Westinghouse
Frame 225A
600A 800A 1600A 2000A 3000A 3200A 4000A
Current Sensor (S) 150 225 225 600 150 400 800 800 1600 2000 3000 3200 4000
Rating Plug (X)
60, 80, 100, 125, 150 100, 150, 225 100, 150, 225 300, 400, 450, 500, 600 60, 80, 100, 125, 150 150, 200, 225, 250, 300, 400 300, 400, 450, 500, 600, 700, 800 300, 400, 450, 500, 600, 700, 800 600, 800, 1000, 1100, 1200, 1600 800, 1000, 1200, 1500, 1600, 2000 1200, 1600, 2000, 2500, 3000 1200, 1600, 2400, 3200 1600, 2000, 2500, 3000, 3600, 4000
Voltage Rating: 635 Vac, maximum
11.94 3M
Low-Voltage Power Circuit Breakers Conversion Kits with Enhanced MicroVersaTrip PlusTM or MicroVersaTrip PMTM Digital RMS Trip Units Long-Time Delay, Short-Time Delay, and Instantaneous Time-Current Curves Curves apply at 50 to 400 Hertz and from -20°C to 55°C Breaker ambient. Note: Operation above 60 Hertz requires thermal and interrupting derating of the circuit breaker.
GES-9913 Adjustments
Long-Time Function: Current settings (C): 0.5 to 1.1 in 0.05 increments, multiples of rating plug amps (X) Delay bands: 1, 2, 3, and 4 Short-Time Function Pickup settings: 1.5 to 9.0 in 0.5 increments, multiples of current setting (C) Delay bands: Min, Int, Max; I2t In, I2t Out Instantaneous Function: See table and curve above
Settings Glossary S = Current Sensor Rating in amps X = Rating Plug in amps C = Current Setting in amps H = Breaker Short-time Ampere Rating