PVSYST V6.53 Institute of energy science (Viet Nam) Page 1/4 Grid-Connected System: Simulation parameters Project :
Views 65 Downloads 3 File size 337KB
PVSYST V6.53
Institute of energy science (Viet Nam)
Page 1/4
Grid-Connected System: Simulation parameters Project :
DAK BLA SOLAR POWER PROJECT
Geographical Site
Dak Bla - Kon Tum
Situation Time defined as
Latitude Legal Time Albedo Dak Bla - Kon Tum
Meteo data:
Simulation variant :
Country
Vietnam
14.44° N Longitude 108.15° E Time zone UT+7 Altitude 600 m 0.20 Meteonorm 7.1 (1992-2000), Sat=100% - Synthetic
5MW Simulation date
25/12/17 14h40
Simulation parameters Collector Plane Orientation 18 Sheds Inactive band Shading limit angle
Tilt Pitch Top Gamma
Models used
Transposition
Horizon
Free Horizon
Near Shadings
Inverter pack
6.00 m 0.00 m 27.10 ° Perez
Azimuth Collector width Bottom Occupation Ratio Diffuse
0° 4.00 m 0.00 m 66.7 % Perez, Meteonorm
Mutual shadings of sheds
PV Array Characteristics Si-poly Model PV module Original PVsyst database Manufacturer Number of PV modules In series Total number of PV modules Nb. modules Array global power Nominal (STC) Array operating characteristics (50°C) U mpp Total area Module area Inverter Original PVsyst database Characteristics
16°
Model Manufacturer Operating Voltage Nb. of inverters
TP672P-330 Talesun Solar (Zhongli) 20 modules In parallel 18900 Unit Nom. Power At operating cond. 6237 kWp 674 V I mpp Cell area 36674 m²
945 strings 330 Wp 5615 kWp (50°C) 8329 A 33108 m²
Sunny Central 1000CP XT SMA 596-850 V Unit Nom. Power Max. power (=>25°C)
1000 kWac 1100 kWac
5 units
5000 kWac
Total Power
PV Array loss factors Array Soiling Losses Thermal Loss factor
Uc (const)
Wiring Ohmic Loss Global array res. Serie Diode Loss Voltage Drop LID - Light Induced Degradation Module Quality Loss Module Mismatch Losses Incidence effect, ASHRAE parametrization IAM =
29.0 W/m²K 1.4 mOhm 0.7 V
1 - bo (1/cos i - 1)
Loss Fraction Uv (wind)
2.0 % 0.0 W/m²K / m/s
Loss Fraction Loss Fraction Loss Fraction Loss Fraction Loss Fraction bo Param.
1.5 % at STC 0.1 % at STC 2.0 % 0.5 % 1.0 % at MPP 0.05
PVSYST V6.53
Institute of energy science (Viet Nam)
Page 2/4
Grid-Connected System: Simulation parameters (continued)
System loss factors AC loss, transfo to injection External transformer
User's needs :
Grid Voltage Wires: 3x30000.0 mm² Iron loss (24H connexion) Resistive/Inductive losses Unlimited load (grid)
110 kV 700 m 6130 W 19740.0 mOhm
Loss Fraction Loss Fraction Loss Fraction
0.0 % at STC 0.1 % at STC 1.0 % at STC
PVSYST V6.53
Institute of energy science (Viet Nam)
Page 3/4
Grid-Connected System: Main results Project :
DAK BLA SOLAR POWER PROJECT
Simulation variant :
5MW System type Sheds disposition, tilt Model Nb. of modules Model Nb. of units Unlimited load (grid)
Main system parameters PV Field Orientation PV modules PV Array Inverter Inverter pack User's needs Main simulation results System Production
Produced Energy Performance Ratio PR
Grid-Connected 16° azimuth TP672P-330 Pnom 18900 Pnom total Sunny Central 1000CP XT Pnom 5.0 Pnom total
8247 MWh/year 79.87 %
Specific prod.
Normalized productions (per installed kWp): Nominal power 6237 kWp
1322 kWh/kWp/year
Performance Ratio PR
6
1.0
PR : Performance Ratio (Yf / Yr) : 0.799
Lc : Collection Loss (PV-array losses) 0.81 kWh/kWp/day Ls : System Loss (inverter, ...) 0.1 kWh/kWp/day Yf : Produced useful energy (inverter output) 3.62 kWh/kWp/day 5
0.8
4 Performance Ratio PR
Normalized Energy [kWh/kWp/day]
0° 330 Wp 6237 kWp 1000 kW ac 5000 kW ac
3
0.6
0.4
2
0.2
1
0
Jan
Feb
Mar
Apr
May
Jun
Jul
Aug
Sep
Oct
Nov
0.0
Dec
Jan
Feb
Mar
Apr
May
Jun
Jul
Aug
5MW Balances and main results GlobHor
DiffHor
T Amb
GlobInc
GlobEff
EArray
E_Grid
kWh/m²
kWh/m²
°C
kWh/m²
kWh/m²
MWh
MWh
January
106.3
66.70
19.30
116.7
108.2
615.3
597.7
0.821
February
129.1
57.60
20.40
140.8
132.0
735.6
715.1
0.814
March
158.8
76.80
23.00
164.3
153.4
845.7
822.8
0.803
April
153.9
79.00
25.40
150.6
140.0
768.2
747.7
0.796
May
173.5
72.90
27.10
161.8
150.2
818.0
796.4
0.789
June
164.4
69.60
27.60
150.0
139.0
756.7
736.5
0.787
July
171.7
74.90
27.70
158.3
146.8
797.9
776.7
0.787
August
150.8
75.00
27.00
144.4
133.9
730.9
710.8
0.790
September
136.6
77.30
24.90
138.0
128.1
705.4
686.0
0.797
October
116.6
72.10
23.40
122.2
113.2
629.3
611.1
0.802
November
98.9
59.10
21.70
107.5
99.7
554.6
537.2
0.801
December
91.7
58.80
20.20
100.9
93.5
526.0
509.2
0.809
1652.3
839.79
23.99
1655.5
1538.2
8483.6
8247.2
0.799
Year Legends:
PR
GlobHor
Horizontal global irradiation
GlobEff
Effective Global, corr. for IAM and shadings
DiffHor
Horizontal diffuse irradiation
EArray
Effective energy at the output of the array
T Amb
Ambient Temperature
E_Grid
Energy injected into grid
GlobInc
Global incident in coll. plane
PR
Performance Ratio
Sep
Oct
Nov
Dec
PVSYST V6.53
Institute of energy science (Viet Nam)
Page 4/4
Grid-Connected System: Loss diagram Project :
DAK BLA SOLAR POWER PROJECT
Simulation variant :
5MW
Main system parameters PV Field Orientation PV modules PV Array Inverter Inverter pack User's needs
System type Sheds disposition, tilt Model Nb. of modules Model Nb. of units Unlimited load (grid)
Grid-Connected 16° azimuth TP672P-330 Pnom 18900 Pnom total Sunny Central 1000CP XT Pnom 5.0 Pnom total
0° 330 Wp 6237 kWp 1000 kW ac 5000 kW ac
Loss diagram over the whole year
1652 kWh/m² +0.2%
Horizontal global irradiation Global incident in coll. plane
-2.1%
Near Shadings: irradiance loss
-3.2% -2.0% 1538 kWh/m² * 36674 m² coll.
Soiling loss factor Effective irradiance on collectors
efficiency at STC = 17.02%
PV conversion
9601 MWh -0.9%
Array nominal energy (at STC effic.) PV loss due to irradiance level
-6.7%
PV loss due to temperature
-0.5% -2.0%
Module quality loss LID - Light induced degradation
-1.0%
Module array mismatch loss
-1.0%
Ohmic wiring loss Array virtual energy at MPP
-1.6%
Inverter Loss during operation (efficiency)
8485 MWh
0.0% 0.0% 0.0% 0.0% 0.0%
Inverter Loss over nominal inv. power Inverter Loss due to power threshold Inverter Loss over nominal inv. voltage Inverter Loss due to voltage threshold Night consumption Available Energy at Inverter Output
0.0% -1.1%
AC ohmic loss External transfo loss
8343 MWh
8247 MWh
IAM factor on global
Energy injected into grid