11.5. Datasheet Modulo de Control XP6C, FCM-1, FRM-1

Southern Peru Copper Corporation Ampliación Toquepala a 120,000 TMPD Documento No. PATCT-DA-296240-05-DS-039 Revisión 0

Views 71 Downloads 1 File size 2MB

Report DMCA / Copyright

DOWNLOAD FILE

Recommend stories

Citation preview

Southern Peru Copper Corporation Ampliación Toquepala a 120,000 TMPD Documento No. PATCT-DA-296240-05-DS-039 Revisión 0

SOUTHERN PERU COPPER CORPORATION MINA TOQUEPALA

PROYECTO NO. PATCT AMPLIACIÓN TOQUEPALA A 120,000 TMPD

CONTRATO NO. L7-T23-003

HOJA DE DATOS

XP6-C,XP-R FCM-1-REL (A) Series,FCM-1(A)&FRM-1(A) Series (NOTIFIER) Modulo de Control DOCUMENTO NO. PATCT-DA-296240-05-DS-039 REV. 0

O:\OT\(13) DOCUMENTOS\DS-Hoja de Datos\PATCT-DA-296240-05-DS-039_0.doc

O:\OT\(13) DOCUMENTOS\DS-Hoja de Datos\PATCT-DA-296240-05-DS-039_0.doc

Southern Peru Copper Corporation Ampliación Toquepala a 120,000 TMPD Documento No. PATCT-DA-296240-05-DS-039 Revisión 0

HOJA DE DATOS Este documento ha sido revisado como se indica a continuación. Los cambios posteriores a la Revisión 0 se identificarán en las barras verticales en el lado derecho de la página, con las adiciones debajo de la última revisión. Reemplace todas las páginas de este documento y destruya las copias superadas. Rev. No.

Originador

Fecha de Revisión

Descripción de la Revisión

A

Julio Plaza

20FEB2018

Revisión Interna

B

Julio Plaza

20FEB2018

Chequeo Cruzado

C

Julio Plaza

20FEB2018

Para Aprobación del Cliente

0

Julio Plaza

03ABR2018

Aprobado para Cotización

Nueva Emisión

Aprobadores HB/M3/SPCC

Re-emisión del Documento Entero

Firma Original

Fecha

Ingeniería SPCC Ingeniería M3 Gerente de Proyecto HB Ingeniería HB Líder de Disciplina HB Originador HB

____________________________________________________________________________________________ O:\OT\(13) DOCUMENTOS\DS-Hoja de Datos\PATCT-DA-296240-05-DS-039_0.doc Página 1 de 14

Southern Peru Copper Corporation Ampliación Toquepala a 120,000 TMPD Documento No. PATCT-DA-296240-05-DS-039 Revisión 0

HOJA DE DATOS

Esta página está en blanco intencionalmente

____________________________________________________________________________________________ O:\OT\(13) DOCUMENTOS\DS-Hoja de Datos\PATCT-DA-296240-05-DS-039_0.doc Página 2 de 14

DN-6924:A • H-353

XP6-C Six Circuit Supervised Control Module and SYNC-1 Accessory Card Intelligent Addressable Devices

General NOTIFIER’s XP6-C six-circuit supervised control module provides intelligent alarm systems with supervised monitoring of wiring to load devices that require an external power supply to operate, such as horns, strobes, or bells. Each module is intended for switching applications involving AC DC or audio, which require wiring supervision. Upon command from the control panel, the XP6-C will disconnect the supervision and connect the external power supply across the load device. The first module is addressed from 01 to 154 while the remaining modules are automatically assigned to the next five higher addresses. Each XP6-C module has terminals for connection to an external supply circuit for powering devices on its notification appliance circuit (NAC). One or multiple power supplies or amplifiers may be used.

Each XP6-C module features a short-circuit-protection monitor to protect the external power supply against short-circuit conditions on the NAC. When an alarm condition occurs, the relay which connects the external supply to the NAC will not be allowed to close if a short-circuit condition currently exists on the NAC. Additionally, an algorithm is incorporated to find shorts when the module is active. The XP6-C module will close all circuits that are not shorted to find the NAC with the problem. Each XP6-C module has panel-controlled green LED indicators. The panel can cause the LEDs to blink, latch on, or latch off. The SYNC-1 accessory card provides the XP6-C with additional functionality with compatible System Sensor SpectrAlert® and SpectrAlert Advance® audio/visual devices.

6924xp6c.jpg

NOTE: Provisions are included for disabling a maximum of three unused addresses.

Alarm current: 35 mA (assumes all six NACS have been switched once and all six LEDs solid ON). Temperature range: 32°F to 120°F (0°C to 49°C) for UL applications; –10°C to +55°C for EN54 applications. Humidity: 10% to 85% noncondensing for UL applications; 10% to 93% noncondensing for EN54 applications. Dimensions: 6.8" (172.72 mm) high x 5.8" (147.32 mm) wide x 1.25" (31.75 mm) deep. Shipping weight: 1.1 lb. (0.499 kg) including packaging.

Features • Six addressable Style B (Class B) or three addressable Style D (Class A) outputs that function as notification appliance/speaker/telephone circuits. • Removable 12 AWG (3.31 mm²) to 18 AWG (0.821 mm²) plug-in terminal blocks. • Status indicators for each point. • Unused addresses may be disabled(up to 3). • Rotary address switches. • FlashScan® or CLIP operation. • Optional SYNC-1 accessory card for SpectrAlert and SpectrAlert Advance devices. • Mount one or two modules in a BB-XP cabinet (optional). • Mount up to six modules on a CHS-6 chassis in a CAB-3 Series, CAB-4 Series, EQ Series, or BB-25 cabinet (optional). • Mounting hardware included.

Specifications Standby current: 2.25 mA (SLC current draw with all addresses used; if some addresses are disabled, the standby current decreases).

Mounting options: CHS-6 chassis, BB-25 cabinet, BB-XP cabinet, CAB-3/CAB-4 series backboxes and doors, or EQ Series cabinet. Wire gauge: 12 AWG (3.31 mm²) to 18 AWG (0.821 mm²), grounded. XP6-C is shipped in Class B position; remove shunt for Class A operation. Maximum SLC wiring resistance: 40 or 50 ohms, panel dependent. Maximum NAC wiring resistance: 40 ohms. Power rating per circuit: 63 W @ 70.7 VAC (UL applications only); 50 W @ 25 VAC. Current ratings: • • • • •

3.0 A @ 30 VDC maximum, resistive, non-coded. 2.0 A @ 30 VDC maximum, resistive, coded. 1.0 A @ 30 VDC maximum, inductive (L/R = 2 ms), coded. 0.5 A @ 30 VDC maximum, inductive (L/R = 5 ms), coded. 0.9 A @ 70.7 VAC maximum (UL only), resistive, noncoded. • 0.7 A @ 70.7 VAC maximum (UL only), inductive (PF = 0.35), non-coded.

DN-6924:A • 08/15/07 — Page 1 of 6

Compatible devices: See the documentation for your panel, and the NOTIFER Device Compatibility document. Contact NOTIFER. See also list of devices compatible with SYNC-1 below.

SYNC-1 Accessory Card The SYNC-1 accessory card is designed to operate with the XP6-C. It works with the SpectrAlert and the SpectrAlert Advance series of horns, strobes, and horn/strobes to provide a means of synchronizing the temporal-coded horns; synchronizing the one-second flash timing of the strobe; and silencing the horns of the horn/strobe combination over a two-wire circuit while leaving the strobes active. Each SYNC-1 accessory card is capable of synchronizing six Class B circuits or three Class A circuits. Maximum load on a loop: 3 A. Operating temperature: 32°F to 120°F (0°C to 49°C). Wire size: 12 to 18 AWG (3.31 to 0.821 mm²). Operating voltage range: 11 to 30 VDC FWR, filtered or unfiltered. Refer to notification appliance installation instructions for number of notification appliances and wire size. Compatible A/V devices: The SYNC-1 Accessory Card is compatible with all System Sensor SpectrAlert and SpectrAlert Advance Audio Visual Devices that have synchronization capability. Other manufacturers may be supported as well. Please refer to the latest Device Compatibility Document, PN 15378. NOTE: *SpectrAlert and SpectrAlert Advance products utilizing SYNC-1 module below.

Product Line Information

SYNC-1: Optional accessory card for synchronization of compatible System Sensor SpectrAlert horns, strobes, and horn/ strobes. BB-XP: Optional cabinet for one or two modules. Dimensions, DOOR: 9.234" (23.454 cm) wide (9.484" [24.089 cm] including hinges), x 12.218" (31.0337 cm) high, x 0.672" (1.7068 cm) deep; BACKBOX: 9.0" (22.860 cm) wide (9.25" [23.495 cm] including hinges), x 12.0" (30.480 cm) high x 2.75" (6.985 cm); CHASSIS (installed): 7.150" (18.161 cm) wide overall x 7.312" (18.5725 cm) high interior overall x 2.156" (5.4762 cm) deep overall. BB-25: Optional cabinet for up to six modules mounted on CHS-6 chassis (below). Dimensions, DOOR: 24.0" (60.96 cm) wide x 12.632" (32.0852 cm) high, x 1.25" (3.175 cm) deep, hinged at bottom; BACKBOX: 24.0" (60.96 cm) wide x 12.550" (31.877 cm) high x 5.218" (13.2537 cm) deep. CHS-6: Chassis, mounts up to six modules in a CAB-3 Series (see DN-3549), CAB-4 Series (see DN-6857) cabinet, or EQ Series cabinet.

Agency Listings and Approvals These listings and approvals apply to the modules specified in this document. In some cases, certain modules or applications may not be listed by certain approval agencies, or listing may be in process. Consult factory for latest listing status. • • • • • •

UL Listed: S3705 (S3705 SYNC-1) ULC Listed: S635/CS118 (XP6-CA) MEA Listed: 43-02-E / 226-03-E (SYNC-1) FM Approved (Local Protective Signaling) CSFM: 7300-0028:219 7300-1653:100 (SYNC-1) Maryland State Fire Marshal: Permit # 2106 (XP6-C)

XP6-C: Six-circuit supervised control module. XP6-CA: Same as above with ULC Listing.

SYNC-1

Module setup: Before installing the accessory card on the XP6-C module, add the shunt to the board where indicated if any horns are required to sound in temporal pattern. Parts included with SYNC-1: Two shunts, four screws, and two standoffs. See installation instructions for details on mounting and wiring the accessory card and module.

XP6-C

6924sync.wmf

Figure 1 Mounting the SYNC-1 accessory card to the XP6-C module

Page 2 of 6 — DN-6924:A • 08/15/07

6924wir1.wmf

6924wirblock.wmf

Wiring Diagrams

NOTE: EOL relay coil connections must be made using EOL relay connector assemblies on T10 – T16 in event that all NACs on the PCB have dedicated supplies.

6924wir2.wmf

Figure 2 Example of Class B, Style Y NAC configuration with a single supply dedicated to a single NAC

Figure 3 Example of Class B, Style Y NAC configuration with a single supply shared by two NACs

DN-6924:A • 08/15/07 — Page 3 of 6

6924wir3.wmf 6924wir4.wmf

Figure 4 Example of Class A, Style Z NAC configuration with a single supply dedicated to a single NAC

Figure 5 Example of Class A, Style Z NAC configuration with a single supply shared by 2 NACs

Page 4 of 6 — DN-6924:A • 08/15/07

6924wir5.wmf 6924wir6.wmf

Figure 6 Example of Class B, Style Y audio NAC configuration

Figure 7 Example of Class A, Style Z audio NAC configuration

DN-6924:A • 08/15/07 — Page 5 of 6

6924wir7.wmf

NOTE: Supply is shared by NACs +0 and +1 (on PCB #1) as well as +3, +4, and +5 (on PCB # 2). Refer to Figure 2 through Figure 5 for typical NAC wiring. Make certain that the lip on the long power supply jumper engages the retaining tab on T10 or T16 as shown in detail view A-A.

Figure 8 Example of multiple boards sharing the same external power supply

FlashScan®, NOTIFIER®, SpectrAlert®, SpectrAlert Advance®, and System Sensor® are registered trademarks of Honeywell International Inc. ©2007 by Honeywell International Inc. All rights reserved. Unauthorized use of this document is strictly prohibited.

This document is not intended to be used for installation purposes. We try to keep our product information up-to-date and accurate. We cannot cover all specific applications or anticipate all requirements. All specifications are subject to change without notice. Made in the U.S. A.

For more information, contact Notifier. Phone: (203) 484-7161, FAX: (203) 484-7118. www.notifier.com Page 6 of 6 — DN-6924:A • 08/15/07

DN-6926:A1 • A-115

XP6-R Six Relay Control Module Intelligent Fire Alarm Control Panels

General NOTIFIER’s XP6-R six-relay control module provides an intelligent fire alarm system with six Form-C relays. The first module is addressed from 01 to 154 while the remaining modules are automatically assigned to the next five higher addresses. Provisions are included for disabling a maximum of three unused modules. A single isolated set of dry relay contacts is provided for each module address, which is capable of being wired for either a normally-open or normally-closed operation. The module allows the control panel to switch these contacts on command. No supervision is provided for the controlled circuit. Each XP6-R module has panel-controlled green LED indicators. The panel can cause the LEDs to blink, latch on, or latch off.

• Six addressable Form-C relay contacts. • Removable 12 AWG (3.25 mm²) to 18 AWG (0.9 mm²) plugin terminal blocks. • Status indicators for each point. • Unused addresses may be disabled. • Rotary address switches. • FlashScan® or CLIP operation. • Mount one or two modules in a BB-XP cabinet (optional). • Mount up to six modules on a CHS-6 chassis in a CAB-3 Series, CAB-4 Series, EQ Series, or BB-25 cabinet (optional). • Mounting hardware included.

Specifications Standby current: 1.45 mA (SLC current draw with all addresses used; if some addresses are disabled, the standby current decreases). Alarm current: 32 mA (assumes all six relays have been switched once and all six LEDs solid ON). Temperature range: 32°F to 120°F (0°C to 49°C).

6926xp6r.jpg

Features

• • • • • • •

3.0 A @ 30 VDC maximum, resistive, non-coded. 2.0 A @ 30 VDC maximum, resistive, coded. 1.0 A @ 30 VDC maximum, inductive (L/R = 2 ms), coded. 0.5 A @ 30 VDC maximum, inductive (L/R = 5 ms), coded. 0.9 A @ 110 VDC maximum, resistive, non-coded. 0.9 A @ 125 VAC maximum, resistive, non-coded. 0.7 A @ 70.7 VAC maximum, inductive (PF = 0.35), noncoded. • 0.3 A @ 125 VAC maximum, inductive (PF = 0.35), noncoded. • 1.5 A @25 VAC maximum, inductive (PF = 0.35), noncoded. • 2.0 A @25 VAC maximum, inductive (PF = 0.35), noncoded.

Humidity: 10% to 93% noncondensing.

Agency Listings and Approvals

Dimensions: 6.8" (172.72 mm) high x 5.8" (147.32 mm) wide x 1.0" (25.40 mm) deep.

These listings and approvals apply to the modules specified in this document. In some cases, certain modules or applications may not be listed by certain approval agencies, or listing may be in process. Consult factory for latest listing status.

Shipping weight: 1.1 lb. (0.499 kg) including packaging. Mounting options: CHS-6 chassis, BB-25 cabinet, BB-XP cabinet, CAB-3 Series (see DN-3549) cabinet, CAB-4 Series (see DN-6857) cabinet, or EQ Series cabinet. Wire gauge: 12 AWG (3.25 mm²) to 18 AWG (0.9 mm²). Maximum SLC wiring resistance: 40 dependent.

or 50 ohms, panel

Relay current: 30 mA/relay pulse (15.6 ms pulse duration), pulse under panel control.

• • • • • •

UL Listed: S635 ULC Listed: S635 (XP6-RA) MEA Listed: 368-01-E CSFM: 7300-0028:219 Maryland State Fire Marshall: Permit # 2099 FM Approved (Light Protective Signaling Only)

Relay contact ratings: 30 VDC; 70.7 VAC. Current ratings:

DN-6926:A1 • 02/9/10 — Page 1 of 2

Product Line Information XP6-R: Six-relay control module. XP6-RA: Same as above with ULC Listing. BB-XP: Optional cabinet for one or two modules. Dimensions, DOOR: 9.234" (23.454 cm) wide (9.484" [24.089 cm] including hinges), x 12.218" (31.0337 cm) high, x 0.672" (1.7068 cm) deep; BACKBOX: 9.0" (22.860 cm) wide (9.25" [23.495 cm] including hinges), x 12.0" (30.480 cm) high x 2.75" (6.985 cm); CHASSIS (installed): 7.150" (18.161 cm) wide overall x 7.312"

(18.5725 cm) high interior overall x 2.156" (5.4762 cm) deep overall. BB-25: Optional cabinet for up to six modules mounted on CHS-6 chassis (below). Dimensions, DOOR: 24.0" (60.96 cm) wide x 12.632" (32.0852 cm) high, x 1.25" (3.175 cm) deep, hinged at bottom; BACKBOX: 24.0" (60.96 cm) wide x 12.550" (31.877 cm) high x 5.218" (13.2537 cm) deep. CHS-6: Chassis, mounts up to six modules in a CAB-3 Series (see DN-3549), CAB-4 Series (see DN-6857), or EQ Series (see DN-60229) cabinet.

Notifier® and FlashScan® are registered trademarks of Honeywell International Inc. ©2009 by Honeywell International Inc. All rights reserved. Unauthorized use of this document is strictly prohibited.

This document is not intended to be used for installation purposes. We try to keep our product information up-to-date and accurate. We cannot cover all specific applications or anticipate all requirements. All specifications are subject to change without notice. Made in the U.S. A.

For more information, contact Notifier. Phone: (203) 484-7161, FAX: (203) 484-7118. www.notifier.com Page 2 of 2 — DN-6926:A1 • 02/9/10

DN-60390:B • H-235

FCM-1-REL(A) Releasing Control Module Intelligent/Addressable Devices

General The FCM-1-REL Releasing Control Module is specifically designed for fire suppression releasing applications in FlashScan® systems. Power to the release agent solenoid(s) runs through the module for full-time monitoring and supervision.

NOTE: FCM-1-REL is required for all new FlashScan-mode releasing applications with NFS2-3030 (version 14.0 or higher), NFS2-640 (version 12.0 or higher) and NFS-320(E)(C) (version 12.0 or higher) panels. Use FCM-1 for releasing applications on NFS-640, NFS-3030, and all CLIP mode panels.

Features • • • • • • • • • • •

Redundant protocol for added protection Configurable for Class A or Class B operation External supply voltage monitoring Can power one 24V or two 12V solenoids SEMS screws for easing wiring Panel controlled status LED Analog communications Rotary address switches Low standby current Mounts in standard 4" (10.16 cm) junction box FlashScan operation

Specifications GENERAL SPECIFICATIONS • Operating Voltage: 15 to 32 VDC • Communication Line Loop Impedance: 40 Ohm max. • Temperature Range: 14°F to 140°F (-10° to 60°C) • Relative Humidity: 10% to 95% noncondensing • Shipping Weight: 5.5 oz (156 g) • Dimensions: 4.275" W × 4.675" H × 1.400" D (10.86 cm W × 11.87 cm H × 3.56 cm D)

60390cov.jpg

The FCM-1-REL Releasing Control Module uses a redundant protocol; the module must be armed with a pair of signals in order to activate. It will then enter a 3-second window awaiting a pair of confirmation signals. If no confirmation is received, the module will automatically reset. It also supervises the wiring to the connected load and reports the status to the panel as NORMAL, OPEN, or SHORT CIRCUIT. The module has two pairs of output termination points available for fault-tolerant wiring and a panel-controlled LED indicator. The module may be connected to either one 24VDC solenoid or up to two 12VDC solenoids (in series). To ensure proper operation, this module shall be connected to a compatible Notifier system control panel only (list available from Notifier). In addition, please refer to Notifier Device Compatibility Document PN 15378 for the list of compatible solenoids.

FCM-1-REL

EXTERNAL SUPPLY • Normal Operating Voltage: 24 VDC Nominal • Maximum Line Loss: 2.3 VDC (total allowable loss from power supply to module and from module to solenoid) • Minimum Operating Voltage to Activate Solenoid: 18 VDC (at solenoid) • Standby Current: 6.4 mA • Activation Current: 10 mA SOLENOID • Supervisory Loop Voltage: 3.3 V • Supervisory Loop Current (Normal): 30 mA • Maximum Activation Current: 2 A

Product Line Information NOTE: “A” suffix indicates ULC Listed model.

FCM-1-REL(A): Releasing Control Module. SMB500: Optional Surface-Mount Backbox. CB500: Control Module Barrier — required by UL for separating power-limited and non-power limited wiring in the same junction box as FCM-1-REL.

SLC • Average Operating Current: 700 µA max @ 24 VDC (one communication every 5 sec. with LED enabled) • Maximum Activation Current: 9.0 mA (LED on) DN-60390:B • 05/20/2009 — Page 1 of 2

Agency Listings and Approvals These listings and approvals apply to the modules specified in this document. In some cases, certain modules or applications may not be listed by certain approval agencies, or listings may be in process. Consult factory for latest listing status. • • • •

UL Listed: S635 ULC Listed: (FCM-1-RELA) FM Approved CSFM: 7300-0028:249

Notifier® and FlashScan® are registered trademarks of Honeywell International Inc. ©2009 by Honeywell International Inc. All rights reserved. Unauthorized use of this document is strictly prohibited.

This document is not intended to be used for installation purposes. We try to keep our product information up-to-date and accurate. We cannot cover all specific applications or anticipate all requirements. All specifications are subject to change without notice. Made in the U.S. A.

For more information, contact Notifier. Phone: (203) 484-7161, FAX: (203) 484-7118. www.notifier.com Page 2 of 2 — DN-60390:B • 05/20/2009

DN-6724:B3

FCM-1(A) & FRM-1(A) Series Control and Relay Modules Intelligent / Addressable Devices

General FCM-1(A) Control Module: The FCM-1(A) Addressable Control Module provides Notifier intelligent fire alarm control panels a circuit for Notification Appliances (horns, strobes, speakers, etc.). Addressability allows the FCM-1(A) to be activated, either manually or through panel programming, on a select (zone or area of coverage) basis. FRM-1(A) Relay Module: The FRM-1(A) Addressable Relay Module provides the system with a dry-contact output for activating a variety of auxiliary devices, such as fans, dampers, control equipment, etc. Addressability allows the dry contact to be activated, either manually or through panel programming, on a select basis.

7000cov.JPG

FlashScan® (U.S. Patent 5,539,389) is a communication protocol developed by NOTIFIER Engineering that greatly enhances the speed of communication between analog intelligent devices. Intelligent devices communicate in a grouped fashion. If one of the devices within the group has new information, the panel CPU stops the group poll and concentrates on single points. The net effect is response speed greater than five times that of other designs.

FCM-1(A)

Features • Built-in type identification automatically identifies these devices to the control panel. • Internal circuitry and relay powered directly by two-wire SLC loop. The FCM-1(A) module requires power (for horns, strobes, etc.), or audio (for speakers). • Integral LED “blinks” green each time a communication is received from the control panel and turns on in steady red when activated. • LED blink may be deselected globally (affects all devices). • High noise immunity (EMF/RFI). • The FCM-1(A) may be used to switch 24-volt NAC power, audio (up to 70.7 Vrms). • Wide viewing angle of LED. • SEMS screws with clamping plates for wiring ease. • Direct-dial entry of address 01– 159 for FlashScan loops, 01 – 99 for CLIP mode loops. • Speaker, and audible/visual applications may be wired for Class B or A (Style Y or Z).

Applications The FCM-1(A) is used to switch 24 VDC audible/visual power, high-level audio (speakers). The FRM-1(A) may be programmed to operate dry contacts for applications such as door holders or Air Handling Unit shutdown, and to reset four-wire smoke detector power.

• The FCM-1(A) is configured for a single Class B (Style Y) or Class A (Style Z) Notification Appliance Circuit. • The FRM-1(A) provides two Form-C dry contacts that switch together.

Operation Each FCM-1(A) or FRM-1(A) uses one of 159 possible module addresses on a SLC loop (99 on CLIP loops). It responds to regular polls from the control panel and reports its type and status, including the open/normal/short status of its Notification Appliance Circuit (NAC). The LED blinks with each poll received. On command, it activates its internal relay. The FCM-1(A) supervises Class B (Style Y) or Class A (Style Z) notification or control circuits. Upon code command from the panel, the FCM-1(A) will disconnect the supervision and connect the external power supply in the proper polarity across the load device. The disconnection of the supervision provides a positive indication to the panel that the control relay actually turned ON. The external power supply is always relay isolated from the communication loop so that a trouble condition on the external power supply will never interfere with the rest of the system. Rotary switches set a unique address for each module. The address may be set before or after mounting. The built-in TYPE CODE (not settable) will identify the module to the control panel, so as to differentiate between a module and a sensor address.

NOTE: Refer to the SLC Manual (PN 51253) for details regarding releasing applications with the FCM-1(A). Refer to the FCM-1-REL datasheet (DN-60390) for new FlashScan® releasing applications.

Specifications for FCM-1(A)

Construction

Maximum current draw: 6.5 mA (LED on).

• The face plate is made of off-white heat-resistant plastic. • Controls include two rotary switches for direct-dial entry of address (01-159).

Average operating current: 350 μA direct poll, 375 μA group poll with LED flashing, 485 μA Max. (LED flashing, NAC shorted.)

Normal operating voltage: 15 to 32 VDC.

DN-6724:B3 • 2/17/2011 — Page 1 of 2

Maximum NAC Line Loss: 4 VDC. External supply voltage (between Terminals T10 and T11): Maximum (NAC): Regulated 24 VDC; Maximum (Speakers): 70.7 V RMS, 50W. Drain on external supply: 1.7 mA maximum using 24 VDC supply; 2.2 mA Maximum using 80 VRMS supply. Max NAC Current Ratings: For class B wiring system, the current rating is 3A; For class A wiring system, the current rating is 2A. Temperature range: 32°F to 120°F (0°C to 49°C).

Contact Ratings for FRM-1(A) Current Rating

Load Description

Application

30 VDC

Resistive

Non-Coded

2A

30 VDC

Resistive

Coded

.9 A

110 VDC

Resistive

Non-Coded

.9 A

125 VDC

Resistive

Non-Coded

.5 A

30 VDC

Inductive (L/R=5ms)

Coded

1A

30 VDC

Inductive (L/R=2ms)

Coded

.3 A

125 VAC

Inductive (PF=0.35)

Non-Coded

1.5 A

25 VAC

Inductive (PF=0.35)

Non-Coded

.7 A

70.7 VAC

Inductive (PF=0.35)

Non-Coded

2A

25 VAC

Inductive (PF=0.35)

Non-Coded

3A

Maximum Voltage

Humidity range: 10% to 93% non-condensing. Dimensions: 4.5" (114.3 mm) high x 4" (101.6 mm) wide x 1.25" (31.75 mm) deep. Mounts to a 4" (101.6 mm) square x 2.125" (53.975 mm) deep box. Accessories: SMB500 Electrical Box; CB500 Barrier

Specifications for FRM-1(A) Normal operating voltage: 15 to 32 VDC. Maximum current draw: 6.5 mA (LED on). Average operating current: 230 μA direct poll; 255 μA group poll. EOL resistance: not used. Temperature range: 32°F to 120°F (0°C to 49°C).

NOTE: Maximum (Speakers): 70.7 V RMS, 50 W

Humidity range: 10% to 93% non-condensing. Dimensions: 4.5" (114.3 mm) high x 4" (101.6 mm) wide x 1.25" (31.75 mm) deep. Mounts to a 4" (101.6 mm) square x 2.125" (53.975 mm) deep box. Accessories: SMB500 Electrical Box; CB500 Barrier

Agency Listings and Approvals In some cases, certain modules may not be listed by certain approval agencies, or listing may be in process. Consult factory for latest listing status. • • • • • •

UL: S635 ULC: S3705 (A version only) FM Approved CSFM: 7300-0028:0219 MEA: 14-00-E FDNY: COA #6067, #6065

Product Line Information NOTE: “A” suffix indicates ULC Listed model.

FCM-1(A): Intelligent Addressable Control Module. FRM-1(A): Intelligent Addressable Relay Module. A2143-20: Capacitor, required for Class A (Style Z) operation of speakers. SMB500: Optional Surface-Mount Backbox. CB500: Control Module Barrier — required by UL for separating power-limited and non-power limited wiring in the same junction box as FCM-1(A). NOTE: For installation instructions, see the following documents: • FCM-1(A) Installation document I56-1169. • FRM-1(A) Installation document I56-3502. • Notifier SLC Wiring Manual, document 51253.

Notifier® and FlashScan® are registered trademarks of Honeywell International Inc. ©2011 by Honeywell International Inc. All rights reserved. Unauthorized use of this document is strictly prohibited.

This document is not intended to be used for installation purposes. We try to keep our product information up-to-date and accurate. We cannot cover all specific applications or anticipate all requirements. All specifications are subject to change without notice. Made in the U.S. A.

For more information, contact Notifier. Phone: (203) 484-7161, FAX: (203) 484-7118. www.notifier.com Page 2 of 2 — DN-6724:B3 • 2/17/2011