TURCK Switching Amplifiers

The MK13-UNF-Ex0/24VDC and MK13-UPF-Ex0/24VDC are single channel switching amplifiers with intrinsically safe input circuits. They are used to isolate and transfer discrete signals from a hazardous location to a non-hazardous location. Inputs are typically NAMUR sensors or dry contacts, although devices providing a variable resistance conforming to DIN 19234 may be used - e.g. variable resistors, thermistors, etc. PNP NPN

- MK13-UPF-Ex0/24VDC - MK13-UNF-Ex0/24VDC

Each provide two short-circuit protected transistor outputs. A three-position switch on the front cover selects the output mode. Positions “A”, “R” and “V” represent direct mode (N.O.), inverse mode (N.C.) and complementary mode, respectively. The output mode is dependent on the input device. Refer to Truth Table. In positions “A” and “R”, output 1A follows the input signal, while the Alarm/1B output provides indication of faults in the input circuit. The Alarm/1B output remains energized during normal operation. In position “V”, the Alarm/1B output provides an output complementary to output 1A. No alarm indication is provided in position “V”. The input circuit is monitored for short-circuit and wire-break. If a fault in the input circuit occurs, both outputs are de-energized and the green LED is switched off.

MK13-UNF-Ex0/24VDC MK13-UPF-Ex0/24VDC

When dry contacts are the input device, the input circuit monitoring function must be turned off by jumpering terminals 3-4, or resistors must be added to the switch as shown in Contact Configuration. A yellow LED indicates switching status.

Connection Diagram

B9ClearwaterTURCK 3000 Campus Drive Minneapolis, MN 55441 Application Support: Fax: (763) 553-0708 www.turck.com TechInc. - Phone: 800.894.0412 - Fax: 208.368.0415 - Web:1-800-TURCK-IS www.clrwtr.com - Email: [email protected]

Type ID Number Power Supply Supply voltage Current consumption Galvanic isolation

MK13-UNF-Ex0/24VDC M7505400

MK13-UPF-Ex0/24VDC M7505200

10-30 VDC, £10% ripple approx. 20 mA between hazardous and non-hazardous circuits, test voltage 2.5 kVrms

10-30 VDC, £10% ripple approx. 20 mA between hazardous and non-hazardous circuits, test voltage 2.5 kVrms

Input Circuits Nominal operating characteristics (per DIN 19234) - Voltage 8V - Current 8 mA - Switching threshold 1.55 mA

8V 8 mA 1.55 mA

Intrinsic Safety Parameters

See page K10

See page K10

Output Circuits Voltage drop Switching current, each output Switching frequency

two NPN transistor outputs £2.5 V 100 mA, short-circuit protected £3 kHz

two PNP transistor outputs £2.5 V 100 mA, short-circuit protected £3 kHz

Housing Style

Diagram A (page A17)

Diagram A (page A17)

Switching Amplifiers

Selectable Fault Output Programmable Line Monitoring MK13-UNF-Ex0/24VDC MK13-UPF-Ex0/24VDC

Contact Configuration

Truth Table Input (Terminal 1-2)

Programming

A A R R V V

Dry Contacts

Inductive NAMUR

Capacitive NAMUR

Output (term. 3-4 jumpered)

Input

Short or Wire-Break

Normal Channel

A/R Switch Position

Output (terminals 3-4 open)

LED

Channel

Normal

LED

Dry Contacts

Channel

LED

1A

Yellow

1A

Yellow

1A

Yellow

Alarm/1B

Green

Alarm/1B

Green

Alarm/1B

Green

Off

Off

Off

Off

Off

Off

On

On

Off

Off

On

On

On

On

Off

Off

On

On

On

On

Off

Off

On

On

On

On

Off

Off

On

On

On

On

Off

Off

On

On

Off

Off

Off

Off

Off

Off

On

On

Off

Off

On

On

On

On

Off

Off

On

On

On

On

Off

Off

Off

On

Off

Off

Off

Off

Off

Off

On

On

Off

Off

On

On

Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: [email protected]

TURCK Switching Amplifiers

These devices are two-channel switching amplifiers with intrinsically safe input circuits. They are used to isolate and transfer discrete signals from a hazardous location to a non-hazardous location. Inputs are typically NAMUR sensors or dry contacts, although devices providing a variable resistance conforming to DIN 19234 may be used - e.g. variable resistors, thermistors, etc. Each device provides one SPDT relay output per channel. When the output is energized, the 2-color switching status LED illuminates yellow. Six programming switches, three per channel, located on the front cover of each device enable selection of the output mode, as well as separate activation of wire-break and short-circuit monitoring. The switches labeled “A/R” select the output mode for each channel. Positions “A” and “R” represent direct mode (N.O.) and inverse mode (N.C.), respectively. The output function is dependent on the input device. See the truth table opposite for detailed output function. The switches labeled “DB” and “K” activate wire-break and short-circuit monitoring of the input circuit, respectively. When these switches are set to ON and the corresponding fault in the input circuit occurs, the respective output is de-energized and the 2-color switching status LED illuminates red. If dry contacts are the input devices, resistors must be connected to the contacts or the “DB” and “K” switches must be set to OFF. See the Contact Configuration specification for correct resistor installation. A green LED indicates “Power ON” status.

MK13-22Ex0-R/24VDC MK13-22Ex0-R/115VAC MK13-22Ex0-R/230VAC

Connection Diagram

B21 3000 Campus Drive Minneapolis, MN 55441 Application Support: Fax: (763) 553-0708 www.turck.com ClearwaterTURCK TechInc. - Phone: 800.894.0412 - Fax: 208.368.0415 - Web:1-800-TURCK-IS www.clrwtr.com - Email: [email protected]

Type ID Number

MK13-22Ex0-R/24VDC M7541127

MK13-22Ex0-R/115VAC M7541122

MK13-22Ex0-R/230VAC M7541120

10-30 VDC, £10% ripple £1.5 W between input, output and supply circuits, test voltage 2.5 kVrms

98-126 VAC, 48-62 Hz £50 mA between input, output and supply circuits, test voltage 2.5 kVrms

196-253 VAC, 48-62 Hz £30 mA between input, output and supply circuits, test voltage 2.5 kVrms

Input Circuits Nominal operating characteristics (per DIN 19234) - Voltage 8V - Current 8 mA - Switching threshold 1.55 mA

8V 8 mA 1.55 mA

8V 8 mA 1.55 mA

Intrinsic Safety Parameters

See page K10

See page K10

See page K10

Output Circuits Switching voltage Switching current per channel Maximum load Contact material Switching frequency

one SPDT relay per channel 250 VAC / 120 VDC 2A 500 VA / 60 W AgCdO +3m Au £10 Hz

one SPDT relay per channel 250 VAC / 120 VDC 2A 500 VA / 60 W AgCdO +3m Au £10 Hz

one SPDT relay per channel 250 VAC / 120 VDC 2A 500 VA / 60 W AgCdO +3m Au £10 Hz

LED Indications Power “On” Output energized Fault indication

green yellow red

green yellow red

green yellow red

Housing Style

Diagram D (page A17)

Diagram D (page A17)

Diagram D (page A17)

Power Supply Supply voltage Power consumption Galvanic isolation

Contact Configuration

Truth Table Output (DB and/or K on)

Input

Programming

(terminals 1-5, 2-6)

A/R Switch Position

Dry Contacts

Inductive NAMUR

Capacitive NAMUR

Input

Short or Wire-break

Normal Chan.1 Chan.2

LED Yellow

Chan.1 Chan.2

LED Red

A

De-ener.

Off

De-ener.

A

Ener.

On

R

Ener.

R

De-ener.

Output (DB & K off) Normal

Dry Contacts

Channel 1 Channel 2

LED Yellow

On

De-energized

Off

De-ener.

On

Energized

On

On

De-ener.

On

Energized

On

Off

De-ener.

On

De-energized

Off

Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: [email protected]

Switching Amplifiers

Two-Channel SPDT Relay Output Programmable Line Monitoring MK13-22Ex0-R/...(24VDC/115VAC/230VAC)

TURCK Switching Amplifiers These devices are single channel switching amplifiers with intrinsically safe input circuits. They are used to isolate and transfer discrete signals from a hazardous location to a non-hazardous location. Inputs are typically NAMUR sensors or dry contacts, although devices providing a variable resistance conforming to DIN 19234 may be used - e.g. variable resistors, thermistors, etc. Three programming switches on the front cover of each device enable selection of the output mode, and separate activation of wire-break and short-circuit monitoring. The switch labeled “A/R” selects the output mode. Positions “A” and “R” represent direct mode (N.O.) and inverse mode (N.C.), respectively. The output function is dependent on the input device. See the truth table opposite for detailed output function. The switches labeled “DB” and “K” activate wire-break and short-circuit monitoring of the input circuit, respectively. When these switches are set to ON and the corresponding fault in the input circuit occurs, the respective output is de-energized and the switching status LED illuminates red. If dry contacts are the input devices, resistors must be connected to the contacts or the “DB” and “K” switches must be set to OFF. See the Contact Configuration specification for correct resistor installation. A green LED indicates “Power ON” status. A 2-color LED indicates the switching status (yellow) as well as input circuit fault conditions (red). MK13-11Ex0-T/*** (24VDC, 115VAC, 230VAC) These devices provide one potential-free transistor output that follows the input signal. If wire-break and/or short-circuit monitoring of the input circuit are activated, the switching status LED will illuminate red and the output will de-energize upon detection of a fault.

MK13-11Ex0-T/24VDC MK13-11Ex0-T/115VAC MK13-11Ex0-T/230VAC MK13-12Ex0-T/24VDC MK13-12Ex0-T/115VAC MK13-12Ex0-T/230VAC MK13-121Ex0-T/24VDC MK13-121Ex0-T/115VAC MK13-121Ex0-T/230VAC

MK13-12Ex0-T/*** (24VDC, 115VAC, 230VAC) These devices provide two potential-free transistor outputs connected in parallel. Both outputs follow the input signal. If wire-break and/or short-circuit monitoring of the input circuit are activated, the switching status LED will illuminate red and both outputs will de-energize upon detection of a fault. MK13-121Ex0-T/*** (24VDC, 115VAC, 230VAC) These devices provide two potential-free transistor outputs, one follows the input signal and the other provides indication of faults in the input circuit when wire-break and/or short-circuit monitoring of the input circuit are activated. When a fault is detected, the switching status LED will illuminate red and the transistor and alarm outputs will de-energize.

Connection Diagram

B17 3000 Campus Drive Minneapolis, MN 55441 Application Support: Fax: (763) 553-0708 www.turck.com ClearwaterTURCK TechInc. - Phone: 800.894.0412 - Fax: 208.368.0415 - Web:1-800-TURCK-IS www.clrwtr.com - Email: [email protected]

Potential-Free Transistor Output Programmable Line Monitoring MK13-11Ex0-T/...(24VDC/115VAC/230VAC) MK13-12Ex0-T/...(24VDC/115VAC/230VAC) MK13-121Ex0-T/...(24VDC/115VAC/230VAC) MK13-11Ex0-T/*** M7542107 M7542102 M7542100

MK13-12Ex0-T/*** M7541157 M7541152 M7541150

MK13-121Ex0-T/*** M7542267 M7542262 M7542260

10-30 VDC, £10% ripple 98-126 VAC, 48-62 Hz 196-253 VAC, 48-62 Hz DC: £1 W AC: £1.5 VA between input, output and supply circuits, test voltage 2.5 kVrms

10-30 VDC, £10% ripple 98-126 VAC, 48-62 Hz 196-253 VAC, 48-62 Hz DC: £1.1 W AC: £40 mA between input, output and supply circuits, test voltage 2.5 kVrms

10-30 VDC, £10% ripple 98-126 VAC, 48-62 Hz 196-253 VAC, 48-62 Hz DC: £1.1 W AC: £40 mA between input, output and supply circuits, test voltage 2.5 kVrms

See page K10

See page K10

See page K10

8V 8 mA 1.55 mA

8V 8 mA 1.55 mA

Switching voltage Switching current Switching frequency Voltage drop

one potential-free transistor, short-circuit protected 30 VDC 50 mA £3 kHz £2.5 V

two potential-free transistors, short-circuit protected 30 VDC 50 mA £3 kHz £2.5 V

two potential-free transistors, short-circuit protected 30 VDC 50 mA £3 kHz £2.5 V

Housing Style

Diagram C (page A17)

Diagram C (page A17)

Diagram C (page A17)

Power Supply Supply voltage - 24 VDC - 115 VAC - 230 VAC Power consumption Galvanic isolation

Intrinsic Safety Parameters

Input Circuits Nominal operating characteristics (per DIN 19234) - Voltage 8V - Current 8 mA - Switching threshold 1.55 mA

Switching Amplifiers

Type ID Number - 24 VDC - 115 VAC - 230 VAC

Contact Configuration

Output Circuits

Truth Table Output (DB and/or K on)

Input

Programming

(terminals 1-4) Normal Output

A/R Switch Position

Dry Contacts

Inductive NAMUR

Capacitive NAMUR

LED

1, (2)

On

R

Off On

Off

Off On

Off

Off

Off On

Off Off

On

Off On

On On

On On

Off

On

Yellow On

Off On

On Off

Off

LED

1

On Off

On

Output

Dry Contacts

(2, Alarm)

Off Off

On

R

Red (Alarm)

Off

Normal

LED

1, (2)

(Alarm)

A

Output

Yellow

A

Input

Short or Wire-break

Output (DB & K off)

On On

Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: [email protected]

TURCK Switching Amplifiers These devices are single channel switching amplifiers with intrinsically safe input circuits. They are used to isolate and transfer discrete signals from a hazardous location to a non-hazardous location. Inputs are typically NAMUR sensors or dry contacts, although devices providing a variable resistance conforming to DIN 19234 may be used - e.g. variable resistors, thermistors, etc. Three programming switches on the front cover of each device enable selection of the output mode, and separate activation of wire-break and short-circuit monitoring. The switch labeled “A/R” selects the output mode. Positions “A” and “R” represent direct mode (N.O.) and inverse mode (N.C.), respectively. The output function is dependent on the input device. See the truth table opposite for detailed output function. The switches labeled “DB” and “K” activate wire-break and short-circuit monitoring of the input circuit, respectively. When these switches are set to ON and the corresponding fault in the input circuit occurs, the respective output is de-energized and the switching status LED illuminates red. If dry contacts are the input devices, resistors must be connected to the contacts or the “DB” and “K” switches must be set to OFF. See the Contact Configuration specification for correct resistor installation. A green LED indicates “Power ON” status. A 2-color LED indicates the switching status (yellow) as well as input circuit fault conditions (red). MK13-11Ex0-R/... (24VDC, 115VAC, 230VAC) These devices provide one SPDT relay output that follows the input signal. If wire-break and/or short-circuit monitoring of the input circuit are activated, the switching status LED will illuminate red and the output relay will de-energize upon detection of a fault.

MK13-11Ex0-R/24VDC MK13-11Ex0-R/115VAC MK13-11Ex0-R/230VAC MK13-12Ex0-R/24VDC MK13-12Ex0-R/115VAC MK13-12Ex0-R/230VAC MK13-121Ex0-R/24VDC MK13-121Ex0-R/115VAC MK13-121Ex0-R/230VAC

MK13-12Ex0-R/... (24VDC, 115VAC, 230VAC) These devices provide two SPDT relay outputs connected in parallel. Both outputs follow the input signal. If wire-break and/or short-circuit monitoring of the input circuit are activated, the switching status LED will illuminate red and both output relays will de-energize upon detection of a fault. MK13-121Ex0-R/... (24VDC, 115VAC, 230VAC) These devices provide two SPDT relay outputs, one follows the input signal and the other provides indication of faults in the input circuit when wire-break and/or short-circuit monitoring of the input circuit are activated. When a fault is detected, the switching status LED will illuminate red and the output and alarm relays will de-energize.

Connection Diagram

B15 3000 Campus Drive Minneapolis, MN 55441 Application Support: Fax: (763) 553-0708 www.turck.com ClearwaterTURCK TechInc. - Phone: 800.894.0412 - Fax: 208.368.0415 - Web:1-800-TURCK-IS www.clrwtr.com - Email: [email protected]

SPDT Relay Output Programmable Line Monitoring MK13-11Ex0-R/...(24VDC/115VAC/230VAC) MK13-12Ex0-R/...(24VDC/115VAC/230VAC) MK13-121Ex0-R/...(24VDC/115VAC/230VAC) MK13-11Ex0-R/*** M7541107 M7541102 M7541100

MK13-12Ex0-R/*** M7541117 M7541112 M7541110

MK13-121Ex0-R/*** M7541167 M7541162 M7541160

10-30 VDC, £10% ripple 98-126 VAC, 48-62 Hz 196-253 VAC, 48-62 Hz DC: £1 W AC: £40 mA between input, output and supply circuits, test voltage 2.5 kVrms

10-30 VDC, £10% ripple 98-126 VAC, 48-62 Hz 196-253 VAC, 48-62 Hz DC: £1.3 W AC: £40 mA between input, output and supply circuits, test voltage 2.5 kVrms

10-30 VDC, £10% ripple 98-126 VAC, 48-62 Hz 196-253 VAC, 48-62 Hz DC: £1.3 W AC: £40 mA between input, output and supply circuits, test voltage 2.5 kVrms

Input Circuits Nominal operating characteristics (per DIN 19234) - Voltage 8V - Current 8 mA - Switching threshold 1.55 mA

8V 8 mA 1.55 mA

8V 8 mA 1.55 mA

Intrinsic Safety Parameters

See page K10

See page K10

See page K10

Output Circuits Switching voltage per output Switching current per output Maximum load per output Contact Material Switching frequency

one SPDT relay 250 VAC / 120 VDC 2A 500 VA / 60 W AgCdO +3m Au £10 Hz

two SPDT relays 250 VAC / 120 VDC 2A 500 VA / 60 W AgCdO +3m Au £10 Hz

two SPDT relays 250 VAC / 120 VDC 2A 500 VA / 60 W AgCdO +3m Au £10 Hz

Housing Style

Diagram D (page A17)

Diagram D (page A17)

Diagram D (page A17)

Power Supply Supply voltage - 24VDC - 115VAC - 230VAC Power consumption Galvanic isolation

Switching Amplifiers

Type ID Number - 24VDC - 115VAC - 230VAC

Contact Configuration

Truth Table Output (DB and/or K on)

Input

Programming

(terminals 1-5) Output

Dry Contacts

Inductive NAMUR

Capacitive NAMUR

LED

1, (2)

R

On Energized

De-ener.

Energized On

De-ener.

De-ener.

On Energized

De-ener. Off

Ener.

Energized On

On Ener.

Off Energized

De-ener.

Ener.

Yellow De-energized

De-ener. On

De-energized On

De-ener.

LED

1

On De-ener.

Ener.

Output

Dry Contacts

(2/Alarm)

De-ener. Off

Ener.

R

Red (Alarm)

De-ener.

Normal

LED

1, (2)

Ener.

A

Output

Yellow (Alarm)

A

Input

Short or Wire-break

Normal

A/R Switch Position

Output (DB & K off)

Off Energized

TURCK Inc. 3000 Drive Minneapolis, MN 55441 Application Support: 1-800-TURCK-IS Fax: (763) 553-0708 www.turck.com B16 Clearwater TechCampus - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: [email protected]

TURCK Switching Amplifiers

These devices are single channel switching amplifiers with intrinsically safe input circuits. They are used to isolate and transfer discrete signals from a hazardous location to a non-hazardous location. Inputs are typically NAMUR sensors or dry contacts, although devices providing a variable resistance conforming to DIN 19234 may be used - e.g. variable resistors, thermistors, etc. The input circuit is monitored for short-circuit and wire-break. If a fault in the input circuit occurs, both outputs are de-energized and the green LED is switched off. When dry contacts are the input device, the input circuit monitoring function must be turned off by jumpering terminals 3-4, or resistors must be added to the switch as shown in Contact Configuration. A two-position switch on the front cover selects the output mode for each of the devices. Positions “A” and “R” represent direct mode (N.O.) and inverse mode (N.C.), respectively. The output mode is dependent on the input device. Refer to Truth Table. A yellow LED indicates switching status. The MK13-UPN-Ex0/24VDC provides two short-circuit protected transistor outputs, one PNP and one NPN. Both outputs are energized or de-energized simultaneously. MK13-UR-Ex0/24VDC, MK13-UR-Ex0/115VAC, MK13-UR-Ex0/230VAC: The MK13-UR-Ex0/... amplifiers each provide one SPST relay output.

MK13-UPN-Ex0/24VDC MK13-UR-Ex0/24VDC MK13-UR-Ex0/115VAC MK13-UR-Ex0/230VAC

Connection Diagram

B11 3000 Campus Drive Minneapolis, MN 55441 Application Support: Fax: (763) 553-0708 www.turck.com ClearwaterTURCK TechInc. - Phone: 800.894.0412 - Fax: 208.368.0415 - Web:1-800-TURCK-IS www.clrwtr.com - Email: [email protected]

Type ID Number

- 24VDC - 115VAC - 230VAC

Power Supply Supply voltage

- 24VDC - 115VAC - 230VAC - 24VDC - 115VAC - 230VAC

Current consumption

MK13-UPN-Ex0/24VDC M7505100

MK13-UR-Ex0/*** M7505300 M7505302 M7505303

10-30 VDC, £10% ripple

19-29 VDC, £10% ripple 98-126 VAC, 48-62 Hz 184-276 VAC, 48-62 Hz 20 mA 80 mA 40 mA between hazardous and non-hazardous circuits, test voltage 2.5 kVrms

20 mA 80 mA 40 mA between hazardous and non-hazardous circuits, test voltage 2.5 kVrms

Galvanic isolation

Input Circuits Nominal operating characteristics (per DIN 19234) - Voltage 8V - Current 8 mA - Switching threshold 1.55 mA

8V 8 mA 1.55 mA

Intrinsic Safety Parameters

See page K10

See page K10

Output Circuits Voltage drop Contact material Switching frequency Switching current, each output Switching voltage Maximum load

one PNP & one NPN transistor output £2.5 V na £3 kHz 100 mA, short-circuit protected na na

one SPST relay output na AgNi 0.15 + 3m Au £10 Hz £2 A 250 VAC / 120 VDC 500 VA / 120 W

Housing Style

Diagram A (page A17)

Diagram A (page A17)

Switching Amplifiers

Transistor or Relay Output Programmable Line Monitoring MK13-UPN-Ex0/24VDC MK13-UR-Ex0/...(24VDC/115VAC/230VAC)

Contact Configuration

Truth Table Input (Terminal 1-2)

Programming

Output

Output

(terminals 3-4 open)

(term. 3-4 jumpered)

Normal LED

A/R Switch Position

Dry Contacts

Inductive NAMUR

Capacitive NAMUR

Output

Yellow

Output

R

On On

Off

Off

On

Off Off

On

On

Off Off

Off

On On

Off

On

R

On

Off

On On

Off Off

Off On

Yellow Green

Off

On On

Output

Off Off

On

A

Yellow

LED

Dry Contacts

Green

Off Off

Normal

LED

Green

A

Input

Short or Wire-Break

Off Off

Off

On

Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: [email protected]

TURCK Switching Amplifiers

These devices are two-channel switching amplifiers with intrinsically safe input circuits. They are used to isolate and transfer discrete signals from a hazardous location to a no-hazardous location. Inputs are typically NAMUR sensors or dry contacts, although devices providing a variable resistance conforming to DIN 19234 may be used – e.g. variable resistors, thermistors, etc. Each device provides one SPST relay output per channel. When the output is energized the switching status LED illuminates yellow. Three programming switches, located on the front cover of each device enable selection of the output mode, as well as contact multiplication. The switches labeled NO/NC select the output mode for each channel. NO represents direct mode and NC represents inverse mode. The output function is dependent on the input device. See truth table for detailed output function. The switch labeled 1:1 and 1:2 enables the switching status of ch.1 to be transferred to ch. 2 as well. A green LED indicated “Power On” status

MK1-22Ex0-R/24VDC MK1-22Ex0-R/115VAC MK1-22Ex0-R/230VAC

Connection Diagram

B7ClearwaterTURCK 3000 Campus Drive Minneapolis, MN 55441 Application Support: Fax: (763) 553-0708 www.turck.com TechInc. - Phone: 800.894.0412 - Fax: 208.368.0415 - Web:1-800-TURCK-IS www.clrwtr.com - Email: [email protected]

Type ID Number

MK1-22Ex0-R/24VDC M7505631

MK1-22Ex0-R/115VAC M7505632

MK1-22Ex0-R/230VAC M7505630

10...30 VDC £10% £1.5 W between input and output circuits supply voltage for 250 Vrms test voltage 2.5 kVrms

98...126 VAC 48...62 Hz £30 mA rms between input and output circuits supply voltage for 250 Vrms test voltage 2.5 kVrms

196...253 VAC 48...62 Hz £30 mA rms between input and output ciruits supply voltage for 250 Vrms test voltage 2.5 kVrms

according to EN 50227 (NAMUR) intrinsically safe according to EN 50020

according to EN 50227 (NAMUR) intrinsically safe according to EN 50020

according to EN 50227 (NAMUR) intrinsically safe according to EN 50020

8V 8 mA 1.55 mA typ. 0.2 mA

8V 8 mA 1.55 mA typ. 0.2 mA

8V 8 mA 1.55 mA typ. 0.2 mA

2 relay outputs with 1 NO contact each £250 VAC /120 VDC £2 A £500 VA / 60 W £10 Hz silver-alloy + 3 mm Au

2 relay outputs with 1 NO contact each £250 VAC /120 VDC £2 A £500 VA / 60 W £10 Hz silver-alloy + 3 mm Au

2 relay outputs with 1 NO contact each £250 VAC /120 VDC £2 A £500 VA / 60 W £10 Hz silver-alloy + 3 mm Au

LED Indications - Status indication/fault indication 2 x yellow/red - Power "ON" green

2x yellow/red green

2 x yellow/red green

Housing Style

Diagram H (page A17)

Diagram H (page A17)

Power Supply Supply voltage Ub Line frequency/ripple Wpp Current consumption Galvanic isolation

Input Circuits

Operating characteristics - Voltage - Current Switching threshold Hysteresis Output Circuits Switching voltage Switching current per output Switching capacity per output Switching frequency Contact material

Diagram H (page A17)

Truth Table Programming

N.O./N.C. Switch Position

Input (Terminal 1-4, 2-5) Dry Contacts

Inductive NAMUR

Capacitive NAMUR

Output

Ch.1 Term. 5 LED Ch.2 Term. 6 Yellow

N.O.

De-energized

Off

N.O.

Energized

On

N.C.

Energized

On

N.C.

De-energized

Off

Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: [email protected]

Switching Amplifiers

Isolating Switching Amplifier MK1-22Ex0-R 1 channels

TURCK Switching Amplifiers

The MK1-22UN-Ex0/24VDC, MK1-22UP-Ex0/24VDC, MK13-22UN-Ex0/24VDC, and MK13-22UP-Ex0/24VDC are dual-channel switching amplifiers with intrinsically safe input circuits. They are used to isolate and transfer discrete signals from a hazardous location to a non-hazardous location. Inputs are typically NAMUR sensors or dry contacts, although devices providing a variable resistance conforming to DIN 19234 may be used - e.g. variable resistors, thermistors, etc. Each of the switching amplifiers provides one short-circuit protected transistor output for each channel. There are PNP output versions and NPN output versions: PNP NPN

- MK1-22UP-Ex0/24VDC, MK13-22UP-Ex0/24VDC - MK1-22UN-Ex0/24VDC, MK13-22UN-Ex0/24VDC

A two-position switch on the front cover selects the output mode for each of the devices. Positions “A” and “R” represent direct mode (N.O.) and inverse mode (N.C.), respectively. The output mode is dependent on the input device. Refer to Truth Table. The input circuits of the MK 13-22UN-Ex0/24VDC and MK13-22UP-Ex0/24VDC are monitored for short-circuit and wire-break. If a fault in the input circuit occurs, the respective output is de-energized and the switching status LED illuminates red. The input circuit monitoring cannot be disabled. If dry contacts are the input devices, resistors must be connected to the contacts. See Contact Configuration specification for correct resistor installation.

MK1-22UN-Ex0/24VDC MK1-22UP-Ex0/24VDC MK13-22UN-Ex0/24VDC MK13-22UP-Ex0/24VDC

MK1-22UN-Ex0/24VDC and MK1-22UP-Ex0/24VDC do not monitor the input circuit for short-circuit and wire-break. They are thus ideal for use with dry contacts, as it is not necessary to connect additional resistors. A green LED indicates “Power ON” status.

Connection Diagram

B5ClearwaterTURCK 3000 Campus Drive Minneapolis, MN 55441 Application Support: Fax: (763) 553-0708 www.turck.com TechInc. - Phone: 800.894.0412 - Fax: 208.368.0415 - Web:1-800-TURCK-IS www.clrwtr.com - Email: [email protected]

2 Channel Transistor Output MK1-22UN-Ex0/24VDC MK1-22UP-Ex0/24VDC MK13-22UN-Ex0/24VDC MK13-22UP-Ex0/24VDC

Power Supply Supply voltage Current consumption Galvanic isolation

MK...-22UN-Ex0/24VDC

MK...-22UP-Ex0/24VDC

M7505602 M7505612

M7505604 M7505614

19-29 VDC, £10% ripple approx. 50 mA between hazardous and non-hazardous circuits, test voltage 2.5 kVrms

19-29 VDC, £10% ripple approx. 50 mA between hazardous and non-hazardous circuits, test voltage 2.5 kVrms

Switching Amplifiers

Type ID Number - MK1 - MK13

Input Circuits Nominal operating characteristics (per DIN 19234) - Voltage 8V - Current 8 mA Switching threshold 1.55 mA

8V 8 mA 1.55 mA

Intrinsic Safety Parameters

See page K10

See page K10

one NPN transistor output per channel £2.5 V

one PNP transistor output per channel £2.5 V

50 mA maximum 100 mA maximum £3 kHz

50 mA maximum 100 mA maximum £3 kHz

Diagram A (page A17)

Diagram A (page A17)

Contact Configuration

Output Circuits Voltage drop Switching current per output - MK1 - MK13 Switching frequency Housing Style

Truth Table

A/R Switch Position

MK13

Input- (Ch.1 Terminals 1-3)

Programming

Output

(Ch.2 Terminals 2-4)

Dry Contacts

Dry Contacts

(MK13)

(MK1)

Inductive NAMUR

Capacitive NAMUR

Short or Wire-break

Ch.1 Term. 5 Ch.2 Term. 6

Yellow LED

Ch.1 Ch.2

Red LED

A

Off

Off

Off

On

A

On

On

Off

On

R

On

On

Off

On

R

Off

Off

Off

On

Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: [email protected]

TURCK Switching Amplifiers

The MK1-2RP/24VDC and MK1-2AP/24VDC are dual channel switching amplifiers with input circuits according to DIN 19x234. They can be used with sensors conforming to DIN 19x234 (NAMUR) or mechanical contacts. The couplers provide one PNP, short-circuit protected transistor output per channel. The input circuits are not self-monitored. The MK1-2AP/24VDC provides two normally open outputs. The MK1-2RP/24VDC provides two normally closed outputs.

MK1-2AP/24VDC MK1-2RP/24VDC

Connection Diagram

B3ClearwaterTURCK 3000 Campus Drive Minneapolis, MN 55441 Application Support: Fax: (763) 553-0708 www.turck.com TechInc. - Phone: 800.894.0412 - Fax: 208.368.0415 - Web:1-800-TURCK-IS www.clrwtr.com - Email: [email protected]

Type ID Number

MK1-2AP/24VDC M7505500

MK1-2RP/24VDC M7505501

Power Supply Supply voltage Current consumption

19-29 VDC, 10% ripple 20 mA

19-29 VDC, 10% ripple 20 mA

Input Circuit Operating characteristics - Voltage - Current Switching threshold Hysteresis

DIN 19 234 (NAMUR)

DIN 19 234 (NAMUR)

8V 5 mA 1.55 mA 0.2 mA

8V 5 mA 1.55 mA 0.2 mA

Output Circuit Voltage drop Switching current for each output Switching frequency

two PNP transistor outputs 2.5 V 100 mA, short-circuit protected 1 kHz

two PNP transistor outputs 2.5 V 100 mA, short-circuit protected 1 kHz

LED Indications - Output energized

yellow (2)

yellow (2)

Housing Style

Diagram A ( page A17)

Diagram A (page A17)

Truth Table MK1-2RP Input Dry Contacts

Inductive NAMUR

Output Capacitive NAMUR

Channel

LED

1

Yellow

2

Yellow

On

On

On

On

Off

Off

Off

Off

Truth Table MK1-2AP Input Dry Contacts

Inductive NAMUR

Output Capacitive NAMUR

Channel

LED

1

Yellow

2

Yellow

Off

Off

Off

Off

On

On

On

On

Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: [email protected]

Switching Amplifiers

Switching Amplifier MK1-2AP/24VDC MK1-2RP/24VDC 2 Channel

TURCK Switching Amplifiers

These devices are two-channel switching amplifiers with intrinsically safe input circuits. They are used to isolate and transfer discrete signals from a hazardous location to a non-hazardous location. Inputs are typically NAMUR sensors or dry contacts, although devices providing a variable resistance conforming to DIN 19234 may be used - e.g. variable resistors, thermistors, etc. Each device provides one potential-free transistor output per channel. When the output is energized, the 2-color switching status LED illuminates yellow. Six programming switches, three per channel, located on the front cover of each device enable selection of the output mode, as well as separate activation of wire-break and short-circuit monitoring. The switches labeled “A/R” select the output mode for each channel. Positions “A” and “R” represent direct mode (N.O.) and inverse mode (N.C.), respectively. The output function is dependent on the input device. See the truth table opposite for detailed output function. The switches labeled “DB” and “K” activate wire-break and short-circuit monitoring of the input circuit, respectively. When these switches are set to ON and the corresponding fault in the input circuit occurs, the respective output is de-energized and the 2-color switching status LED illuminates red. If dry contacts are the input devices, resistors must be connected to the contacts or the “DB” and “K” switches must be set to OFF. See the Contact Configuration specification for correct resistor installation. A green LED indicates “Power ON” status.

MK13-22Ex0-T/24VDC MK13-22Ex0-T/115VAC MK13-22Ex0-T/230VAC

Connection Diagram

B23 3000 Campus Drive Minneapolis, MN 55441 Application Support: Fax: (763) 553-0708 www.turck.com ClearwaterTURCK TechInc. - Phone: 800.894.0412 - Fax: 208.368.0415 - Web:1-800-TURCK-IS www.clrwtr.com - Email: [email protected]

Type ID Number

MK13-22Ex0-T/24VDC M7542127

MK13-22Ex0-T/115VAC M7542122

MK13-22Ex0-T/230VAC M7542120

10-30 VDC, £10% ripple £1.2 W between input, output and supply circuits, test voltage 2.5 kVrms

98-126 VAC, 48-62 Hz £50 mA between input, output and supply circuits, test voltage 2.5 kVrms

196-253 VAC, 48-62 Hz £30 mA between input, output and supply circuits, test voltage 2.5 kVrms

Input Circuits Nominal operating characteristics (per DIN 19234) - Voltage 8V - Current 8 mA - Switching threshold 1.55 mA

8V 8 mA 1.55 mA

8V 8 mA 1.55 mA

Intrinsic Safety Parameters

See page K10

See page K10

See page K10

Switching voltage Switching current per channel Switching frequency Voltage drop

one potential-free transistor per channel, short-circuit protected £30 V £50 mA £3 kHz £2.5 V

one potential-free transistor per channel, short-circuit protected £30 V £50 mA £3 kHz £2.5 V

one potential-free transistor per channel, short-circuit protected £30 V £50 mA £3 kHz £2.5 V

LED Indications Power “On” Output energized Fault indication

green yellow red

green yellow red

green yellow red

Housing Style

Diagram C (page A17)

Diagram C (page A17)

Diagram C (page A17)

Power Supply Supply voltage Power consumption Galvanic isolation

Contact Configuration

Output Circuits

Truth Table Output (DB and/or K on)

Input

Programming

(terminals 1-4, 2-5)

A/R Switch Position

Dry Contacts

Inductive NAMUR

Capacitive NAMUR

Input

Short or Wire-break

Normal Chan.1 Chan.2

LED Yellow

Chan.1 Chan.2

LED Red

A

Off

Off

Off

A

On

On

R

On

R

Off

Output (DB & K off) Normal

Dry Contacts

Chan.1 Chan.2

LED Yellow

On

Off

Off

Off

On

On

On

On

Off

On

On

On

Off

Off

On

Off

Off

Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: [email protected]

Switching Amplifiers

Two-Channel Potential-Free Transistor Output Programmable Line Monitoring MK13-22Ex0-T/...(24VDC/115VAC/230VAC)

Power Switching status Closed circuit/ open circuit output mode selection Static or dynamic mode

7

8

5

6

Isolating Switching Amplifier MK15-12Ex0-PN/24VDC 1-channel

Pwr 1 NC stat 1:1

NO dyn

MK15-12Ex0-PN 24VDC

Pulse stretching

1

[EEx ia/ib] IIC/IIB

• 1-channel isolating switching amplifier • Intrinsically safe input circuits EEx ia/ib • Area of application according to ATEX: II (1/2) GD • Galvanic isolation between input circuit, output circuit and supply voltage • Static and dynamic pulse processing • Switching frequency up to 5 kHz • Two transistor outputs, 1 npn and 1 pnp short-circuit protected • Selectable NO/NC output function

3

4

1

2

The MK15-12Ex0-PN/... is a single channel type special switching amplifier, particularly suited for transfer of high pulse frequencies (e. g. when used in scanning turbine rotation). They can be connected to sensors according to EN 60947-5-6 (NAMUR), variable resistors or potential-free contacts. The device is equipped with one shortcircuit protected pnp transistor output and one short-circuit protected npn output transistor. Three front panel programming switches set the channel function (normally open mode (NO) and normally closed (NC) mode), pulse expansion and the selection of pulse processing for the input signal (static or dynamic).

–3

If pulse expansion is active, the output pulse is extended by 10 ms. With static pulse processing, the NAMUR switching thresholds are scanned in a range of 0...5 kHz. Dynamic pulse processing is to be used with sine and square wave input signals whose absolute value switching thresholds do not correspond to the NAMUR standard. A signal deviation (current change) of approx. 0.5 mA in an operating range of 1.5...3.5 mA switches the output. The green LED on the front cover indicates that the devices are powered. The yellow LED indicates the switching status of the output (LED on – transistor conducting).

pnp

5

1

npn

6

2

100 mA ö +1

YE

GN

7

+

8

Power –

Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: [email protected]

Isolating Switching Amplifier MK15-12Ex0-PN

Type Ident-No.

MK15-12Ex0-PN/24VDC 7541316

Supply voltage U B Line frequency/ripple WPP Power/current consumption Galvanic isolation

10...30 VDC ≤ 10 % approx. 20 mA between input circuit, output circuit and supply voltage for 250 Vrms, test voltage 2.5 kVrms

Input circuits Operating characteristics – Voltage – Current Switching threshold (static) Hysteresis (static)

according to EN 60947-5-6 (NAMUR), intrinsically safe according to EN 50020 8.2 V 8.2 mA 1.55 mA 0.2 mA (typ.)

Output circuits Voltage drop output ( 5 ) Voltage drop output ( 6 ) Switching current output ( 5 ) Switching current output ( 6 ) Switching frequency

Two transistor outputs ≤ 2.5 V ≤ 2.5 V ≤ 100 mA, short-circuit protected, pnp ≤ 100 mA, short-circuit protected, npn ≤ 5 kHz

Ex-approval acc. to certificate of conformity Maximum nominal values – No load voltage U0 – Short-circuit current I0 – Power P0 – Internal resistance Ri Characteristic Max. external inductances/capacitances L0/C 0 – [EEx ia] IIC – [EEx ia] IIB Internal inductance Li Ambient temperature Tu Marking of device

TÜV 03 ATEX 2121

0.9 mH/710 nF / 1.9 mH/620 nF / 4.9 mH/530 nF 4.9 mH/2,7 µF 120 µH -25...+70 °C II (1/2) GD [EEx ia/ib] IIC/IIB

LED indications – Switching status – Power

yellow green

Housing Mounting Connection Connection profile Degree of protection (IEC 60529/EN 60529) Operating temperature

11.3 V 14 mA 39 mW 823 Ω linear

8-pole, 18 mm wide, Polycarbonate/ABS, flammability class V-0 per UL 94 snap-on clamps for top-hat rail (DIN 50022) or screw terminals for panel mounting via flat terminals with self-lifting pressure plates ≤ 2 x 2.5 mm2 or 2 x 1.5 mm2 with wire sleeves IP20 -25…+60 °C

89

70 18