RASTHRIYA PROJECT 06484 PROJECT No.: SAFETY AND FIRE FIGHTING SYSTEM (UNIT 00) PROCESS DATA SHEET FIRE FIGHTING TANK
Views 126 Downloads 3 File size 773KB
RASTHRIYA PROJECT 06484
PROJECT No.:
SAFETY AND FIRE FIGHTING SYSTEM (UNIT 00)
PROCESS DATA SHEET FIRE FIGHTING TANK 00-FB-301
00
22/11/2013
ISSUE FOR PROPOSAL
ABG
JLS
JRF
Rev. No:
DATE
DESCRIPTION
PREPARED BY
CHECKED BY
APPROVED BY
DOCUMENT TITLE PROCESS CONDENSATE TANK DATA SHEET DOCUMENT NUMBER
06484-00-120-DS-0003
REVISION PAGE
1
OF
3
00
This document contains confidential information property of TECNICAS REUNIDAS/ESPINDESA, any reproduction or use of its content, total or partial, including without limitation any of its characteristics patented or able to be patented, it is forbidden and it cannot be reproduced or used without the permission of TECNICAS REUNIDAS and ESPINDESA.
STORAGE TANK PROCESS DATA SHEET Rev.
00
Date
22/11/2013
JOB Nº
06484
UNIT
SAFETY AND FIRE FIGHTING SYSTEM (00) RCF-GAIL-CIL-FCIL
ABG
CLIENT
Checked
JLS
LOCATION TALCHER COMPLEX, ODISHA (INDIA)
Approved
JRF
1
Item Nº:
00-FB-301
2
Service:
FIRE FIGHTING TANK
3
Fluid:
SERVICE WATER (Note 1)
4
Nominal capacity:
1357
m3
5
Net Capacity:
1101
m3
6
Diameter (ID)
12000
mm
7
Height
12000
mm
8 9
TANK PRESSURE
Quantity:
06484-00-120-DS-0003 2 OF 3
2
ATM.
kg/cm g
Design
0,03
kg/cm2 g
-0,005
kg/cm2 g
Vacuum design
11
Operating
TANK TEMPERATURE
1
Operating
10
12
DOC Nº PAGE REV
REV
Prepared
AMB
Design
ºC
80
ºC kg/cm2 g
13
Operating Press.
14
Operating Temp.
ºC
15
Design Press.
kg/cm2 g
COIL
16
Design Temp.
ºC
17
Nom. Diameter
in
18
Length
m
MATERIAL
19 20
Shell / Roof
21
Cladding
22
Coil
CORR. ALLOW.
CS
1,5
mm
Nota 6
-
mm
-
-
mm
23 24
Type
25 26
X Conical Roof
Floating Roof
X API
Refrigerated
Bottom
27 28
Steam out Conditions:
ºC
-
kg /cm2 g
Short term maximum temperature:
-
ºC
-
kg /cm2 g
Flat
Short term minimun temperature:
-
ºC
-
kg /cm g
Conical Pointing Downwards
TANK VENTING DATA:
Conical Pointing Upwards
- Blanketing:
29
Code:
API STD.650
30
Stress Relieve for Process Reasons:
31
Insulation:
-
Type
Not Insulated
Thickness
32
-
mm
NO
- Max inbreathing rate (Note 4):
kg/h
- Max outbreathing rate (Note 4):
kg/h
- Emergency relief:
Flow (Note 4):
- Relieving conditions:
Temperature:
NOZZLES
33
2
kg/h
/MW:
ºC /Pressure:
kg/kmol kg/cm2 g
NOZZLES
34
Nº
Quantity
Size
Service
Type
Nº
Quantity
Size
Service
Type
35
N1
1
4"
INLET
RF
M1
1
24"
MAN HOLE IN SHELL
API 650
M2
1
24"
MAN HOLE IN ROOF
API 650
36
N2
1
12"
OUTLET
RF
37
N3
1
6"
OVERFLOW
RF
38
N4
1
4"
DRAIN (Note 7)
RF
39
N5
1
12"
VENT (Note 2,3,4)
BW
40
N6
1
8"(Note 8)
LEVEL GAUGE
RF
41
N7
1
8"(Note 8)
LEVEL TRANSMITTER
RF
42
N8
1
2"(Note 8)
TEMP. GAUGE
RF
43
N9
1
8"(Note 9)
FIRE PUMP TESTING HEADER
RF
44 45 46 47 48 49 50
See general notes on next page.
STORAGE TANK PROCESS DATA SHEET Rev.
00
Date
22/11/2013
JOB Nº
06484
UNIT
SAFETY AND FIRE FIGHTING SYSTEM (00)
ABG
CLIENT
RCF-GAIL-CIL-FCIL
Checked
JLS
LOCATION
TALCHER COMPLEX, ODISHA (INDIA)
Approved
JRF
DOC Nº
06484-00-120-DS-0003
PAGE
3 OF 3
REV
Prepared
1
GENERAL NOTES FOR TANK:
00-FB-301
2 3
1. Liquid SG = 0,995 @ 32ºC
4
2. Swan neck and bird screen to be fitted. No other elements which may obstruct the flow area allowed.
5
3. To be confirmed by vendor
6
4. Maximum filling rate: 50 m3/h
7
Maximum pumpout rate: 318 m3/h
Tank Vendor to confirm vent size for 1,5 times indicated filling/pump out rates according API 2000. The open drain flow shall be considered.
8
5.- Drawoff Swamp.
9
6.- Full Epoxy Lining is required
10
7.- Tank should be 100% drainable.
11
8.- To be Confirmed by Instrument Deparment
12
9.- To be confirmed with final fire pumps
13
10.- Fire water capacity to be confirmed during detail desgin, after risk asessment.
14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50
RASHTRIYA PROJECT 06484
PROJECT No.:
NITRIC ACID PLANT, 01
TANK PROCESS DATA SHEET START-UP TANK 01-FB-001
00
22/11/2013
ISSUE FOR PROPOSAL
FJ
JLS
JR
Rev. No:
DATE
DESCRIPTION
PREPARED BY
CHECKED BY
APPROVED BY
DOCUMENT TITLE START-UP TANK DATA SHEET DOCUMENT NUMBER
06484-01-120-DS-0023
REVISION PAGE
1
OF
3
00
This document contains confidential information property of TECNICAS REUNIDAS/ESPINDESA, any reproduction or use of its content, total or partial, including without limitation any of its characteristics patented or able to be patented, it is forbidden and it cannot be reproduced or used without the permission of TECNICAS REUNIDAS and ESPINDESA.
STORAGE TANK PROCESS DATA SHEET Rev.
00
Date
22/11/2013
Prepared
FJ
JOB Nº
06484
UNIT
Nitric Acid Plant (unit 01)
CLIENT
RDF-GAIL-CIL-FCIL
LOCATION
Talcher Complex, Odisha (India)
JRF
DOC. Nº
06484-01-120-DS-0023
PAGE
2/3
REV
JLS
Approved
REV
Checked
1
Item Nº:
2
Service:
3
Fluid:
4
Nominal capacity:
5
Net Capacity:
Quantity:
01-FB-001
NITRIC ACID 60% (Note 1) m3
198
m3
6
Diameter (ID)
6000
mm
7
Height
7000
mm
Operating
8 9
1
START-UP TANK
TANK PRESSURE
Design
Atm.
bar g
0.1
bar g
10
Vacuum design
-0.02
bar g
11
Operating
≤ 50
ºC
Design
80
12
TANK TEMPERATURE
ºC
13
Operating Press.
14
Operating Temp.
-
ºC
15
Design Press.
-
bar g
16
Design Temp.
-
ºC
17
Nom. Diameter
-
in
18
Length
-
m
bar g
COIL
MATERIAL
19 20
-
Shell
CORR. ALLOW.
AISI 304L
-
mm
21
Cladding
-
-
mm
22
Roof
-
-
mm
23 24
Type
25
X Conical Roof
Floating Roof
Steam out Conditions:
-
ºC
-
kPa g
X API
Refrigerated
Short term maximum temperature:
-
ºC
-
kPa g
-
ºC
-
kPa g
26
Bottom
Flat
Short term minimun temperature:
27
NOTE (2)
Conical Pointing Downwards
TANK VENTING DATA:
Conical Pointing Upwards
- Blanketing:
28 29
Code:
30
Stress Relieve for Process Reasons:
API STD.650
31
Insulation:
Type
Not Insulated
Thickness
32
-
-
NO
- Max inbreathing rate :
kg/h
- Max outbreathing rate :
kg/h
- Emergency relief: mm
kg/h
Flow :
- Relieving conditions: Temperature:
NOZZLES
33
/MW:
ºC /Pressure:
kg/kmol kPa g
NOZZLES
34
Nº
Quantity
Size
Service
TYPE
Nº
Quantity
Size
Service
TYPE
35
N1
1
4''
ACID INLET DA-002
RF
N11
1
2"
DEMI WATER
RF
1
2''
ACID INLET FROM FA-002
RF
N12
1
2"
SEAL DRAIN
RF
36
N2
37
N3
1
4''
RECIRCULATION
RF
N13
1
4"
SPARE
RF
38
N4
1
2''
DRAIN
RF
N14
1
2"
NITRIC ACID TO GA-016
RF
39
N5
1
4''
LEVEL
RF
M1
1
24"
MAN HOLE in Roof
RF
40
N6
1
2''
GA-011 RETURN
RF
M2
1
24"
MAN HOLE in Sheel
RF
41
N7
1
6''
ACID OUTLET
RF
42
N8
1
2''
T INSTRUMENT
RF
43
N9
1
10"
VENT
RF
N10
1
6"
OVERFLOW
RF
44 45 46
See general notes on next page.
STORAGE TANK PROCESS DATA SHEET Rev.
00
Date
22/11/2013
JOB Nº
06484
UNIT
Nitric Acid Plant (unit 01)
CLIENT
RDF-GAIL-CIL-FCIL
FJ
Checked
JLS
LOCATION Talcher Complex, Odisha (India)
Approved
JRF
DOC. Nº
06484-01-120-DS-0023
PAGE
3/3
REV
Prepared
1
GENERAL NOTES FOR TANK:
01-FB-001
2 3
1. Liquid SG = 1.38 @ 10ºC
4
2. Tank bottom with 0.5% slope to N4
5
3. Stainless steel bolt and nuts
6
4. The equipment 01-FA-008 is supported over the vent nozzle
7
5. Level connections sizes to be confirmed by instrument department
8
6, N1, N2, N3 with dip pipe and shyphon breaker
9
7, Wear plate at bottom, and dip pipes in inlet N1, N2, N3, N6
10
8. Equipment 01-FA-007 will be located above nozzle n9
11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44
RASTHRIYA PROJECT 06484
PROJECT No.:
AMMONIUM NITRATE SOLUTION STORAGE (UNIT 05)
VESSEL PROCESS DATA SHEET AN SOLUTION TANKS 05-FB-101 A/B
00
22/11/2013
ISSUE FOR PROPOSAL
MSP
JLS
JRF
Rev. No:
DATE
DESCRIPTION
PREPARED BY
CHECKED BY
APPROVED BY
DOCUMENT TITLE AN SOLUTION TANKS PROCESS DATA SHEET DOCUMENT NUMBER
06484-05-120-DS-0001
REVISION PAGE
1
OF
3
00
This document contains confidential information property of TECNICAS REUNIDAS/ESPINDESA, any reproduction or use of its content, total or partial, including without limitation any of its characteristics patented or able to be patented, it is forbidden and it cannot be reproduced or used without the permission of TECNICAS REUNIDAS and ESPINDESA.
STORAGE TANK PROCESS DATA SHEET Rev.
00
Date
22/11/2013
JOB Nº
06484
UNIT
AMMONIUM NITRATE SOLUTION STORAGE (05)
MSP
CLIENT
RCF-GAIL-CIL-FCIL
Checked
JLS
LOCATION
TALCHER COMPLEX, ODISHA (INDIA)
Approved
JRF
DOC Nº
06484-05-120-DS-0001
PAGE
2 OF 3
REV
Prepared
1
Item Nº:
05-FB-101 A/B
2
Service:
AMMONIUM NITRATE SOLUTION STORAGE TANK
3
Fluid:
4
Nominal capacity:
5
Net Capacity:
6
Diameter (ID)
7
Height
12
1220 (2)
m3
12000
mm
10800
mm
m
3
Operating
kg/cm2 g
Atm.
+0,1 / -0,02 kg/cm2 g
Design
TANK PRESSURE
2
Vacuum design
10 11
2
AMMONIUM NITRATE SOLUTION (96 %) (1)
8 9
Quantity:
TANK TEMPERATURE
kg/cm g
Operating
140
ºC
Design
180
ºC 2
13
Operating Press.
5.1
kg/cm g
14
Operating Temp.
152
ºC
Design Press.
9/FV
kg/cm2 g
Design Temp.
200
ºC
15
COIL
16 17
Nom. Diameter
(Notes 4,5) 6 mm
18
Length
(Notes 4,5) 6 mm
19 20
Shell / Roof
21
Cladding
22
Coil / Internals
MATERIAL
CORR. ALLOW.
AISI 304L
0
mm
-
-
mm
AISI 304L
0
mm REV
23 24
Type
25 26
Bottom
27 28
X Conical Roof
Floating Roof
Steam out Conditions:
-
ºC
-
kg/cm2 g
X API
Refrigerated
Short term maximum temperature:
-
ºC
-
kg/cm2 g
Flat
Short term minimun temperature:
-
ºC
-
kg/cm2 g
Conical Pointing Downwards
TANK VENTING DATA:
Conical Pointing Upwards
- Blanketing:
29
Code:
30
Stress Relieve for Process Reasons:
31
Insulation:
32
API STD.650 -
Type
Heat conservation
Thickness
100
mm
(19)
NO
- Max inbreathing rate :
(8)
kg/h
- Max outbreathing rate :
(8)
kg/h
- Emergency relief:
Flow :
- Relieving conditions:
Temperature:
-
NOZZLES
33 34
Nº
Quantity
Size
35
N1
1
6"
36
N2
1
37
N3
38
kg/h MW: -
ºC
Pressure:
-
kg/kmol
-
kg/cm2 g
NOZZLES Type
Nº
Quantity
Size
AN SOLUTION INLET (9) (14)
RF
N12
1
2"
BOTTOM COIL STEAM INLET
RF
2"
AMMONIA GAS (9) (18)
RF
N13 A/B
2
4"
KICKBACK LINES FROM PUMPS (9)
RF
1
2"
PROCESS CONDENSATE (9)
RF
N14
1
2"
BOTTOM COIL CONDENSATE OUTLET
RF
N4
1
4"
DRAIN (13)
RF
N15
1
2"
SHELL COIL STEAM INLET
RF
39
N5 A/B
2
6"
LEVEL (7)
RF
N16
1
2"
SHELL COIL CONDENSATE OUTLET
40
N6
1
2"
ANSOL SAMPLE RETURN (9)
RF
M1
1
24"
MANHOLE IN SHELL
API 650
41
N7
1
8"
AN SOLUTION OUTLET (14)
RF
M2
1
24"
MANHOLE IN ROOF
API 650
42
N8 A/B/C/D
4
2"
TEMPERATURE (3)
RF
43
N9
1
12"
VENT (8)
RF
44
N10
1
6"
OVERFLOW
RF
45 46 47 48 49 50
See general notes on next page
Service
Service
Type
RF
STORAGE TANK PROCESS DATA SHEET Rev.
00
Date
22/11/2013
JOB Nº
06484
UNIT
AMMONIUM NITRATE SOLUTION STORAGE (05)
MSP
CLIENT
RCF-GAIL-CIL-FCIL
Checked
JLS
LOCATION
TALCHER COMPLEX, ODISHA (INDIA)
Approved
JRF
DOC Nº
06484-05-120-DS-0001
PAGE
3 OF 3
REV
Prepared
1
GENERAL NOTES FOR TANK: 05-FB-101 A/B
2 3
3
1. Liquid density at 140ºC = 1423,6 kg/m .
4
2. Total tank volume (approx) between top TL and bottom TL. Working volume: 1074 m3 (volume between HLL and LLL).
5
3. At different height. Two of them below LLL.
6
4. Bottom coil:
7
- Comprised of two independent coils with independent steam inlet and condensate outlet.
8
- The lenght of each coil will be minimum 50 m, the size 2".
9
- Both pipe coils will be placed at the bottom of tank with a proper support arrangement to be developed by vendor.
10
- Each coil will cover the complete surface of bottom.
11
- A clearance of minimum 300 mm from the floor shell shall be maintained while arranging the two pipes.
12
5. Shell coil:
13
- Two helicoidal coils of 40 mm diameter will be installed inside the tank to heat along shell from LLL to HHLL.
14
- Adequate arrangements shall be made to support helicoidal coils about 300 mm from shell inside.
15 16
- The minimum lenght shall be 70 m for each coil. 6. Stainless steel bolt and nuts.
17
7. Level connections sizes to be confirmed by Instrument department.
18
8. Maximum filling rate: 33 m3/h. Maximum pumpout rate: 90 m3/h. Preliminary vent size. Tank vendor to confirm vent size 1,5 times the indicated filling / pumpout rates
19
according to API 2000. Vent to be insulated to retain heat to prevent blockage due to crystallization.
20
9. Line with dip pipe and syphon breaker. Syphon breaker above HHLL.
21
10. Copper, tin, zinc and their alloys are not allowed in tank manufacturing.
22
11. Environmental conditions:
- Minimum air temperature: 12 ºC (dry bulb). - Maximum wind speed: As per IS 875 Part 3
23 24
12. 4" nozzle to be used for dip pipe calibration of level instruments
25
13. Drain to be from the bottom of the tank and at the lowest end to ensure full drainage of the tank.
26
14. Nozzle N1 and nozzle N7 to be on opposite ends.
27
15. Mixing eductors to be close to tank floor ( to pump suction nozzle N7, on the same elevation) and supported off the floor of the tank. Eductors to be pointed tangential to
28
the tank wall angled upward at 15º to horizontal. Provide mechanical reinforcement to handle nozzle vibration. Mixing eductors to be supplied by vendor on kickback lines
29
as indicated. Tank design and eductors location shall ensure that there are no stagnant areas that can accumulate contaminants or pockets where ammonium nitrate
30
can be confined within the equipment or structural items within the tank.
31
16. It is considered a small sump at bottom for pump suction nozzle N7.
32
17. Approximated dimmensions.
33
18. Ammonia sparger: 2" diameter of downcomer, 40 m pipe in circular shape of 4000 mm diameter with 3 mm diameter holes separated 50 mm each other along an axis.
34
Sparger 350 mm below minimum level. Locate ammonia sparger near mixing eductor suction nozzle to provide an adequate ammonia mixing.
35
19. Insulation also on roof.
36
20. Both tank floor as well as sump must be isolated.
37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52
AMMONIA INJECTION DETAILS FOR TANK: 05-FB-101 A/B
RASTHRIYA PROJECT 06484
PROJECT No.:
AMMONIUM NITRATE SOLUTION STORAGE (UNIT 05)
VESSEL PROCESS DATA SHEET PROCESS CONDENSATE TANK 05-FB-102
00
22/11/2013
ISSUE FOR PROPOSAL
MSP
JLS
JRF
Rev. No:
DATE
DESCRIPTION
PREPARED BY
CHECKED BY
APPROVED BY
DOCUMENT TITLE PROCESS CONDENSATE TANK DATA SHEET DOCUMENT NUMBER
06484-05-120-DS-0002
REVISION PAGE
1
OF
3
00
This document contains confidential information property of TECNICAS REUNIDAS/ESPINDESA, any reproduction or use of its content, total or partial, including without limitation any of its characteristics patented or able to be patented, it is forbidden and it cannot be reproduced or used without the permission of TECNICAS REUNIDAS and ESPINDESA.
STORAGE TANK PROCESS DATA SHEET Rev.
00
Date
22/11/2013
JOB Nº
06484
UNIT
AMMONIUM NITRATE SOLUTION STORAGE (05)
CLIENT
RCF-GAIL-CIL-FCIL
Checked
JLS
LOCATION
TALCHER COMPLEX, ODISHA (INDIA)
Approved
JRF
DOC Nº
06484-05-120-DS-0002
PAGE
2 OF 3
REV
MSP
REV
Prepared
1
Item Nº:
05-FB-102
2
Service:
PROCESS CONDENSATE TANK
3
Fluid:
PROCESS CONDENSATE (Note 1)
4
Nominal capacity:
106
m3
5
Net Capacity:
95
m3
6
Diameter (ID)
4500
mm
7
Height
7200
mm
8 9
TANK PRESSURE
Quantity:
1
Operating
ATM.
kg/cm2 g
Design
0,03
kg/cm2 g
-0,005
kg/cm2 g
10
Vacuum design
11
Operating
50
ºC
Design
100
ºC
12
TANK TEMPERATURE
kg/cm2 g
13
Operating Press.
14
Operating Temp.
ºC
15
Design Press.
kg/cm2 g
COIL
16
Design Temp.
ºC
17
Nom. Diameter
in
18
Length
m
MATERIAL
19
CORR. ALLOW.
20
Shell / Roof
AISI 304L
0
mm
21
Cladding
-
-
mm
22
Coil
-
-
mm
23 24
Type
25 26
X Conical Roof
Floating Roof
Steam out Conditions:
-
X API
Refrigerated
Short term maximum temperature:
-
Flat
Short term minimun temperature:
-
Conical Pointing Downwards
TANK VENTING DATA:
Conical Pointing Upwards
- Blanketing:
Bottom
27 28 29
Code:
API STD.650
30
Stress Relieve for Process Reasons:
31
Insulation:
-
Type Thickness
32
mm
-
kg /cm2 g
ºC
-
kg /cm2 g
ºC
-
kg /cm2 g
NO
- Max inbreathing rate (Note 4):
kg/h
- Max outbreathing rate (Note 4):
kg/h
- Emergency relief:
Flow (Note 4):
- Relieving conditions:
Temperature:
NOZZLES
33
ºC
kg/h
/MW:
ºC /Pressure:
kg/kmol kg/cm2 g
NOZZLES
34
Nº
Quantity
Size
Service
Type
Nº
Quantity
Size
Service
Type
35
N2
1
4"
PROCESS CONDENSATE OUTLET
RF
M1
1
24"
MAN HOLE IN SHELL
API 650
36
N3
1
4"
OVERFLOW
RF
M2
1
24"
MAN HOLE IN ROOF
API 650
37
N4 22/11/2013
2"
MIN.FLOW RECYCLE
RF
38
N5
1
2"
DRAIN (Note 5)
RF
39
N6
1
3"
VENT (Note 2,3)
BW
40
N7
1
4"
LEVEL TRANSMITTER
RF
41
N8
1
2"
LEVEL TRANSMITTER
RF
42
N9
1
2"
TEMP. GAUGE
RF
43
N10
1
2"
CONDENSATE INLET
RF
44 45 46 47 48 49 50
See general notes on next page.
STORAGE TANK PROCESS DATA SHEET Rev.
00
Date
22/11/2013
JOB Nº
06484
UNIT
AMMONIUM NITRATE SOLUTION STORAGE (05) RCF-GAIL-CIL-FCIL
MSP
CLIENT
Checked
JLS
LOCATION
TALCHER COMPLEX, ODISHA (INDIA)
Approved
JRF
DOC Nº
06484-05-120-DS-0002
PAGE
3 OF 3
REV
Prepared
1
GENERAL NOTES FOR TANK:
05-FB-102
2 3
1. Liquid SG = 0,988 @ 50ºC
4
2. Swan neck and bird screen to be fitted. No other elements which may obstruct the flow area allowed.
5
3. To be confirmed by vendor
6
4. Maximum filling rate: 15 m3/h
Liquid SG= 1,00 @ T amb
7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50
Maximum pumpout rate: 30 m3/h
Tank Vendor to confirm vent size for 1,5 times indicated filling/pump out rates according API 2000. The open drain flow shall be considered. 5. Drawoff Swamp.
RASHTRIYA PROJECT 06484
PROJECT No.:
NITRIC ACID STORAGE, 06
TANK PROCESS DATA SHEET NITRIC ACID STORAGE 06-FB-001 A/B
00
22/11/2013
ISSUE FOR PROPOSAL
FJ
JLS
JR
Rev. No:
DATE
DESCRIPTION
PREPARED BY
CHECKED BY
APPROVED BY
DOCUMENT TITLE NITRIC ACID STORAGE DATA SHEET DOCUMENT NUMBER
06484-06-120-DS-001
REVISION PAGE
1
OF
3
00
This document contains confidential information property of TECNICAS REUNIDAS/ESPINDESA, any reproduction or use of its content, total or partial, including without limitation any of its characteristics patented or able to be patented, it is forbidden and it cannot be reproduced or used without the permission of TECNICAS REUNIDAS and ESPINDESA.
STORAGE TANK PROCESS DATA SHEET Rev.
00
Date
22/11/2013
Prepared
JOB Nº
FJ
06484
UNIT
Nitric Acid Storage (unit 06)
CLIENT
RDF-GAIL-CIL-FCIL
LOCATION
Talcher Complex, Odisha (India)
JRF
DOC. Nº
06484-06-120-DS-001
PAGE
2/3
REV
JLS
Approved
REV
Checked
06-FB-001 A/B Quantity:
1
Item Nº:
2
Service:
3
Fluid:
4
Nominal capacity:
5
Net Capacity:
NITRIC ACID 60% (Note 1) m3
3728
m3
6
Diameter (ID)
17500
mm
7
Height
15500
mm
Operating
8 9
1
NITRIC ACID STORAGE
TANK PRESSURE
Design
Atm.
bar g
0.1
bar g
10
Vacuum design
-0.02
bar g
11
Operating
≤ 50
ºC
Design
80
12
TANK TEMPERATURE
ºC
13
Operating Press.
14
Operating Temp.
-
ºC
15
Design Press.
-
bar g
16
Design Temp.
-
ºC
17
Nom. Diameter
-
in
18
Length
-
m
bar g
COIL
MATERIAL
19 20
-
Shell
CORR. ALLOW.
AISI 304L
-
mm
21
Cladding
-
-
mm
22
Roof
-
-
mm
23 24
Type
25
X Conical Roof
Floating Roof
Steam out Conditions:
-
ºC
-
kPa g
X API
Refrigerated
Short term maximum temperature:
-
ºC
-
kPa g
-
ºC
-
kPa g
26
Bottom
Flat
Short term minimun temperature:
27
NOTE (2)
Conical Pointing Downwards
TANK VENTING DATA:
Conical Pointing Upwards
- Blanketing:
28 29
Code:
30
Stress Relieve for Process Reasons:
API STD.650
31
Insulation:
Type
Not Insulated
Thickness
32
-
-
NO
- Max inbreathing rate :
kg/h
- Max outbreathing rate :
kg/h
- Emergency relief: mm
kg/h
Flow :
- Relieving conditions: Temperature:
NOZZLES
33
/MW:
ºC /Pressure:
kg/kmol kPa g
NOZZLES
34
Nº
Quantity
Size
Service
TYPE
Nº
Quantity
Size
Service
TYPE
35
N1
1
6''
ACID INLET
RF
N11
1
2"
DEMI WATER
RF
36
N2
1
6''
RESERVE
RF
N12
1
2"
SEAL DRAIN
RF
37
N3
1
4''
RECIRCULATION
RF
N13
1
4"
SPARE
RF
38
N4
1
2''
DRAIN
RF
M1
1
24"
MAN HOLE in Roof
API 650
39
N5
1
4''
LEVEL
RF
M2
1
24"
MAN HOLE in Sheel
API 650
40
N6
1
2''
GA-002 RETURN
RF
41
N7
1
6''
ACID OUTLET
RF
42
N8
1
2''
T INSTRUMENT
RF
43
N9
1
10" (Note 6)
VENT (Note 4)
RF
N10
1
6"
OVERFLOW
RF
44 45 46
See general notes on next page.
STORAGE TANK PROCESS DATA SHEET Rev.
00
Date
22/11/2013
JOB Nº
06484
UNIT
Nitric Acid Plant (unit 01)
CLIENT
RDF-GAIL-CIL-FCIL
FJ
Checked
JLS
LOCATION Talcher Complex, Odisha (India)
Approved
JRF
DOC. Nº
06484-01-120-DS-0023
PAGE
3/3
REV
Prepared
1
GENERAL NOTES FOR TANK:
06-FB-001 A/B
2 3
1. Liquid SG = 1.38 @ 10ºC
4
2. Tank bottom with 0.5% slope to N4
5
3. Stainless steel bolt and nuts
6
4. The equipment 06-FA-001A/B is supported over the vent nozzle
7
5. Level connections sizes to be confirmed by instrument department
8
6. To be confirmed
9
7. Equipment 06-FA-002 will be located above nozzle n9
10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44
RASTHRIYA PROJECT 06484
PROJECT No.:
CONDENSATE POLISHING SYSTEM (UNIT 20)
VESSEL PROCESS DATA SHEET POLISHING CONCENTRATE TANK 20-FB-101
00
22/11/2013
ISSUE FOR PROPOSAL
MSP
JLS
JRF
Rev. No:
DATE
DESCRIPTION
PREPARED BY
CHECKED BY
APPROVED BY
DOCUMENT TITLE POLISHING CONCENTRATE TANK DATA SHEET DOCUMENT NUMBER
06484-20-120-DS-0002
REVISION PAGE
1
OF
3
00
This document contains confidential information property of TECNICAS REUNIDAS/ESPINDESA, any reproduction or use of its content, total or partial, including without limitation any of its characteristics patented or able to be patented, it is forbidden and it cannot be reproduced or used without the permission of TECNICAS REUNIDAS and ESPINDESA.
STORAGE TANK PROCESS DATA SHEET Rev.
00
Date
22/11/2013
JOB Nº
06484
UNIT
CONDENSATE POLISHING SYSTEM
CLIENT
RCF-GAIL-CIL-FCIL
JLS
LOCATION
TALCHER COMPLEX, ODISHA (INDIA)
Approved
JRF
DOC. Nº
06484-20-120-DS-0002
PAGE
2 OF 3
REV
MSP
Checked
REV
Prepared
1
Item Nº:
20-FB-101
2
Service:
POLISHING CONCENTRATE TANK
3
Fluid:
AMMONIUM NITRATE SOLUTION (5 g/l)
4
Nominal capacity:
420
m3
5
Net Capacity:
390
m3
6
Diameter (ID)
7500
mm
7
Height
9900
mm
8 9
TANK PRESSURE
12
Operating
ATM
kg/cm2 g
0,03
kg/cm2 g
-0,005
kg/cm2 g
Operating
TANK TEMPERATURE
1
Design Vacuum design
10 11
Quantity:
AMB
Design
ºC
80
ºC kg/cm2 g
13
Operating Press.
-
14
Operating Temp.
-
ºC
15
Design Press.
-
kg/cm2 g
16
Design Temp.
-
ºC
17
Nom. Diameter
-
in
18
Length
-
m
COIL
MATERIAL
19 20
Shell / Roof
21 22
CORR. ALLOW.
304 L
0
mm
Cladding
-
-
mm
Coil
-
-
mm
23 24
Type
25
X Conical Roof
Floating Roof
Steam out Conditions:
-
ºC
-
kg/cm2 g
X API
Refrigerated
Short term maximum temperature:
-
ºC
-
kg/cm2 g
-
ºC
-
kg/cm2 g
26
Bottom
Flat
Short term minimun temperature:
27
NOTE (2)
Conical Pointing Downwards
TANK VENTING DATA:
Conical Pointing Upwards
- Blanketing:
28 29
Code:
API STD.650
30
Stress Relieve for Process Reasons:
31
Insulation:
-
Type -
mm
Nº
Quantity
Size
35
N1
1
2"
36
N2
1
2"
37
N3
1
8" (3)
VENT (4)
BW
38
N4
1
2"
MIN. FLOW RECYCLE 20-GA-001 A/B
RF
39
N5
1
4"
OVERFLOW
RF
40
N6
1
2"
TEMP. GAUGE
RF
41
N7
1
4"
DRAIN
RF
3"
POLISHING CONCENTRATE OUTLET
RF
N8
1
Service POLISHING CONCENTRATE LP DEMI WATER INLET
Service
Type
RF
M1
1
24"
MAN HOLE IN ROOF
API 650
RF
M2
1
24"
MAN HOLE IN SHELL
API 650
1
2"
LEVEL TRANSMITTER
RF
1
2"
LEVEL TRANSMITTER
RF
50
See general notes on next page.
kg/kmol kg/cm2 g
Size
N9
45
/MW:
ºC /Pressure:
Quantity
N10
49
Temperature:
Nº
44
48
- Relieving conditions:
kg/h
Type
43
47
Flow:
NOZZLES
34
46
kg/h (3)
- Emergency relief:
NOZZLES
33
42
kg/h
- Max outbreathing rate (3):
Not Insulated
Thickness
32
NO
- Max inbreathing rate (3):
STORAGE TANKS PROCESS DATA SHEET Rev.
00
Date
22/11/2013
Prepared
JOB Nº
MSP
06484
UNIT
CONDENSATE POLISHING SYSTEM
CLIENT
RCF-GAIL-CIL-FCIL
JLS
LOCATION
TALCHER COMPLEX, ODISHA (INDIA)
JRF
DOC. Nº
06484-20-120-DS-0002
PAGE
3 OF 3
REV
Checked Approved
1
GENERAL NOTES FOR TANK:
20-FB-101
2 3
1. Liquid SG: Max. 1,00 @ 10ºC.
4
2. Tank bottom with 0,5% slope to N7
5
3. Maximum filling rate: 5,5 m3/h
6
Maximum pumpout rate: 4,4 m3/h
8
Vendor shall design the venting system based on 1,5 times these filling / pumpout rates shown, and verified that the design covers
9
the scenario of fire case.
10
4. Swan neck and bird screen to be fitted. No other elements which may obtruct the flow are allowed.
11
5. Tank should be 100% drainable.
12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50