POWER FACTOR CONTROLLER PFR-X/PFR-M
The power factor controllers of the PFR range calculate the active and reactive power in the mains from the measured current and voltage. They also determine if power is being imported or exported. The controllers identify the output of the capacitor stages installed and connect or disconnect them in the optimum manner as required by the actual mains conditions. The controllers consider the frequency of changes in the reactive load and follow the principle of rotational switching. The integrated digital display can show the actual power factor, the mains frequency, the actual tariff, the programmed target power factor, the con-
nected steps. This makes general and specific monitoring of the capacitor bank and its operating conditions possible. In addition to that, PFR-M offers additional information such as detailed information on harmonics, THD, operating temperatures, kWh, kvarh. It also offers the option of operation in two different tariff modes, as well as an optional RS485 modbus, and/or internal data logger. The PFR power factor controller is ready for operation on preset default functions immediately after installation without any modifications or adjustments.
FEATURES PFR-X/PFR-M
DISPLAY OPTIONS PFR-X/PFR-M
- 4-quadrant-operation - automatical identification of the power of connected capacitors - optimized switching - automatic and manual operation - port for external alarm - adjustment of the switching time delay - alarm during insufficient measuring current - zero voltage tripping - TTL port - programmable fan control
- cos phi - connected capacitor stages - No of switching operations per branch to date - delivery of actual power (e.g. during the operation of generators) - alarm during insufficient voltage or current
POWER FACTOR CONTROLLER
Additional features PFR-M: - port for e.g. connection of a tariff switch - separate setting of target and alarm cosphi for two different tariffs - alarm during insufficient measuring current or overcurrent - digital output for e.g. fan control or THD alarm - temperature sensing - optional RS485 Modbus - optional internal data-logger Optional features PFR-X: - programmable fan control (PFR-X-L) - port for connection of a tariff switch (PFR-X-L) - separate setting of target and alarm cosphi for two different tariffs
Additional features PFR-M: - V, Amps, kVA, kW, kvar - mains frequency; THD U, THD I, harmonic voltages U 2.-30., harmonic currents I 2.-30., temperature, kWh, kvarh
PFR Connection Scheme
UM
UB
Alarm
relay
4A
Tariff 2 (PFR-M)
Fan (PFR-M)
load Last
2A K1
K1
K12
A
PFR
B C
K 12
RS 485 Modbus (PFR-M) (optional)
IM L1 L2 L3 N
Operation/control voltage No of output relays(voltage free) Output rating Display elements Operating elements Measuring voltage Measuring current External alarm contact Terminals Fuses Ambient temperature Protection class Mounting position Dimensions(H x W x D) Approval Marks
Order codes Description PFR-X 04 50-530V PFR-X 06 50-530V PFR-X 08 50-530V PFR-X 12 50-530V PFR-M06 50-530V PFR-M12 50-530V
45-65HZ 45-65HZ 45-65HZ 45-65HZ 45-65HZ 45-65HZ
PFR-X
PFR-M
230V 50/60Hz 4, 6, 8, 12 250V, 1500VA, max. 5A LED behind removable front plate 50…530V 0.01…5.0A c/o contact, voltage free, max. 3A cage clamp, max. 2.5mm² to be installed externally (max 4A) –20°C…+ 70°C Front IP 50, Terminals IP 20 no restrictions 144 x 144 x 58 mm
230V 50/60Hz 6, 12 250V, 1500VA, max. 5A LCD with backlight membrane keyboard 50…530V 0.01…5.0A c/o contact, voltage free, max. 3A pluggable screw terminal, max. 2.5mm² to be installed externally (max 4A) –20°C…+ 70°C Front IP 50, Terminals IP 20 no restrictions 144 x 144 x 58 mm
order no. 17236.002-97.6 17236.002-97.7 17236.002-97.8 17236.002-97.9 17236.002-95.4 17236.002-96.4
CE Conformity The controller is declared to conform to the following European Directives: 73/23/EWG Low-Voltage Directive 2004/108/EG EMC directive 93/68/EWG Directive for amendment of directive 73/23/EWG (CE- Mark of Conformity)
POWER FACTOR CONTROLLER
TECHNICAL DATA PFR-X/PFR-M