Engineering data sheet Chapter: Accessories Item: 30272x Page: 1 of 1 Pressure relief General For installation in
Views 161 Downloads 1 File size 67KB
Engineering data sheet
Chapter:
Accessories
Item:
30272x
Page: 1 of 1
Pressure relief General For installation in walls to the fire protected enclosure to allow the excess air to exit the room, when INERGEN is released in the area. The relief incorporates a closing mechanism that provides a seal against the entry of flames and smoke. This is achieved by the use of a special intumescent material that swells at high temperatures. The material has been tested by Warrington Fire Research and can withstand fire for more than 60 minutes. To be installed with the intumescent material towards the unprotected enclosure, flush with the wall and the butterfly valve axis in vertical position.
The components 1. 2. 3. 4. 5.
Duct Wall plate Mesh Butterfly valve Intumescent honeycomb
3
2
1
4
5
Lmin 500 mm
Specifications Duct material: Valve material: Intumescent material:
Item no. 302720 302721 302722 302723 302724 302725 302726 302728
Zinc plated steel Aluminium 63mm Dufalite Fireblack
Area [cm2] 40 65 95 150 250 385 615 1000
Ø [mm] 80 100 125 160 200 250 315 400
Document: 30272x Trykaflastningsspjæld.doc
Product: Inergen
Id:
KP
Rev: 07.08.06
Vølundsvej 17 DK- 3400 Hillerød Tel +45 7022 2769 Fax +45 7023 2769
Lmin [mm] 90 95 105 125 165 210 245 290
1 2 3 4 5 6 7 8 9
Text
Designation Pressure Pressure Pressure Pressure Pressure Pressure Pressure Pressure
relief relief relief relief relief relief relief relief
A040 A065 A095 A150 A250 A385 A615 A1000
3
2