1 © Nokia 2017

FPFH-NPP Training - Topics CONTENT: Unboxing the appliance General Overview The tools you need A little bit about cables Cable installation in various configurations Connection schemes Quick start up Resetting username and password LED output state indication Secure VPN-connection Using the GUI and what you can do with it... 2

© Nokia 2017

2

FPFH-NPP Training - Unboxing

When you receive FPFH‘s, you will get them delivered on a pallet, 16 pieces of them will be on it....

Check the pallet for any damages. Do not accept damaged shipments!

3

© Nokia 2017

FPFH-NPP Training - Unboxing

• •

• •

4

© Nokia 2017 Artesyn Confidential

As usual, take care for „The right side up“ As usual, cut open the adhesive tape on the top of the box without damaging anything inside Put the appliance on a dry even surface. Don‘t forget, there‘s an accessory kit packed with spare rubber parts, make sure you don‘t lose it...

FPFH-NPP Product Overview

The FPFH – NPP module is designed for 19” rackmounted applications and offers a controlled distribution of DC bus voltage with integrated over-current protection.

5

© Nokia 2017

FPFH-NPP Training – Overview of product

Its an outdoor application Width = about 48 cm Height = about 12 cm Depth = about 16 cm

IP65

IP 65 Definition Complete protection from dust, oil and other non-corrosive material Complete protection from contact with enclosed equipment Protection from water, up to water projected by a nozzle against the enclosure from any direction

It has a solid aluminium chassis, and weighs about 7 Kgs.. 6

© Nokia 2017

FPFH-NPP Training – Overview of product

Note: The polarity of the input and output terminals is indicated on the front panel. Reverse polarity protection on Input is implemented.

7

© Nokia 2017

FPFH-NPP Training – Overview of product

KEY ELECTRIC PARAMETERS

SURGE PROTECTION DEVICE (SPD) INTEGRATED Note: In this product, you can not change, or repair the SPD device, once it has tripped

8

© Nokia 2017 Artesyn Confidential

FPFH-NPP Training – The tools you need Tool kit required:

9

© Nokia 2017

FPFH-NPP Training – The tools you need Always strip cable jackets with special tool CS76199.08

There is a lot of complex cable stripping to be done when installing this product and it has to be very precise. That is the reason why you should always use the jacket stripper instead of „just some sort of knife“... 10

© Nokia 2017

FPFH-NPP Training – The tools you need You may want to make yourselves familiar with the Sleeve Expander tool „SES-KN“

You will be using this tool very often when installing this device! 11

© Nokia 2017

FPFH-NPP Training – The tools you need

VERY IMPORTANT!

! Usage of ESD wristband is mandatory.

12

© Nokia 2017

FPFH-NPP Training – The tools you need

User- and Installation manual for the FPFH-NPP..

13

© Nokia 2017

Use this manual at all times as your primary source of reference!

FPFH-NPP Training – A little bit about cables ☺ The amount of cables to be installed for this unit in a very confined space, is so massive, that we have to talk about this a little bit....

14

© Nokia 2017

Not only the amount of cables, but also the bending raidii are something to pay good attention to...

FPFH-NPP Training – A little bit about cables ☺

The user manual has a reference library telling you what type of cable to use „when and where“...

15

© Nokia 2017

FPFH-NPP Training – A little bit about cables ☺

The manual also provides precise information how and in what permitted radii to bend the cables...

16

© Nokia 2017

FPFH-NPP Training – A little bit about cables ☺

Most important, the manual will tell you exactly how to strip each cable and further prepare it for each Input/Output of the device...

17

© Nokia 2017

FPFH-NPP Training – A little bit about cables ☺

Because of some of the cables having specific configuration arrangement, you will also be introduced to the technology of COLD-SHRINK and HEAT-SHRINK TUBING in the manual...

18

© Nokia 2017

FPFH-NPP Training – A little bit about cables ☺ 3-way cold shrink tubelet

19

© Nokia 2017

Heat shrink tubing

FPFH-NPP Training – Cable installation in various configurations

Its possible to install the FPFH-NPP unit in the following configurations:



In EDGE mechanical unit „3U“ EMHA (470316A.xxx)



On a plinth frame base



Vertical, on a mastpole



In a cabinet



In a stack (Units screwed together, on top of one another)



Without anything, just the unit itself...

20

© Nokia 2017

FPFH-NPP Training – Cable installation in various configurations In EDGE mechanical unit „3U“ EMHA (470316A.xxx) and also on a plinth frame..

21

© Nokia 2017 Artesyn Confidential

FPFH-NPP Training – Cable installation in various configurations Vertical, on a mastpole, with plinth..

22

© Nokia 2017

FPFH-NPP Training – Cable installation in various configurations In a cabinet..

23

© Nokia 2017

FPFH-NPP Training – Cable installation in various configurations

See the User Installation manual for details on each cable installation configuration, each section has about 10 pages of illustrated instructions!

You will be shown in every detail how to go about installing the cables in the User Installation Manual! 24

© Nokia 2017

!

FPFH-NPP Training – Connection Schemes

There are several interconnection possibilities for the FPFH-NPP...

25

© Nokia 2017

FPFH-NPP Training – Connection Schemes

26

© Nokia 2017

INTERCONNECTIONS:

FPFH-NPP Training – Connection Schemes

27

© Nokia 2017

INTERCONNECTIONS:

FPFH-NPP Training – Connection Schemes

RJ45 alarm cable

RS485 IN

ALARM FSEB

RS485 OUT

-48V OUT 1

INTERCONNECTIONS:

-48V OUT 3

-48V OUT 5

-48V IN1

Nokia BTS Ethernet cable

HDMI FSEB cable Alarm

-48V OUT 2

Ethernet

User interface for site -48V -48V installation or maintenance OUT IN2 6 (temporary connection)

-48V OUT 4

FPFH

FSEB Alarm Interface Box

RJ45 alarm cable

Ethernet cable

RS485 IN

Alarm

ALARM FSEB

Ethernet

RS485 OUT

-48V OUT 1

Network interface for site installation or remote control

-48V OUT 3

-48V OUT 2

-48V OUT 5

-48V OUT 4

-48V IN1

-48V OUT 6

-48V IN2 FPFH

Ethernet cable

28

© Nokia 2017

Network interface for site installation or remote control

FPFH-NPP Training – Connection Schemes

INTERCONNECTIONS:

29

© Nokia 2017

FPFH-NPP Training – Connection Schemes

RS485 IN

ALARM FSEB

RS485 OUT

HDMI RS 485 cable

-48V OUT 1

INTERCONNECTIONS:

-48V OUT 3

-48V OUT 5

-48V IN1

FlexiSystemModule R4 HDMI FSEB cable

Ethernet cable Alarm

-48V OUT 2

Ethernet

User interface for site -48V -48V installation or maintenance OUT IN2 6 (temporary connection)

-48V OUT 4

FPFH

FSEB Alarm Interface Box

HDMI RS 485 cable

RS485 IN

Alarm

ALARM FSEB

Ethernet

Ethernet cable

RS485 OUT

-48V OUT 1

Network interface for site installation or remote control

-48V OUT 3

-48V OUT 2

-48V OUT 5

-48V OUT 4

-48V IN1

-48V OUT 6

-48V IN2 FPFH

Ethernet cable

30

© Nokia 2017

Network interface for site installation or remote control

FPFH-NPP Training – Connection Schemes

31

© Nokia 2017

INTERCONNECTIONS:

FPFH-NPP Training – Connection Schemes

32

© Nokia 2017

INTERCONNECTIONS:

FPFH-NPP Training – Connection Schemes

FPRB alarm cable

Alarm RS485

Rectifier

RJ45 alarm cable

SNMP or User interface for site installation or maintenance

Rectifier

RS485

Ethernet

Nokia BTS

Cat 5 network cable

-48V OUT

INTERCONNECTIONS:

RS485

Rectifier RS485

FPRB

RS485 Y-cable with HDMI connector RS485 IN

ALARM FSEB

RS485 OUT

-48V OUT 1

-48V OUT 3

-48V OUT 5

-48V IN1

HDMI FSEB cable Alarm

Ethernet

-48V OUT 2

-48V OUT 4

-48V OUT 6

-48V IN2 FPFH

FSEB Alarm Interface Box Ethernet cable Network interface for site installation or remote control

33

© Nokia 2017

FPFH-NPP Training – Connection Schemes

34

© Nokia 2017

INTERCONNECTIONS:

FPFH-NPP Training – Connection Schemes

FPRB alarm cable

Alarm RS485

Rectifier

RJ45 alarm cable

SNMP or User interface for site installation or maintenance

Rectifier

RS485

Ethernet

FlexiSystemModule R4

Cat 5 network cable

-48V OUT

INTERCONNECTIONS:

RS485

Rectifier RS485

FPRB

RS485 Y-cable with HDMI connector RS485 IN

ALARM FSEB

RS485 OUT

-48V OUT 1

-48V OUT 3

-48V OUT 5

-48V IN1

HDMI FSEE cable Alarm

Ethernet

-48V OUT 2

-48V OUT 4

-48V OUT 6

-48V IN2 FPFH

FSEE Alarm Interface Box Ethernet cable Network interface for site installation or remote control

35

© Nokia 2017

FPFH-NPP Training – Connection Schemes

36

© Nokia 2017

INTERCONNECTIONS:

FPFH-NPP Training – Connection Schemes

FPRB alarm cable

Alarm RS485

SNMP or User interface for site installation or maintenance

Rectifier

RJ45 alarm cable

Rectifier

RS485

Ethernet

Third Party BTS

Cat 5 network cable

-48V OUT

INTERCONNECTIONS:

RS485

Rectifier RS485

FPRB

RS485 Y-cable with HDMI connector RS485 IN

Alarm

ALARM FSEB

Ethernet

RS485 OUT

-48V OUT 1

-48V OUT 3

-48V OUT 2

-48V OUT 5

-48V OUT 4

-48V IN1

-48V OUT 6

-48V IN2 FPFH

Ethernet cable Network interface for site installation or remote control

37

© Nokia 2017

FPFH-NPP Training – Connection Schemes

38

© Nokia 2017

INTERCONNECTIONS:

FPFH-NPP Training – Quick Start-Up

Quick-Start... If you want to start up FPFH-NPP, simply apply voltage to the appliance input terminals!

It is not necessary to press any button to power up the unit. As soon as it gets electricity from an external source, it will power up by itself... 39

© Nokia 2017

FPFH-NPP Training – Quick Start-Up

Quick-Start... After power up, all LEDS on the display will flash for 1 second, then go dark again...

40

© Nokia 2017

FPFH-NPP Training – Quick Start-Up

Quick-Start...

All outputs are factory-preset to OFF state. To enable outputs, press the SEL button for 1 second, number 1 will start blinking. This is to show you which output you are adressing.... If you do not SET the output that is blinking (thereby turning it ON), after 30 seconds, the blinking will stop. Should you press the SEL button again, the same output will start to blink for 30 seconds again.

41

© Nokia 2017

FPFH-NPP Training – Quick Start-Up

Quick-Start...

If you press the SEL button a second time in the 30 seconds that it is blinking, you will move on to output number 2. Repeated pressing of SEL will move you through all 6 outputs... After number 6, the display moves back to number 1. Pay attention that the output 2 is below number 1, number 3 is above number 4, etc... 42

© Nokia 2017

FPFH-NPP Training – Quick Start-Up

Quick-Start... Whereever you are, if you press the SELECT button, the LED will blink 1 x per second for 30 seconds and afterwards be permanently lit. You have now set the corresponding output ON... 43

© Nokia 2017

Once the output states are changed, the configuration is stored and will automatically be applied at subsequent power-up!

FPFH-NPP Training – Quick Start-Up

Quick-Start... If you press SELECT on whichever active output you may choose, the LED will blink 1 x per second for 30 seconds, then extinguish. You have now turned the output OFF... Once the output states are changed, the configuration is stored and will automatically be applied at subsequent power-up! 44

© Nokia 2017

Artesyn Confidential

FPFH-NPP Training – LED Output State Indication

LED Behavior

Output State

Possible Reasons

No light

Off

Output configured in „OFF“ state

No light

Appliance turned off

No electricity to appliance

Constant light

Output turned off

Output configured in „ON“ state, either manually or via web interface connection

Slow blinking light

Display pad is in configuration mode

The display pad is in configuration mode

Slow blinking light

Inactive output

The output may be inactive because of periodic configuration via the web interface connector

Fast blinking light

E-fuse tripped

The current set limit has been reached, either because the limit current has been set or the appliance hardware protection has triggered (for instance short circuits)

Note: The table does not reflect the LED states of the ETHERNET connector on the back panel! 45

© Nokia 2017

FPFH-NPP Training – Reset Username and Password

2 1

The following values will be reseted to: • • • • •

46

The IP-Adress to default = „142.120.72.175“ User “admin” to default password = “admin” User “user” to default password = “default” Subnet Mask to default subnet mask = “255.255.255.0” Gateway address to default gateway address = 142.120.72.245”

© Nokia 2017

FPFH-NPP Training – Secure VPN connection

!

!

FPFH-NPP uses unsecured HTTP connections. Connecting the system to a network requires a secured VPN connection. Artesyn is not responsible for any security issues in relation to insufficient secured network access points, which are in use by the end customer. We strongly urge our customers to take care for proper and state of the art security measures on their interfaces. Artesyn does not endorse nor support the content of third party tools related to this topic. Disclaimer: Links to Third-Party web sites or third party tools are provided for user convenience only. Artesyn does not endorse nor support the content of third party links or tools. Artesyn is not responsible for the content or the functionality of a third-party web sites or a third party tools. Privacy, security and quality policies may differ from those practiced by Artesyn. Artesyn does not represent any third party or third party tool. 47

© Nokia 2017

FPFH-NPP Training – Using the GUI

Connecting.. The IP adress of the network settings must be in same range as the IP-Adress of FPFH-NPP

Default IP-Adress = 142.120.72.175 Communication port = 80 (HTTP) Ensure Windows firewall does not block port!

Connect FPFH-NPP with a network cable (Cat5) to a computer...

48

© Nokia 2017

FPFH-NPP Training – Using the GUI

Works with..

Google Chrome v47 .0.2526.73 m (64-bit)

Microsoft Internet Explorer 11

Firefox v42.0 49

© Nokia 2017

FPFH-NPP Training – Using the GUI

Mainpage..

50

© Nokia 2017

There are 4 menus available

FPFH-NPP Training – Using the GUI

Output settings-Turn ON/OFF all outputs To turn everything ON or OFF, pick your choice, the system will ask for confirmation. Upon confirmation, all ON or OFF will be actuated...

51

© Nokia 2017

FPFH-NPP Training – Using the GUI

Output settings- configurate an output

 Actual values are displayed and automatically updated in the top section

Max. 15 characters

 Settings can be applied to additional outputs by checking the boxes in “apply configuration to outputs”

Your choice of settings

 Output mode options are “On”, “Off”, or “Timecontrol”  Timing is based on daily or weekly schedule and time-slots are defined by the user  Output switching parameters are configured at bottom section  “Save” transmits actual settings  You can load the default factory settings via one button click

52

© Nokia 2017

Settings can be applied to other outputs via checkmark Or choose default factory settings

FPFH-NPP Training – Using the GUI

Date- and Time settings.. Please pay attention to the date- and time format. SET will save your inputs. SYNC will set the time and date automatically. The source of the time and date will be the local workstation that you are working on and not a network server!

53

© Nokia 2017

FPFH-NPP Training – Using the GUI

Network settings-Settings Type in your settings

You can change the settings of the IPAdress, Subnet-mask, GatewayAddress and MAC-Adress. Clicking on RELOAD will load the settings into the mask, that where the last ones saved... Default will reset the whole system to default factory values.

The following values will be reseted to:

54

© Nokia 2017

• • • • •

The IP-Adress to default = „142.120.72.175“ User “admin” to default password = “admin” User “user” to default password = “default” Subnet Mask to default subnet mask = “255.255.255.0” Gateway address to default gateway address = 142.120.72.245”

Reset the whole unit to default factory values

FPFH-NPP Training – Using the GUI

Network settings-Security Max. 32 characters

In the security settings you can change your password. Mind that a password can only have a maximum of 32 characters...

55

© Nokia 2017

FPFH-NPP Training – Using the GUI

Network settings-Login/Logout

By clicking LOGIN, you return to the LOGIN of the FPFH-NPP. By clicking LOGOUT, you will be logged out of the system.

56

© Nokia 2017

FPFH-NPP Training – Using the GUI

System settings-Unit Name & Location

You may have a preferred name for your FPFH-NPP unit, or it might make sense from the beginning on, to name the units according to where they are located (i.E.: Oulu 1 or Helsinki 15 etc..) Maximum 15 characters!

57

© Nokia 2017

FPFH-NPP Training – Using the GUI

System settings-Product Info

This window is read-only. Nevertheless, some of the settings (like IP-Adress or subnet-mask) can be changed using functions in the menu, while others cannot be changed at all (as for instance Production Date)

58

© Nokia 2017

FPFH-NPP Training – Using the GUI

System settings-Sytem Reboot

This will completely reboot the system. Please acknowledge, that when the system is restarted, all outputs will be turned OFF by default...

59

© Nokia 2017

FPFH-NPP Training – Using the GUI

System settings-Export Config file Presumably, once you have configured 1 unit by hand, you will want to configure others exactly the same way... For this reason, we have provided you with a function, that enables you to download all the settings of the unit in 1 file. You can then import that file into other units, saving you lots of time...

60

© Nokia 2017

FPFH-NPP Training – Using the GUI

System settings- Import Config File Presumably, once you have configured 1 unit by hand, you will want to configure others exactly the same way... For this reason, we have provided you with a function, that enables you to download all the settings of the unit in 1 file. You can then import that file into other units, saving you lots of time...

The firmware version of the unit you exported the config. file from and the unit you are going to import it to, must be exactly the same! If in one of the units, the firmware version differs from the other, the system will reject the import of the file!

61

© Nokia 2017

Thank you very much for your attention...

62

© Nokia 2017