FLAME ARRESTERS D E FLAGRATION // AT EX CERT I F IE D SAFETY DEVICES THAT PROTECT EQUIPMENT, LIVES & THE ENVIRONMEN
Views 95 Downloads 0 File size 2MB
FLAME ARRESTERS
D E FLAGRATION
//
AT EX
CERT I F IE D
SAFETY DEVICES THAT PROTECT EQUIPMENT, LIVES & THE ENVIRONMENT
D E F L A G R AT I O N F L A M E A R R E S T E R S
//
PAG E 2
Groth Corporation
Groth Corporation, formerly Groth Equipment Corporation, was founded by Edward Groth on August 1, 1960 and incorporated on September 7th that same year. Groth began as a manufacturers’ representative, distributor, and re-manufacturer of pressure relief valves sold to the refining and petrochemical industries. In 1999, Groth Corporation joined Continental Disc Corporation and moved to its current Stafford, Texas manufacturing site in 2002. These two events strengthened Groth’s position as a global leader in low pressure safety solutions. Today, Groth is a global leader in low pressure safety equipment with representatives around the world, providing engineered solutions with uncompromising commitment to customer satisfaction. Groth industrial products are comprised of independent product lines, classified as: Pressure/Vacuum Relief Valves, Blanket Gas Regulators and Flame Arresters.
OUR EXPERTISE & DEVOTION When choosing a solution from Groth Corporation, you can be assured that our expertise and devotion to quality will translate into efficiency and safety, and that our every effort will demonstrate our commitment to provide innovative solutions, quality products, and comprehensive service. We pride ourselves in providing expertise to the following industries: Biogas Processing Chemical Equipment Food & Beverage OEM Oil & Gas Pharmaceutical Transportation Utilities Wastewater as well as many others.
S M A RT
RELIEF...S AFE
S O LU T IO NS ℠
D E F L A G R AT I O N F L A M E A R R E S T E R S
//
PAG E 3
Flame Arrester Overview
Deflagration Flame Arresters are fire safety devices used to protect stored or process media from deflagrations. A deflagration flame arrester can be used on the top of a tank or as an in-line safety device where combustible gases are transported through low pressure pipe lines. Flame arresters are designed to inhibit flame propagation in gas piping systems and to protect low pressure tanks containing flammable liquids. Arresters protect low flash point liquids from external sources of heat and ignition, increasing fire protection and safety.
End-of-Line and In-Line Explanation
Below is an explanation of the differences between End-of-Line and In-Line Flame Arrester products. ISO 16852 section 3.21 End-of-Line Flame Arrester Flame arrester that is fitted with one pipe connection only ISO 16852 section 3.22 In-Line Flame Arrester Flame arrester that is fitted with two pipe connections, one on each side of the flame arrester
S M A RT
R E LIEF...S AFE
S O LU T IO NS ℠
DATA SHEET D E F L A G R AT I O N F L A M E A R R E S T E R S
//
PAG E 4
ALL INFORMATION BELOW ISArrester REQUIRED. Application PLEASE SEE NOTEQuestionnaire ON APPLICATION LIMITS. ATEX Flame Below is an example of the information required in order for us to help you choose the
CUSTOMER: appropriate flame arrester model for your application. The illustration shows how to use
the charts and graphs on the following pages to locate that information. Find the number icon on this page and its corresponding number on page 5.
NEC Methane
D
PROCESS
A
1
Gas Group (choose one): IIA1 NEC IIA IIB2 IIB1 IEC q METHANE q IIA1 X q Pressure D q IIA Pre-Ignition q C
IEC
PROCESS
Gas Group (circle one) C B
IIB3
IIB
IIC
1.05 bara Operational Pressure ________________________ 2
Maximum Pressure Drop
220 C
Operational Temperature 3
________________________
Required Flow
8 mbar ________________________
Maximum Pressure Drop 4
L
Pre-Ignition Temperature
300 Nm /H Air Max AllowRequired WorkingFlow ________________________ Pressure 5 3
INSTALLATION
INSTALLATION
Run-Up Length (L)
Run-Up Length (L)
Flange Size (D)
1.5 m ________________________ 80 mm
Flange Size (D) ________________________
L / (L/D) D Run-Up Length Ratio 6
1500 mm 18.75 80 mm = ________________________
Orientation (choose one): 7 (circle one) Orientation q Vertical q Horizontal X
Vertical
8 Mounting (choose one): q In-Line Location q End-of-Line (circle one) X
In-Line
Horizontal
End-of-Line
Refer to ISO 16852, Section 7.4 Limits for use, for more information on the application limits of flame arresters.
NOTE:
Groth in-line deflagration flame arresters must be installed at or within 10 pipe Definitions: diameters ofLength the source of ignition and areon only gas groups IIA1 / Run-Up (L): pipe length the approved unprotectedfor side of the Methane, pre-ignition pressures at arrester or below 15.7 psia, and pre-ignition flame diagram - tested deflagration with straight pipe) temperatures at or below 140°F. (see Groth end-of-line flame arresters must Run-Up be installed atRatio or within diameters of the end diameter of a vent pipe and are Length (L/D): 10 pipe run-up length divided by pipe only approved for gas groups IIA / D, pre-ignition pressure at or below 14.7 psia (atmospheric), and pre-ignition temperatures at or below 140°F. 10/5/2011
A blank downloadable version of this ATEX Flame Arrester Application Questionnaire is available for your use at grothcorp.com.
S M A RT
RELIEF...S AFE
S O LU T IO NS ℠
D E F L A G R AT I O N F L A M E A R R E S T E R S
//
PAG E 5
How to Use the Charts & Graphs on the Following Pages 8
7
Model 7588 (In-Line//Vertical) SPECIFICATIONS 2
A Width
B Height
in (mm)
in (mm)
2" DN 50
8‐3/4" (222)
14" (356)
3" DN 80
Nominal Size
6
3
1
Approx. Approx. Operational * Maximum Ship. Wt. Ship. Wt. Temperature Operational * Maximum * Gas (Aluminum (Carbon or Run Up Range Pressure Group SS Body) Body) (L/D) psia Lbs Lbs °F (bara) (kg) (kg) (°C)
* Burn Time tBT minutes
15.7 (1.08)
50
IIA1
18 (8)
40 (18)
‐4 to 140 (‐20 to 60)
5
9‐1/2" 16" (241) (406)
15.7 (1.08)
20
IIA1
27 (12)
60 (27)
‐4 to 140 (‐20 to 60)
5
4" DN 100
11‐1/2" 18‐1/4" (292) (464)
15.7 (1.08)
10
IIA1
42 (19)
91 (41)
‐4 to 140 (‐20 to 60)
5
6" DN 150
16‐1/2" 21" (419) (533)
15.7 (1.08)
10
IIA1
92 (42)
184 (83)
‐4 to 140 (‐20 to 60)
5
8" DN 200
21" 25" (533) (635)
15.7 (1.08)
10
IIA1
146 (66)
309 (140)
‐4 to 140 (‐20 to 60)
5
10" DN 250 DN 250
24‐3/4" 30" (629) (762)
15.7 (1.08) (1 08)
10
IIA1
237 (108)
498 (226)
‐4 to 140 (‐20 to 60 ) (‐20 to 60 )
5
12" DN 300
28‐5/8" 32‐1/2" (727) (826)
15.7 (1.08)
10
IIA1
306 (139)
694 (314)
‐4 to 140 (‐20 to 60)
5
* Testing parameters based on ISO 16852
Model 7588 FLOW CAPACITY
100
Pressure Dro op [mbar]
4
60
30
10
6 100
300
600
3000
1000
Flow Rate
[Nm3/H
6000
10000
Air] 5
Application Analysis Model 7588 specifications satisfy requirements: 1, 2, 3, 6, 7, and 8
The pressure drop and flow requirements are checked on the Flow Capacity graph and confirm the 80mm size will satisfy the requirements S M A RT
R E LIEF...S AFE
S O LU T IO NS ℠
30000
PAG E 6
Model 7588 IEC IIA1
F L A M E
A R R E S T E R
PRODUCT TYPE
IN-LINE VERTICAL DEFLAGRATION ARRESTERS
INDUSTRIES
Oil & Gas Chemical Liquid Storage Food & Beverage Wastewater
FEATURES & BENEFITS
TECHNICAL DETAILS
Flame arrester element geometry maximizes flame quenching capability while minimizing pressure drop Proven spiral-wound, crimped ribbon, flame element provides reliable flame protection Modular design allows easy and costeffective flame bank maintenance Drains and instrument ports available upon request Thermocouple is required for ATEX Exterior painting or coating available DIN or ASME/ANSI drilling available
Sizes 2" through 12" Housing standard material: carbon steel (WCB/CS), stainless steel (CF8M/316), aluminum (356/6061) Flame element standard material: 316L stainless steel Other materials available upon request Good for IEC gas group IIA1 (MESG > 1.14 mm) Certified to ATEX in compliance with EN ISO 16852:2010 Certificate #: IBExU12ATEX2018 X
A
B
PAG E 7
Model 7588 (In-Line//Vertical) SPECIFICATIONS A Width
B Height
in (mm)
in (mm)
2" DN 50
8‐3/4" (222)
14" (356)
3" DN 80
Nominal Size
Approx. Approx. Operational * Maximum Ship. Wt. Ship. Wt. Temperature Operational * Maximum * Gas (Aluminum (Carbon or Run Up Range Pressure Group SS Body) Body) (L/D) psia Lbs Lbs °F (bara) (kg) (kg) (°C)
* Burn Time tBT minutes
15.7 (1.08)
50
IIA1
18 (8)
40 (18)
‐4 to 140 (‐20 to 60)
5
9‐1/2" 16" (241) (406)
15.7 (1.08)
20
IIA1
27 (12)
60 (27)
‐4 to 140 (‐20 to 60)
5
4" DN 100
11‐1/2" 18‐1/4" (292) (464)
15.7 (1.08)
10
IIA1
42 (19)
91 (41)
‐4 to 140 (‐20 to 60)
5
6" DN 150
16‐1/2" 21" (419) (533)
15.7 (1.08)
10
IIA1
92 (42)
184 (83)
‐4 to 140 (‐20 to 60)
5
8" DN 200
21" 25" (533) (635)
15.7 (1.08)
10
IIA1
146 (66)
309 (140)
‐4 to 140 (‐20 to 60)
5
10" DN 250 DN 250
24‐3/4" 30" (629) (762)
15.7 (1.08) (1 08)
10
IIA1
237 (108)
498 (226)
‐4 to 140 (‐20 to 60 ) (‐20 to 60 )
5
12" DN 300
28‐5/8" 32‐1/2" (727) (826)
15.7 (1.08)
10
IIA1
306 (139)
694 (314)
‐4 to 140 (‐20 to 60)
5
* Testing parameters based on ISO 16852
Model 7588 FLOW CAPACITY
100
Pressure Dro op [mbar]
60
30
10
6 100
300
600
Flow Rate S M A RT
3000
1000
[Nm3/H
R E LIEF...S AFE
Air]
S O LU T IO NS ℠
6000
10000
30000
PAG E 8
Model 7598 IEC IIA1
F L A M E
A R R E S T E R
PRODUCT TYPE
IN-LINE HORIZONTAL DEFLAGRATION ARRESTERS
INDUSTRIES
Oil & Gas Chemical Liquid Storage Food & Beverage Wastewater
FEATURES & BENEFITS
Flame arrester element geometry maximizes flame quenching capability while minimizing pressure drop Proven spiral-wound, crimped ribbon, flame element provides reliable flame protection Modular design allows easy and costeffective flame bank maintenance Drains and instrument ports available upon request Thermocouple is required for ATEX Exterior painting or coating available DIN or ASME/ANSI drilling available Eccentric design allows for horizontal installation by preventing liquid accumulation
TECHNICAL DETAILS
Sizes 2" through 12" Housing standard material: carbon steel (WCB/CS), stainless steel (CF8M/316), aluminum (356/6061) Flame element standard material: 316L stainless steel Other materials available upon request Good for IEC gas group IIA1 (MESG > 1.14 mm) Certified to ATEX in compliance with EN ISO 16852:2010 Certificate #: IBExU12ATEX2017 X
A
B
PAG E 9
Model 7598 (In-Line//Horizontal) SPECIFICATIONS Nominal Size
A Width
B Height
in (mm)
in (mm)
Approx. Approx. Operational * Burn * Maximum Ship. Wt. Ship. Wt. Time Temperature Operational * Maximum * Gas (Aluminum (Carbon or tBT Range Pressure Run Up SS Body) Body) Group (L/D) psia Lbs Lbs °F minutes (bara) (kg) (kg) (°C)
2" DN 50
13‐3/4" 9‐1/2" (349) (241)
15.7 (1.08)
50
IIA1
31 (14)
69 (31)
‐4 to 140 (‐20 to 60)
5
3" DN 80
15‐3/4" (400)
11" (279)
15.7 (1.08)
20
IIA1
40 (18)
85 (38)
‐4 to 140 (‐20 to 60)
5
4" DN 100
18" (457)
12‐1/2" (318)
15.7 (1.08)
10
IIA1
53 (24)
112 (51)
‐4 to 140 (‐20 to 60)
5
6" DN 150
21" (533)
16‐1/2" (419)
15.7 (1.08)
10
IIA1
111 (50)
216 (98)
‐4 to 140 (‐20 to 60)
5
8" DN 200
25" (635)
20‐1/2" (521)
15.7 (1.08)
10
IIA1
213 (97)
413 (187)
‐4 to 140 (‐20 to 60)
5
10" DN 250 DN 250
30 (762)
24‐1/2" (622)
15.7 (1 08) (1.08)
10
IIA1
306 (139)
622 (282)
‐4 to 140 ( 20 to 60 ) (‐20 to 60 )
5
32‐1/2" 28‐1/2" (826) (724)
15.7 (1.08)
10
IIA1
378 (171)
693 (314)
‐4 to 140 (‐20 to 60)
5
12" DN 300
* Testing parameters based on ISO 16852
Model 7598 FLOW CAPACITY
100
Pressure Dro op [mbar]
60
30
10
6 100
300
600
Flow Rate S M A RT
3000
1000
R E LIEF...S AFE
[Nm3/H
Air]
S O LU T IO NS ℠
6000
10000
30000
PAG E 1 0
Model 7688 IEC IIA
F L A M E
A R R E S T E R
PRODUCT TYPE
IN-LINE VERTICAL DEFLAGRATION ARRESTERS
INDUSTRIES
Oil & Gas Chemical Liquid Storage Food & Beverage Wastewater
FEATURES & BENEFITS
TECHNICAL DETAILS
Flame arrester element geometry maximizes flame quenching capability while minimizing pressure drop Proven spiral-wound, crimped ribbon, flame element provides reliable flame protection Modular design allows easy and costeffective flame bank maintenance Drains and instrument ports available upon request Thermocouple is required for ATEX Exterior painting or coating available DIN or ASME/ANSI drilling available
Sizes 2" through 12" Housing standard material: carbon steel (WCB/CS), stainless steel (CF8M/316), aluminum (356/6061) Flame element standard material: 316L stainless steel Other materials available upon request Good for IEC gas group IIA (MESG > 0.90 mm) Certified to ATEX in compliance with EN ISO 16852:2010 Certificate #: IBExU12ATEX2016 X
A
B
PAG E 1 1
Model 7688 (In-Line//Vertical) SPECIFICATIONS Approx. Approx. Operational * Burn * Maximum Ship. Wt. Ship. Wt. Time Temperature Operational * Maximum * Gas (Aluminum (Carbon or Run Up tBT Range Pressure Group SS Body) Body) (L/D) psia Lbs Lbs °F minutes (bara) (kg) (kg) (°C) 23.2 19 41 ‐4 to 140 50 IIA 10 (1.60) (9) (18) (‐20 to 60)
A Width
B Height
2" DN 50
in (mm) 8‐3/4" (222)
in (mm) 14" (356)
3" DN 80
9‐1/2" 16" (241) (406)
23.2 (1.60)
50
IIA
28 (13)
61 (28)
‐4 to 140 (‐20 to 60)
10
4" DN 100
11‐1/2" 18‐1/4" (292) (464)
17.4 (1.20)
50
IIA
44 (20)
93 (42)
‐4 to 140 (‐20 to 60)
10
6" DN 150
16‐1/2" 21" (419) (533)
17.4 (1.20)
50
IIA
98 (44)
189 (86)
‐4 to 140 (‐20 to 60)
10
8" DN 200
21" 25" (533) (635)
17.4 (1.20)
50
IIA
155 (70)
317 (144)
‐4 to 140 (‐20 to 60)
2
10" DN 250 DN 250
24‐3/4" 30" (629) (762)
17.4 (1.20)
50
IIA
250 (113)
512 (232)
‐4 to 140 (‐20 to 60 ) (‐20 to 60 )
2
12" DN 300
28‐5/8" 32‐1/2" (727) (826)
17.4 (1.20)
50
IIA
324 (147)
712 (323)
‐4 to 140 (‐20 to 60)
2
Nominal Size
* Testing parameters based on ISO 16852
Model 7688 FLOW CAPACITY
100
Pressure Dro op [mbar]
60
30
10
6 100
300
600
Flow Rate S M A RT
3000
1000
R E LIEF...S AFE
[Nm3/H
Air]
S O LU T IO NS ℠
6000
10000
30000
PAG E 1 2
Model 7698 IEC IIA
F L A M E
A R R E S T E R
PRODUCT TYPE
IN-LINE HORIZONTAL DEFLAGRATION ARRESTERS
INDUSTRIES
Oil & Gas Chemical Liquid Storage Food & Beverage Wastewater
FEATURES & BENEFITS
Flame arrester element geometry maximizes flame quenching capability while minimizing pressure drop Proven spiral-wound, crimped ribbon, flame element provides reliable flame protection Modular design allows easy and costeffective flame bank maintenance Drains and instrument ports available upon request Thermocouple is required for ATEX Exterior painting or coating available DIN or ASME/ANSI drilling available Eccentric design allows for horizontal installation by preventing liquid accumulation
TECHNICAL DETAILS
Sizes 2" through 12" Housing standard material: carbon steel (WCB/CS), stainless steel (CF8M/316), aluminum (356/6061) Flame element standard material: 316L stainless steel Other materials available upon request Good for IEC gas group IIA (MESG > 0.90 mm) Certified to ATEX in compliance with EN ISO 16852:2010 Certificate #: IBExU12ATEX2015 X
A
B
PAG E 1 3
Model 7698 (In-Line//Horizontal) SPECIFICATIONS Nominal Size
A Width
B Height
in (mm)
in (mm)
Approx. Approx. Operational * Maximum Ship. Wt. Ship. Wt. Temperature Operational * Maximum * Gas (Aluminum (Carbon or Range Pressure Run Up SS Body) Body) Group (L/D) psia Lbs Lbs °F (bara) (kg) (kg) (°C)
* Burn Time tBT minutes
2" DN 50
13‐3/4" 9‐1/2" (349) (241)
23.2 (1.60)
50
IIA
32 (14)
70 (32)
‐4 to 140 (‐20 to 60)
10
3" DN 80
15‐3/4" (400)
11" (279)
23.2 (1.60)
50
IIA
41 (19)
86 (39)
‐4 to 140 (‐20 to 60)
10
4" DN 100
18" (457)
12‐1/2" (318)
17.4 (1.20)
20
IIA
55 (25)
114 (52)
‐4 to 140 (‐20 to 60)
10
6" DN 150
21" (533)
16‐1/2" (419)
17.4 (1.20)
20
IIA
116 (53)
222 (101)
‐4 to 140 (‐20 to 60)
10
8" DN 200
25" (635)
20‐1/2" (521)
17.4 (1.20)
20
IIA
221 (100)
422 (191)
‐4 to 140 (‐20 to 60)
2
10" DN 250 DN 250
30 (762)
24‐1/2" (622)
17.4 (1.20) (1 20)
20
IIA
320 (145)
635 (288)
‐4 to 140 ((‐20 to 60 ) 20 to 60 )
2
32‐1/2" 28‐1/2" (826) (724)
17.4 (1.20)
20
IIA
397 (180)
836 (379)
‐4 to 140 (‐20 to 60)
2
12" DN 300
* Testing parameters based on ISO 16852
Model 7698 FLOW CAPACITY
100
Pressure Dro op [mbar]
60
30
10
6 100
300
600
Flow Rate S M A RT
3000
1000
R E LIEF...S AFE
[Nm3/H
Air]
S O LU T IO NS ℠
6000
10000
30000
PAG E 1 4
Model 7678 IEC IIA
F L A M E
A R R E S T E R
PRODUCT TYPE
END-OF-LINE VERTICAL DEFLAGRATION ARRESTERS
INDUSTRIES
Oil & Gas Chemical Liquid Storage Food & Beverage Wastewater
FEATURES & BENEFITS
TECHNICAL DETAILS
Flame arrester element geometry maximizes flame quenching capability while minimizing pressure drop Proven spiral-wound, crimped ribbon, flame element provides reliable flame protection Modular design allows easy and costeffective flame bank maintenance Drains and instrument ports available upon request Thermocouple is required for ATEX Exterior painting or coating available DIN or ASME/ANSI drilling available
Sizes 2" through 12" Housing standard material: carbon steel (WCB/CS), stainless steel (CF8M/316), aluminum (356/6061) Flame element standard material: 316L stainless steel Other materials available upon request Good for IEC gas group IIA (MESG > 0.90 mm) Certified to ATEX in compliance with EN ISO 16852:2010 Certificate #: IBExU12ATEX2019 X
A
B
PAG E 1 5
Model 7678 (End-Of-Line//Vertical) SPECIFICATIONS Approx. Approx. Operational * Burn Ship. Wt. A B Ship. Wt. Time Temperature Nominal Width Height * Gas (Aluminum (Carbon or tBT Range Size Group SS Body) Body) in in Lbs Lbs °F minutes (mm) (mm) (kg) (kg) (°C) 2" DN 50
13 (5.90)
18 (8.16)
IIA
22 (10)
37 (17)
‐4 to 140 (‐20 to 60)
2
3" DN 80
15 (6.80)
16 (7.3)
IIA
35 (16)
65 (29)
‐4 to 140 (‐20 to 60)
2
4" DN 100
19.5 (8.85)
21.1 (9.6)
IIA
49 (22)
90 (41)
‐4 to 140 (‐20 to 60)
2
6" DN 150
23.5 (10.7)
24.2 (11)
IIA
105 (48)
168 (76)
‐4 to 140 (‐20 to 60)
2
8" DN 200
28.3 (12.8)
32 (14.5)
IIA
160 (73)
280 (127)
‐4 to 140 (‐20 to 60)
2
10" DN 250 DN 250
30 (13.6) (13 6)
34 (15.4) (15 4)
IIA
244 (111)
417 (189)
‐4 to 140 ((‐20 to 60 ) 20 to 60 )
2
12" DN 300
40 (18.1)
38 (17.2)
IIA
314 (142)
567 (257)
‐4 to 140 (‐20 to 60)
2
* Testing parameters based on ISO 16852
Model 7678 FLOW CAPACITY
100
Tank Pressure [mbar]
60
30
10
6 100
300
600
Flow Rate S M A RT
3000
1000
R E LIEF...S AFE
[Nm3/H
Air]
S O LU T IO NS ℠
6000
10000
30000
S M A R T
R E L I E F . . . S A F E
S O L U T I O N S
℠
GROTH CORPORATION
13650 N. Promenade Blvd. Stafford, TX 77477 Ph (281) 295-6800 | Fax (281) 295-6999 [email protected] | grothcorp.com
THE NETHERLANDS
Energieweg 20 2382 NJ Zoeterwoude-Rijndijk The Netherlands Ph +(31) 71 5412221 | Fax +(31) 71 5414361 [email protected]
CHINA
Room 910, Tower B, COFCO Plaza No. 8 JianGuoMenNei Avenue Beijing (100005), P.R. China Ph +(86) 10 522 4885 | Fax +(86) 10 6522 2885 [email protected]
www.grothcorp.com
INDIA
423/P/1, Mahagujarat Industrial Estate, Moraiya, Sarkhej-Bavla Road, Ahmedabad (GJ) 382213 INDIA Ph +(91) 2717 619 333 | Fax +(86) 10 6522 2885 [email protected]
Continental Disc Corporation reserves the right to alter the information in this publication without notice. // © 2012 Groth Corporation Reproduction without written permission is prohibited.
PRINTED IN U.S.A. TCH0993 // 0812