Bitronics Areva

MEASUREMENTS BiTRONICS 70 Series Measurement System A SUBSTATION AUTOMATION SOLUTION FOR REAL-TIME MONITORING AND EVEN

Views 76 Downloads 3 File size 650KB

Report DMCA / Copyright

DOWNLOAD FILE

Recommend stories

Citation preview

MEASUREMENTS

BiTRONICS 70 Series Measurement System

A SUBSTATION AUTOMATION SOLUTION FOR REAL-TIME MONITORING AND EVENT RECORDING The BiTRONICS 70 Series Measurement System is a substation automation solution designed to satisfy the real-time monitoring and event recording needs of AC network operators. M870D M871

M570D

The BiTRONICS 70 Series Measurement System consists of four component types. These components form a real-time monitoring and event recording system for use in high voltage AC substations. The component types are monitoring and recording IEDs, detached displays, firmware, and software.

M570D

BITRONICS 70 SERIES MEASUREMENT SYSTEM COMPONENTS

M571

M571

> COMPONENT 1: 70 Series Monitoring and Recording IEDs Each Monitoring and Recording IED has pre-arranged channel inputs for different substation elements - feeder, transformer, single bus, and dual bus. There are two families: • The M570 Compact Family design optimizes lower prices for lesser options options are built-in at time of order.

• The M870 Modular Family design has a wider dynamic input range and allows many more options to be added at any time. > COMPONENT 2: 70D Family of Displays The 70D displays give a choice for flush or surface switchboard mounting remotely from 70 Series IEDs.

Customer benefits • Preempt catastrophic events. • Lower investigative expenses. • Reduce your automation investment. • Improve Security. • Lower life-cycle costs. • Protect your investment.

T&D

> COMPONENT 3: 70 Series Firmware 70 Series Firmware is imbedded in all 70 Series IEDs to support functions typically found in : • Disturbance Recorders

• SOE Recorders • Trend Recorders • Revenue Meters • Power Quality Monitors • AC Switchboard Meters • SCADA Transducers > COMPONENT 4: 70 Series Software 70 Series Software is an integrated set of PC-based programs to facilitate implementation and operation of the 70 Series Measurement System.

70 SERIES IED: M870 MODULAR FAMILY This family consists of the following models: > M871 Single Line, Dual Bus IED The M870 Modular Family offers a broad range of configurations that allow field hardware upgrades, with these specs for each IED :

• • • • • • • •

14 Channels 100A fault current 56 DI Max & 24 DO Max 2 Chassis sizes

M871 with V10, P31, P11, H11 & S10 (left to right) mounted in C07A5 chassis

4 Serial Ports Optional Ethernet Port & Modbus Plus 8 AO Min by Optional Analog Output Converter 70 Series Firmware & Software

> M870 Modules The M870 IED can be configured by selecting the following modules and chassis at time of order. These modules can also be added after purchase up to the capacity of the chassis.

M871 in Transformer Application

M871 in Capacitor Bank Application

M871 with Analog Output Converter RS485

2>3

• • • • • • • • • •

V10 Universal Power Supply P20 Modbus Plus P30A - 8/4 Digital I/O P31 - 16/4 Digital I/O H11 - Host Processor A10 - Analog Processor P10 - Ethernet RJ45 10/100 Mbs P11 - Ethernet P10 + 10 Mbs Fiber P12 - Ethernet P10 + 100 Mbs Fiber S10, S11, S12 - Signal Input

C12A8 Chassis - 12 bays with 8 cPCI slots

P20 Modbus Plus Module H11 Module with optional Flash memory up to 256MB

70 SERIES IED: M570 COMPACT FAMILY This family consists of the following models:

Optional Ethernet

> M571 Single Line, Dual Bus IED The BiTRONICS M570 Compact Family of IEDs offers fixed option configurations for less demanding applications with the following specs for each IED:

• • • • • • •

20A fault current Up to 14 Channels

Optional Status In Relay out

Optional 4 DI & 4 DO Optional Ethernet Unlimited AO by Analog Output Converter

M571 with options indicated

70 Series Firmware 70 Series Software

M571 for Distributed Generation with sync check measurement support

M571 for Feeder Application with sync check measurement support

RS485

M571 with Analog Output Converter

IMPROVE SECURITY OF OPERATION BY DESIGN: >> Ensure enterprise-wide retrieval of event files

without exposing relay IEDs to security issues. Using separate IEDs for monitoring and recording insures limited access by foreign intruders to the safety and protection systems as well as verifying the protection system operation. >> If the relay doesn't operate, the cause may never

be known, so an independent IED is essential. >> The common task of setting triggers

can be done without the re-commissioning of the relay.

70 SERIES FIRMWARE The 70 Series Firmware, common to all of the 70 Series IEDs, allows the IEDs to satisfy a number of different applications. The firmware provides the following functions:

• 5 simultaneous recorders • More than 2000 measurements • Instantaneous, Demands, Harmonics to 63rd for Line Current, Bus Voltage L-N, L-L

Each 70 Series IED records and saves the events and trends based on user configured criteria. This criteria may include conditions associated with all the electrical parameters of the IED. This criteria can also include conditions observed by other IEDs connected on the same Local Area Network (LAN). The following gives example graphics derived from the 5 recorder files.

• Instantaneous, Demands, Real, Reactive, Apparent for Bus Power, total, per Ø

• Bus 1 - Bus 2 Voltage Phase Angle and Slip Frequency per Ø

• Multiple ports & protocols • DNP, Modbus, Serial or UDP/TCP, UCA, FTP, Modbus Plus

• Up to 15 remote displays

> Recorders 1 & 2 - Disturbance Voltage and frequency disturbances

• • • •

Two independent disturbance recorders Catch sags and swells in voltage supply Record frequency deviations Enough memory to store more than 8000 events

Example of Frequency Disturbance Example of Voltage Disturbance

PREEMPT CATASTROPHIC EVENTS BY NEVER MISSING A DISTURBANCE: >> Enable utility operation personnel to never miss the

varying length of disturbances on an AC network by employing high fidelity multi-mode recorders with megabytes of non-volatile memory. >> This includes disturbances such as faults, voltage

sags and swells, frequency deviations, power swings, and system planning data.

4>5

> Recorder 3 - WaveForm Record waveform of all signals on any disturbance

• Oscillography recording at 128 samples per cycle • Adequate resolution to record any protection scheme miss-operation or nuisance tripping

• Enterprise-wide retrieval of event files without exposing relay IEDs to security issues

• Set event triggers without recommissioning the relays • Linear recording up to 100 amp symmetrical faults • Enough memory to store more than 1700 events

> Recorder 4 - Trend Oscillography (waveform) captured during a disturbance

Forecast load demand and monitor voltage profile

• Trend recorder • Record system planning and load profiling data for weeks

• Monitor voltage performance for weeks • Enough memory to store more than 400 days of trend data

> Recorder 5 - Sequence of Events Record events in the order they happened

• Sequence of events recorder • Quickly reconstruct the cause and effect of cascading operations

• Time-stamp resolution to 1 microsecond • Enough memory to store 1000 events

Trend any parameter over time. Display in graph and circular chart.

Sequence of Events report

932 933 934 935 936 937 938 939 940 941 942

03-Jun-2003 03-Jun-2003 03-Jun-2003 03-Jun-2003 03-Jun-2003 03-Jun-2003 03-Jun-2003 03-Jun-2003 03-Jun-2003 03-Jun-2003 04-Jun-2003

19:03:18.136489 19:21:30.000000 20:22:08.154353 21:49:56.537266 21:50:35.577024 21:51:05.064116 21:51:30.134855 21:53:08.000000 21:57:52.169387 21:53:08.000000 14:31:10.136090

System Startup, firmware version 01.12.0 Shutdown was caused by watchdog trip System Startup, firmware version 01.12.0 Trigger Waveform Recorder is above 0 threshold Trigger Waveform Recorder is above 0 threshold Trigger Disturbance 1 Recorder is above 0 threshold Trigger Disturbance 2 Recorder is above 0 threshold Shutdown was caused by reset button or Power Cycle System Startup, firmware version 01.12.0 Shutdown was caused by reset button or Power Cycle System Startup, firmware version 01.12.0

70D DISPLAY FAMILY This family consists of the following models:

> M870D Remote Display

• M870D Remote Display • M570D Remote Display

Flush mounted through 4" round hole, separately powered

This Display Family provides a local presentation of any of the measured parameters- the display looks like a BiTRONICS digital meter but is driven remotely from the IED. Multiple values are displayed continuously & scrollable, all fully configurable. Replaces Switchboard meters.

• • • • •

Remotely connected to either a M570 or M870 IED Up to 1000 meters distant Fits 4 inch round hole Daisy-chain 15 from one 70 Series IED Separate power supply

> M570D Remote Display 1. 2.

Pressing any button when the display is scrolling will end the scroll Connect to the front panel RS232 port with a “straight through” cable.

Move up and down through list of screens. If display is scrolling, the first button pressed will stop the scrolling.

Lower cost, flexible surface mount with power from M570 Monitor

• • • • •

Remotely connected to M570 IED 50 feet (15 meters) distant Surface mount Covers 4-inch round hole Covers DIN 92mm openings

Toggle displayscroll On and Off.

Scroll through screens to “Home” screen. If display is scrolling, the first button pressed will stop the scrolling.

M570D Remote Display

M870D display showing straight-through port

LOWER INVESTIGATIVE EXPENSES BY QUICK DIAGNOSIS OF THE CAUSE OF A DISTURBANCE: >> Quickly reconstructs the cause/effect of cascading

operations with enough fidelity and time resolution to troubleshoot any protection scheme miss-operation or nuisance tripping with microsecond accuracy. >>

Operation costs can be lowered further with services from the AREVA T&D Automation Support group.

>> Obtain expert advice from engineers, all with

substation experience.

6>7

70 SERIES SOFTWARE The 70 series software consists of a number of programs combining to provide many features to the user

> Programs

• • • • • •

Installer Launcher Configurator BiVIEW II - Communication Utility Retriever - Automatic file retriever Wavewin BiTRONICS - COMTRADE viewer and file manager

> Features

• Integrated installation • Common software for M870 and M570 IEDs

70 Series Software Launcher

and 70D displays

• Software CD ships free with order

Configurator Display tab from Series 70 Software

BiVIEW Synchro Data View from Series 70 Software

SOFTWARE TOOLS TO LOWER LIFE CYCLE COSTS: >> A complete suite of user friendly software programs

can greatly improve the startup costs of an automation system. >> Firmware upgrade wizards with remote capability

further lower the life cycle costs of these highly advanced IEDs. >> Automatic retrieval of event files and pre-defined

archiving is essential

USE SUBSTATION LANS TO REDUCE YOUR AUTOMATION INVESTMENT: >> Lower your initial investment by employing a LAN-based IED family

that permits the initial purchase of just what you need for the current budgeted project but allows for easy expansion in the future. >> Reduce investment further by employing switchyard grade IEDs

that allow physical distribution into the yards, which provides further wiring cost savings. >> Lower integration costs by incorporating this technology into

GPS IRIG B

WAN

Router LAN

Typical LAN configuration of a BiTRONICS 70 Series Measurement System. M871 IED, M870D Display, M570 IED (4), M570D Display (4)

BITRONICS BRAND: THE ENGINEER’S CHOICE FOR ELECTRIC POWER MEASUREMENTS.

The BiTRONICS 70 Series Measurement System is manufactured at the Measurement Center of Excellence Bethlehem, PA USA Tel.: (+1) 610.997.5100 - Fax: (+1) 610.997.5450

AREVA T&D Worldwide Contact Centre: http://www.areva-td.com/contactcentre/ Tel.: +44 (0) 1785 250 070

www.areva-td.com

Our policy is one of continuous development. Accordingly the design of our products may change at any time. While every effort is made to produce up to date literature, this brochure should only be regarded as a guide and is intended for information purposes only. Its contents do not constitute an offer for sale or advise on the application of any product referred to in it. We cannot be held responsible for any reliance on any decisions taken on its contents without specific advice.

AUTOMATION-L3-70SERIES-BR-10.04-0642-GB - © - AREVA - 2004. AREVA, the AREVA logo and any alternative version thereof are trademarks and service marks of AREVA. BiTRONICS is a registered trademark of AREVA. All trade names or trademarks mentioned herein whether registered or not, are the property of their owners. - 389191982 RCS PARIS - Printed in France - SONOVISION-ITEP